SETUP (CONT.)
Se� ng a unit number
The SETUP key again and the LCD will display the word UNIT.
The factory default is 00. This number can be used to assign the
thermostat to a par� cular HVAC unit. Use the (
assign a UNIT number from 00 to 99 (Figure 5).
Figure 5
Se� ng a zone number
Press the SETUP key again and the LCD will display the word
ZONE. The factory default is 00. This number can be used to
iden� fy each thermostat wired to a zone control panel or when
used in mul� ple stand-along applica� ons . Use the (
keys to assign a ZONE number from 00 to 99 (Figure 6).
If you chose not to change the unit and zone number defaults,
it will not aff ect the thermostat.
Figure 6
Helpful Hint:
If it is necessary to exit the setup menu before all setup func� ons
are completed, simply press the ENTER key and all se� ngs will be
saved. To re-enter the setup menu, press and hold the SETUP key
un� l the word DAMPER appears and then con� nue pressing the
SETUP key to toggle through the func� ons to where you le� off .
Date: 8-2021
Supersedes: NEW
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Installation and Operation Manual
) or ( ) key to
) and ( )
UNI2-VAV Electronic Thermostat
Se� ng the hea� ng limit
Press the SETUP key again and the LCD will display the hea� ng
limit. The factory default is 76° F. Press the (
to change the hea� ng limit se� ng. It is strongly recommended
that the limit not be set above the factory default se� ng
(Figure 7).
Figure 7
Se� ng the cooling limit
Press the SETUP key again and the LCD will display the cooling
limit. The factory default is 68° F. Press the (
to change the cooling limit se� ng. It is strongly recommended
that the limit not be set below the factory default se� ng
(Figure 8).
Figure 8