Summary of Contents for Flo-Tite PRO-torQ ELO Series
Page 1
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS ELO Series TO PREVENT POTENTIAL INJURY OR DAMAGE TO PROPERTY, READ THIS MANUAL CAREFULLY AND COMPLETELY. Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 1 of 28...
– Potential pinch point. Equipment connected to or driven by this device may start unexpectedly and may cause personal injury or entrapment in linkage systems. Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com...
We have provided in this document all the tools necessary to determine how the various levels interface to the outside world. If there are any questions, please contact Flo-Tite. Notice: HRSN3 Series actuators are fully assembled, calibrated and tested prior to leaving our factory.
On/Off / Proportional* 24VDC/VAC XTS/TS HRCK3IOM On/Off / Proportional 120-230VAC XTS/TS HRCK3IOM * No 24VDC/VAC can be equipped with HRCL/CD options Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 4 of 28...
All terminals accept 12-18AWG solid/stranded wire. • Notice: Do NOT parallel wire multiple on/off actuators together without utilizing isolation relays. If this is your intention, please contact Flo-Tite for a multiple actuator parallel wiring diagram. Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com...
Torque switches are factory set and are not adjustable. Torque Switch (TS) equipped products have secondary of cams/switches to protect actuator, equipment and processes. Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 6 of 28...
Torque Switch cams shown with lower tripping lower switch (Actuator was driving CCW before this trip) Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 7 of 28...
3. CW position calibration is now complete. limiting device. Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 8 of 28...
3. CCW position calibration is now complete. limiting device. Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 9 of 28...
Shown in Full CW Position Less CW CW Limit Switch CCW Limit Switch Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS Shown in Full CW Position Shown in Full CW Position ELo Rev C ECR 044V www.flotite.com Page 10 of 28...
15. Generate a mid-position signal at the fi eld device to move the actuator off its full CW trip position. 16. Return Field control to automatic mode. 17. Actuator is now commissioned and operational. Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 11 of 28...
14. Unit is now calibrated and is ready to be put into service. No other calibration is necessary. Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 12 of 28...
L2 / Neu L1 / Hot Make all connections to the DECREASE MAIN terminal block ONLY! 20mA Feedback Output DECREASE Feedback Output Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 13 of 28...
16. Unit is now calibrated and is ready to be put into service. No other calibration is necessary. Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 14 of 28...
1 = On, 2 = On Fully CCW upon loss of input signal adjust! adjust! Trims Full DEFAULT CCW FB Out (20mA) Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 15 of 28...
12. Actuator stops at 50% travel, and feedback measuers 12mA (6vdc) +/- tolerance error if any (single decimal). 13. Return Field control to automatic mode. Actuator is now commissioned and operational. Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com...
Reset end-of-travel cams and/or mechanical stops as detailed mechanical stops not position at either in the Adjusting CW/CCW End of Travel section. positioned correctly end of travel Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 17 of 28...
Reset end-of-travel cams and/or mechanical stops as detailed in mechanical stops not position at either the Adjusting CW/CCW End of Travel section. positioned correctly end of travel Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 18 of 28...
10.45/265 6/150 4.85/123 3.11/79 8.50/216 4.73/120 9.45/240 0.669/17 1.38/35 turns 24.5/11 20mm 2.756/70 90° Deep *Consult Flo-Tite for optional ISO patterns Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 19 of 28...
External Mechanical Stop Manual Override Adjustments Handwheel Changeable ISO5211 Mounting System Main Shaft Ball Bearings ISO5211 Double Square Female Drive Socket Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 20 of 28...
2933 1120 1120 4610 4610 1809 1809 7446 7446 2766 2766 11388 11388 4702 4702 19360 19360 7018 7018 28896 28896 Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 21 of 28...
• Torque Switches torque switches have those switches bypassed in the diagrams . • Battery Backup Elo-NA8B/Elo-NB9 12vac On/Off • LCS Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 22 of 28...
• Torque Switches torque switches have those switches bypassed in the diagrams . • Battery Backup Elo-NA8B8/Elo-NB9 12vac Proportional • LCS Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 23 of 28...
• Torque Switches torque switches have those switches bypassed in the diagrams . • Battery Backup Elo-NA8E/Elo-NB9 24vac On/Off • LCS Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 24 of 28...
• Torque Switches torque switches have those switches bypassed in the diagrams . • Battery Backup EloNA8E8/Elo-NB9 24vac Proportional • LCS Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 25 of 28...
• Torque Switches torque switches have those switches bypassed in the diagrams . • Battery Backup Elo-NA8L0/Elo-NB9 230vac On/Off • LCS Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 26 of 28...
• Torque Switches torque switches have those switches bypassed in the diagrams . • Battery Backup Elo-NA8L8/Elo-NB9 230vac Proportional • LCS Back to TOC USE ONLY FLO-TITE GENUINE REPLACEMENT PARTS ELo Rev C ECR 044V www.flotite.com Page 27 of 28...
Page 28