HIRED-HAND ICS-500 Manual

Environmental controller

Advertisement

Quick Links

ICS
ICS- - 500 Environmental Controller
500 Environmental Controller
With Back-up system and Contactor Panel
Hired Hand, Inc.
1733 Co Rd 68
PO Box 99
Bremen, AL 35033
4801-0102
REV 9/96

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ICS-500 and is the answer not in the manual?

Questions and answers

Summary of Contents for HIRED-HAND ICS-500

  • Page 1 ICS- - 500 Environmental Controller 500 Environmental Controller With Back-up system and Contactor Panel Hired Hand, Inc. 1733 Co Rd 68 PO Box 99 Bremen, AL 35033 4801-0102 REV 9/96...
  • Page 2: Table Of Contents

    Integrated Control System - 500 Table of Contents 1. Purpose ___________________________________________________________________________1 2. Ratings/Specifications________________________________________________________________1 3. Warnings __________________________________________________________________________1 4. Warranty __________________________________________________________________________2 5. Installation_________________________________________________________________________2 5.1. Tools Required ____________________________________________________________ 2 5.2. Instructions _______________________________________________________________ 2 6. Components Description ______________________________________________________________3 6.1. Controller ________________________________________________________________ 3 6.1.1. General Description _____________________________________________________________3 6.1.2.
  • Page 3: Purpose

    Integrated Control System - 500 Purpose The Integrated Control System model 500 (ICS-500) is an eight stage temperature controller intended for use in agricultural enclosures. The ICS-500 incorporates an electronic temperature controller, an eight stage contactor panel, and an independent back-up system.
  • Page 4: Warranty

    2. Insert two screws into wall approximately 18” apart, leaving the heads away from the wall. 3. Hang ICS-500 over the two screws. The top two holes in the side flanges are slotted to allow easy hanging. 4. Finish mounting the unit by securing the sides with eight more screws 5.
  • Page 5: Components Description

    C O N T R O L L E R Automatic mode... Controller Manual Stage Controls The ICS-500 Environmental Controller. Components Description 6.1. Controller 6.1.1. General Description The System 500 Power Curtain controller is an electronic environmental controller which uses knobs for user controls. The controller can operate the following: ð...
  • Page 6: Controls

    6.1.2. Controls 6.1.2.1. Front Panel The following controls are located on the outside of the panel. 6.1.2.1.1.Automatic/Manual The automatic/manual switch is used as its name implies. The Automatic position allows the controller to move the curtains to control temperature. When the switch is in the manual position, the controller will still operate the stages to control temperature, but the curtain can only be moved using the open/close/off switch.
  • Page 7 6.1.2.1.3.Alternate Program Switch PROGRAM (Programa) Each of the 256 stage programs has another “shadow” program. This separate program is provided to make the change between brooding and full house operation. Position A is a program tailored for brooding, whereas program B is for full house operation. 6.1.2.1.4.Target Temperature TARGET TEMPERATURE (Temperatura Optima)
  • Page 8 6.1.2.1.6.OSC High Limit (Enhanced Version Only) OUTSIDE SENSOR CONTROL DECREASE INCREASE (Disminuir) (Aumentar) The Outside Sensor Control (OSC) High Limit knob allows the user to set the temperature for the controller to go into tunnel mode. Tunnel mode involves shutting the main curtain, opening the tunnel curtain, and staging in tunnel fans.
  • Page 9 6.1.2.2.2.Stage On Timer Jumpers A B C Stage 1 To place a stage on the Timer Stage 2 install a two pin mini-jumper on the pins adjacent to the Stage 3 appropriate stage Stage 4 Stage 5 Stage 6 Stage 7 Stage 8 This controller allows you to put any or all stages on the timer.
  • Page 10 6.1.2.2.4.Five/Ten Minute Timer INSTALL JUMPER FOR 5 MINUTE TIMER The controller's internal timer is normally a ten minute timer. However, installing a jumper on this position allows you to set the internal timer to a five minute timer. 6.1.2.2.5.Run Time Adjust This setting tells the controller how long to run the curtain machine when a change is needed.
  • Page 11 6.1.2.2.7.Variable Speed Fan (Enhanced Version Only) 6.1.2.2.7.1.Variable Minimum Adjust If you have the enhanced version of this controller, this potentiometer controls the minimum speed of the variable speed fan. For example, if the variable minimum is set at 50%, the fan will never run below half speed. If you have the basic version of the controller, these switches are not installed.
  • Page 12: Wiring Connections

    the fan will be running at minimum speed when temperature equals 70 degrees. Example: Minimum 40 percent Offset 5 degrees Span 10 degrees Target Temp 75 degrees The variable speed fan will run at 40% when the inside temp is 70 degrees (target - offset). The controller will increase fan speed if inside temperature is rising up until 80 degrees [(target - offset) + span] at which point the fan would be running at 100 percent.
  • Page 13 Integrated Control System 500...
  • Page 14 Integrated Control System 500...
  • Page 15 Integrated Control System 500...
  • Page 16: Back-Up System

