Hubbell DualLite PLD12MI Installation Instructions

Emergency led driver

Advertisement

PLD12MI
EMERGENCY LED DRIVER
1.To prevent high voltage from being present on yellow & orange output leads prior to installation,
converter connector must be open. Do not join converter connector until installation is complete and AC
power is supplied to the emergency driver.
2.This product is for use with an LED lighting load and supplies 12 W constant power
voltage between 0 VDC and 0 VDC in emergency mode for a minimum of 90 minutes.
1
6
3.Make sure all connections are in accordance with the National Electrical Code or Canadian Electrical Code
and any local regulations.
converter connector of the emergency driver before servicing.
5.This emergency driver is for factory installation and
6.This product is suitable for use in damp locations where the ambient temperature is 5ºC minimum, +50ºC
maximum. Product is not suitable for heated air outlets and wet or hazardous locations.
8.Do not install near gas or electric heaters,Do not use outdoors.
9.Use with grounded, UL Listed, damp location rated fixtures and
case should be grounding.
10.The Driver is intended for ordinary locations and for permanent
installation into one or more Listed emergency luminaires.
11
replaceable. Contact the manufacturer for information on service.
12.The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition
13.Do not use this product for other than intended use.
14.Servicing should be performed by qualified service personnel.
15.
Only apply to LED Driver with the output current less than 3.0A. (See electrical data table)
16. Equipment should be mounted in locations and at heights where it will not be subjected to
tampering by unauthorized personnel.
PLD12Ml
with output
(See electrical data table)
field Installation
.
Contains
LiFePO4
Rechargeable Battery.
Must be recycled or
disposed properly.

LED Luminaire Evaluation

This product is suitable for field installation with suitable LED loads including LED luminaires, DC voltage
driven LED replacements for fluorescent lamps and others. There are 4 checks to determine if your luminaire
is eligible for field installation.
1. Ensure the LED load's rated power is greater than or equal to the power output of this emergency LED
driver. This is to ensure that this emergency product will not produce more power than the LED load can
handle, thus ensuring that the LED load will not be damaged when the system is in the emergency mode.
2. Verify that the forward voltage of the luminaire's LED array is within the limits of this emergency LED
voltage of the LED array is commonly designated as Vf and should be found on the
driver. The forward
luminaire markings, in the luminaire
a voltage meter, it may be possible to directly measure the
from the AC driver.
3. Ensure the output current of the LED driver does not exceed 3Amps.This is the current into the blue
wire.
(See electrical data table)
doing the following:
be biven in lumens per watt (lm/w).
b.
load. In many cases the actual lumen output in emergency mode will be greater than this
calculation gives, however it will provide a good estimate for beginning the lighting design of the system.
C. Using the results of this calculation and industry standard lighting design tools, calculate the
a nticipated illumination levels in the path of egress.
Lumens In Emergency Mode = Lumens per Watt of Fixture * Output Power E
(Lumens)
=
________________
________________
NOTE:
This product has been designed to reliably interface with a wide selection of LED loads. . However,
compatibility cannot be guaranteed with all current
of. the end-use system is suggested. Please contact the factory with any questions.
NOTE: After installation, it will be necessary to measure the egress lighting illumination levels to ensure it
complies with national, state, and local code requirements.
Make sure the necessary branch circuit wiring is available. An unswitched
source of power is required. The emergency driver must be fed from the same
branch circuit as
Installation of this emergency LED driver will vary based on the luminaire type, however, generally
follow these steps:
STEP 1
INSTALLING THE EMERGENCY DRIVER
> Disconnect AC power from the LED luminaire.
Mount the emergency LED driver by the mounting tabs using the supplied screws. The luminaire's
>
installaion instructions may provide guidance on the recommended mounting location.
>
The emergency driver with cable conduit is suitable for remote mounting from the luminaire; the emergency driver
without cable conduit is not suitable for remote mounting.
If used in conjunction with an AC driver, this distance is up to half the distance the AC driver manufacturer
recommends remote mounting the AC driver from the LED Load. If used without an AC driver, consult
factory for remote mounting distances .
Installation Instructions
forward voltage is within the limits of this product. Using
voltage across the LED arrays when operating
mergency LED driver
12
(lm/W)
*
(W)
and future LED systems. Compatibility testing

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DualLite PLD12MI and is the answer not in the manual?

Questions and answers

Summary of Contents for Hubbell DualLite PLD12MI

  • Page 1 Installation Instructions LED Luminaire Evaluation PLD12MI This product is suitable for field installation with suitable LED loads including LED luminaires, DC voltage EMERGENCY LED DRIVER driven LED replacements for fluorescent lamps and others. There are 4 checks to determine if your luminaire is eligible for field installation.
  • Page 2 Mounting Height: This product meets or exceeds the NFPA minimum light requirements with all loads, > down to the smallest rated lamp load, at heights up to 7.17ft (2.2m). Many factors influence emergency illumination levels, such as the lamp load selected, luminare design, and environmental factors therefore end use verification is necessary.

Table of Contents