Azure Access BLU-IC2
Hardware Manual
Revision A
March 30, 2021
© 2021 Azure Access Technology, Inc.
All rights reserved. No parts of this work may be reproduced in any form or by any means - graphic, electronic, or
mechanical, including photocopying, recording, taping, or information storage and retrieval systems - without written
permission.
While every precaution has been taken in the preparation of this document, Author assumes no responsibility for errors or
omissions, or for damages resulting from the use of information contained in this document or from the use of programs
and source code that may accompany it. In no event shall the publisher and the author be liable for any loss of profit or any
other commercial damage caused or alleged to have been caused directly or indirectly by this document.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VL-DVDPL and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Azure VL-DVDPL

  • Page 1 Revision A March 30, 2021 © 2021 Azure Access Technology, Inc. All rights reserved. No parts of this work may be reproduced in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping, or information storage and retrieval systems - without written permission.
  • Page 2 BLU-IC2 Hardware Manual 2-Door Intelligent Network Controller by Azure Access Technology...
  • Page 3 UL & ULC Recognized • UL294 • UL294B • UL1076 & ULC/ORD 1076 • UL2610 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 4: Table Of Contents

    6 SPECIFICATIONS ..................33 7 UL COMPLIANCE AS RECOGNIZED PRODUCT ......... 35 8 REVISION HISTORY ..................36 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 5 Figure 3.8: Access Point Wiring ......................19 Figure 4.1: BLU-IC2 HOSTNAME ....................... 20 Figure 4.2: Typical BLU-IC2 Device Cluster ..................31 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 6: Introduction

    There are also several functions that reside within the cluster that will continue to operate independently. 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 7 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 8: Hardware Layout

    Azure Access BLU-IC2 Hardware Manual Part II Hardware Layout Hardware Layout Figure 2.1: BLU-IC2 Diagram 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 9: Terminal Connectors

    TB11-6 (Reader Power) Input Connections TB5-4 Input 1 Input 1 TB5-3 Input 1 Return IN1G 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 10 Common OUT 1 - C Relay K1 Connection Normally TB10-3 OUT 1 - NC Closed 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 11 Interfaces on the BLU-IC2 is programmed by Host software. Refer to Host software documentation to ensure expected configuration. 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 12: Jumpers

    Make sure the SOM is properly installed before powering on the board. 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 13: Micro Usb Otg Port

    Relay OUT 2 (K2): ON = Energized Relay OUT 3 (K3): ON = Energized Relay OUT 4 (K4): ON = Energized 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 14: Function Buttons

    In the case of sudden power failure, the BLU-IC2 has onboard backup power to retain volatile memory and the real time clock. 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 15: Mounting

    One mounting hole is plated for connecting to Chassis (Earth) ground. Figure 2.3: BLU-IC2 Mounting Holes [inches (mm)] 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 16: System Wiring & Setup

    USB (P1) The USB port is 5V and has a current maximum of 500mA. © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 17: Grounding

    24 AWG, shielded twisted-pair. Wiring requirements satisfied by Belden 9841 or equivalent. © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 18: Figure 3.1: Device Wiring

    “Star” Topology - Incorrect “T stub” Topology - Incorrect Figure 3.2: RS-485 Bus Topologies © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 19: Unsupervised Cabinet Tamper & Power Fault (Tb1)

    Wire these inputs with 24 AWG minimum. See “Unsupervised” in Section 3.6.1 wiring diagram. Figure 3.3: Cabinet Tamper & Power Fault Wiring © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 20: Reader Ports (Tb11 & Tb12)

    LED and beeper may not function on the reader. Figure 3.4: BLU-IC2 TTL Reader Wiring © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 21: Rs-485 (Osdp) Readers

    Input wiring requires minimum 22 AWG up to 1,000ft (304.8m) and a maximum of 30 Ohms of loop resistance. © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 22: End Of Line (Eol) Termination Resistors

    Supervised inputs can be configured with Host Software to use different EOL resistor combinations. © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 23: Output Relays (Tb9 & Tb10)

    (for door contact and REX), and one relay output controlling the door strike. Configuration and assignment of the Access Point’s interfaces is done through the Host software. © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 24: Reader

    A Fail-Secure strike uses electrical current to unlock the door; meaning in a power failure situation, the door will default to a locked state. © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 25: Controller Configuration

    See the Communication Connection topic for more information on using the Hostname and the default IP address. © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 26 Click Confirm Security Exception INTERNET EXPLORER: 1. Click continue to this website (not recommended) © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 27 Configuration options can be accessed by clicking on the menu items at the top of the screen. © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 28: Date & Time

    Reset - If reset button is clicked, all previously entered values will be erased and values will be set to default. 4.2.2 Network This section configures the network ports and options CONFIGURATION © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 29 USB-to-Ethernet adapter. Deselecting the checkbox for a network interface disables it. Network interface 2 will default to DISABLED. © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 30: Mail

    Reset - If reset button is clicked, all previously inputted value will be erased and values will be set to default. © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 31: Services

    Reset - If reset button is clicked, all previously inputted value will be erased and values will be set to default. © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 32: Maintenance

    Azure Access technical support representative. To update firmware, follow this procedure: 1. Obtain the new firmware image from Azure and save it to a PC that is network-accessible to the BLU- IC2. 2. Using the PC’s web browser, connect to the BLU-IC2’s web server and navigate to the “Maintenance”...
  • Page 33 7. The webpage will close. When update is finished, the LEDs will return to normal state. The BLU-IC2 will retain its previous configuration including network address. © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 34 4. Confirm when asked if you are sure you want to update from this image. © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 35: Profile

    Member Up to 8 events and manage Anti- Client Passback and other cluster functions © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 36: Figure 4.2: Typical Blu-Ic2 Device Cluster

    Typical configuration of an IC2 Device cluster. The options should be set in the webpage configuration of each device. © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 37: Troubleshooting

    Please contact Apollo Security Support for maintenance if the ASP-2 is not working properly. © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 38: Specifications

    Use 1 %, ¼ W resistors Output Relays (x4) Dry, Form-C contacts. 2A @ 30VDC © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 39 Dim: 8 in. (203.2 mm) W x 6 in. (152.4 mm) L x .75 in. (19.05 mm) H Mechanical Weight: 0.6 lbs. © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 40: Ul Compliance As Recognized Product

    Products are for user with listed access control or proprietary burglar alarm control units/system. © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...
  • Page 41: Revision History

    Content edits per Bill suggestions Evan Z 3/30/2021 New content updates per Evan & Ron suggestion Sean C © 2021 Azure Access Technology, Inc This manual contains confidential information and may only be reproduced or distributed with the written consent of Azure Access Technology...