    White White Black Yellow Yellow White Orange Orange White Black Brown Brown Green Blue Blue Cap off Purple & Green Black Black with wire nut. Green Green Purple Connection of Curtain Control Circuit and PowerTrak to PVR-H. 6.2. Back-up System The back-up system included with the ICS- is exactly the same unit that comes standard with our Contactor Control System (CCS™).
  • Page 17 30 to 40 degrees. The reminder alert buzzer warns you to check your back-up setpoints every five days. Note: It is important to check your back-up setpoints daily. Connecting Sensor to Back-Up Board P/N 3580-0131 HIRED-HAND ZNR1 ZNR2 Black White Shield...
  • Page 18 Integrated Control System 500...
  • Page 19: Contactor Panel

    Controls 6.3.3.1. Inside Controls There are eight switches on the inside of your ICS-500. Looking into the box they will be on the extreme right hand side on the boards with the large black relays. Each switch has two positions: Heat, and Cool.
  • Page 20: Operation

    Operation 7.1. Curtain Operation 7.1.1. Standard If the controller sees that temperature inside the house is above target temperature it will signal the curtains to open. When the cycle time has elapsed the controller will begin opening the curtain. (The curtain will move for the time set by the Runtime Adjust setting.) If temperature cannot be maintained by the curtains alone, the controller will stage in fans as directed by the stage program.
  • Page 21: Stage Operation

    7.2. Stage Operation Stages may be operated by the controller automatically, by the controller on the timer, or manually by turning the switches on the contactor panel. 7.2.1. Manual To turn a particular stage on, flip its toggle switch to the “ON” position. The red indicator light should turn on.
  • Page 22: Back-Up Operation

    Any time you press the button you reset the five-day timer. Maintenance There are few items on the ICS-500 which require maintenance. This does not mean that maintenance is not important. Remember that the more time you spend making things right, the less time you will spend correcting problems.
  • Page 23 Integrated Control System 500...
  • Page 24 Integrated Control System 500...
  • Page 25 Integrated Control System 500...
  • Page 26: Troubleshooting

    6. If voltages are not correct you need to check and make sure that the 3 conductor cable that connects from controller to PVR-H does not have a short. Disconnect power from the ICS-500 and PVR-H. Then disconnect 3 conductor cable from the PVR-H and ICS500 making sure that they are not touching each other and then measure for a short.
  • Page 27: If Stages Are Not Working At All

    19. Check to see if you can turn the stages on and off with the toggle switches on the front of the contactor panel. 20. Check the voltage on the IN terminal of the System 500 board. 10.5. If Stages are not working at all 21.
  • Page 28 Temperature Vs. Resistance for Hired-Hand Temperature Sensors. Resistance Temp (F) Temp (C) Resistance Temp (F) Temp (C) (Kohms) (Kohms) 165.030 -28.9 39.946 25.0 -3.9 157.128 -18.6 -28.1 39.120 25.7 -3.5 149.644 -17.1 -27.3 38.513 26.2 -3.2 142.552 -15.7 -26.5 37.916 26.8...
  • Page 29 Resistance Temp (F) Temp (C) Resistance Temp (F) Temp (C) (Kohms) (Kohms) 19.065 51.6 10.9 9.956 77.2 25.1 18.884 52.0 11.1 9.869 77.5 25.3 18.616 52.5 11.4 9.741 78.1 25.6 18.352 53.1 11.7 9.614 78.6 25.9 18.179 53.4 11.9 9.530 79.0 26.1 17.503...
  • Page 30: Exploded View/Parts List

    Resistance Temp (F) Temp (C) Resistance Temp (F) Temp (C) (K ohms) (Kohms) 5.326 104.0 40.0 4.454 112.1 44.5 5.262 104.5 40.3 4.402 112.6 44.8 5.199 105.1 40.6 4.334 113.4 45.2 5.137 105.6 40.9 4.284 113.9 45.5 5.076 106.2 41.2 4.217 114.6 45.9...
  • Page 31 Integrated Control System 500...
  • Page 32 Integrated Control System 500...
  • Page 33 Part No. Description 1018-0104 STND_OFF LCBSB-10-01A-RT 1018-2059 STND_OFF SCBS-8N 1039-2031 KNOB 1" dia 1/4 shft indctr 1040-2518 LATCH Panel (CCS) 1042-2693 FUSE HLDR Shock safe Lit fuse 3001-2864 SWTCH SPDT toggle cen off tab 3010-2139 Fuse 10 AMP 1/4X1-1/4 fst act 3010-2528 Fuse 10 AMP 5mmX20mm fsc act 3507-0100...
  • Page 34: Programs

    Chart E Part No. Description 6404-1174 /PCB111 after QA 6404-1185 /PCB115 after QA Chart F Part No. Description 3008-2257 XFMR120V/24V40VA50/60PN_W 3008-2258 XFMR240V/24V40VA50/60PN_W 12. Programs Integrated Control System 500...

Table of Contents