Page 1
CPS-2M USER’S MANUAL temperature / static pressure computer compatible OPN CLO OPN CLO OPEN OPEN CLOSE CLOSE ADJUST Varifan ® CPS-2M www.monitrol.com...
Page 2
CPS-2M Although the manufacturer has made every effort to ensure the accuracy of the information contained herein, this document is subject to change without notice due to ongoing product development. WARNINGS AND PRECAUTIONS Equipment , probe failure, blown fuses and/or tripped breakers may prove harmful to the contents of the building.
(with static pressure probe model # SPS-1) as a means to control the opening of air inlet baffle/curtains. The CPS-2M provides you with full control over its two stages via the use of an easy to follow display panel. All programmable features can be customized to meet your requirements.
CPS-2M DEFINITION OF TERMS MAIN SET POINT The desired room temperature or pressure. ROOM TEMPERATURE / PRESSURE The actual temperature / pressure of the room. (also called ambient temperature in the text) AIR INLET BAFFLE BOARD/AIR INLET CURTAIN A device which regulates air flow into a building by controlling the opening or closing of an air passage.
Make certain that the unit is mounted right side up with the cable entry holes facing down. The CPS-2M will operate in a temperature range of 42°F - 111 °F (5.5 °C - 44 °C). The enclosure is watertight, it is not splash proof or immersion proof.
CPS-2M Once the CPS-2M is in place, use a screwdriver to remove the six screws holding the faceplate to the housing. 2.3 SWITCH SETTING The CPS-2M is configured for a variety of options via two switches: the line voltage selector switch, and the software settings DIP switch.
2.4.1 - Input power Use a screwdriver to remove cable knock-outs for the installation of cabling to the control panel. Do not apply power to the CPS-2M until all connections have been completed! 2.4.1.1 - 115 VAC Make certain that the line voltage selector switch is set to 115 VAC.
Important: disconnect temperature probe, when the static pressure sensor is used. Connect the static pressure probe to the CPS-2M terminals labeled IN1 (IN2 for sensor 2), PWR, GNA and SHLD as indicated in Figure 3.
Make connections as indicated in Figure 3. 2.7 POWERING UP Before powering up the CPS-2M, attach the faceplate to the casing of the CPS-2M using the four screws previously removed. • Set Selector knob to position (12).
Page 12
CPS-2M Fig.1 Two Actuator Motors (230V) Fig 1a Two actuators connected on the same output Page 12 www.monitrol.com...
Page 13
CHAPTER 2 - INSTALLATION Fig 2 Temperature Probe and Static Pressure Sensor Fig 3 Temperature Averaging Probe Connection Page 13 www.monitrol.com...
Page 14
CPS-2M Fig 5 Main Board: Terminal Blocks, Switch, and Jumpers 1057 Figure 6 Wiring diagram for a three phase motor Page 14 www.monitrol.com...
Control Dials The center dial is the Selector dial and is used to select one of the CPS-2M 12 primary or 10 secondary functions. The dial located to the right of the Selector dial is the Adjustor dial and is used to adjust the setting of each func- tion or to enter secondary function mode.
Page 16
Selector dial from function (12) to any other secondary function. When secondary functions 2 through 11 are selected, the status window displays a blinking value along with a scrolling LED display. Selection of function 12 removes the CPS-2M from the secondary function mode. Page 16 www.monitrol.com...
O, Lo is displayed. If the temperature is higher than 0.20" H O, Hi is displayed. Viewing the ambient temperature / pressure: • rotate the Selector dial to position (1) ambient temperature pressure displayed on the CPS-2M. Page 17 www.monitrol.com...
The main set point temperature / pressure level is displayed on the CPS-2M. Note: The actuator motor may be manually controlled by adjusting the main set point to OPN or CLO thereby causing the air inlet to either remain fully open or closed.
The open run timer setting is displayed on the CPS-2M. Example: The open run timer is set to 30 seconds. When the control determines that the air inlet must open, the com- mand to the motor is sent after the delay set by secondary function (2) has expired.
CPS-2M STAGE 2 CLOSE RUN TIMER The close run timer establishes the period of time that the actuator motor operates when it receives the command to close an air inlet baffle board or air inlet curtain. The close run timer is adjusted in 1 second increments from a minimum setting of 1 second to a maximum setting of 1 minute 59 seconds.
Hi is displayed. Displaying highest temperature pressure recorded: • rotate the Selector dial to position (5) Clearing the high temperature / pressure value • quickly rotate Adjustor dial counterclockwise, then clockwise. CLr will be briefly displayed on the CPS-2M. Page 21 www.monitrol.com...
Viewing the lowest temperature / pressure recorded: • rotate the Selector dial to position (6) Clearing the low temperature / pressure value: • quickly rotate Adjustor dial counterclockwise, then clockwise. CLr will be briefly displayed on the CPS-2M. Page 22 www.monitrol.com...
Viewing the lowest temperature / pressure recorded: • rotate the Selector dial to position (7) Clearing the low temperature / pressure value: • quickly rotate Adjustor dial counterclockwise, then clockwise. CLr will be briefly displayed on the CPS-2M. Page 23 www.monitrol.com...
Hi is displayed. Displaying highest temperature pressure recorded: • rotate the Selector dial to position (8) Clearing the high temperature / pressure value • quickly rotate Adjustor dial counterclockwise, then clockwise. CLr will be briefly displayed on the CPS-2M. Page 24 www.monitrol.com...
The close run timer setting is displayed on the CPS-2M. Example: The close run timer is set to 30 seconds. When the control determines that the air inlet must close, the com- mand to the motor is sent after the delay set by secondary function (3) has expired.
CPS-2M STAGE 1 OPEN RUN TIMER The open run timer establishes the period of time that the actuator motor operates when it receives the command to open an air inlet baffle board or air inlet curtain. The open run timer is adjusted in 1 second increments from a minimum setting of 1 second to a maximum setting of 1 minute 59 seconds.
The main set point temperature / pressure level is displayed on the CPS-2M. Note: The actuator motor may be manually controlled by adjusting the main set point to OPN or CLO thereby causing the air inlet to either remain fully open or closed.
O, Lo is displayed. If the temperature is higher than 0.20" H O, Hi is displayed. Viewing the ambient temperature / pressure: • rotate the Selector dial to position (12) ambient temperature pressure displayed on the CPS-2M. Page 28 www.monitrol.com...
CHAPTER 3 - USER’S GUIDE STAGE 2 ACTUATOR MOTOR DIFFERENTIAL In order to minimize erratic behavior of the actuator motor when ambient room temperature or static pressure is exactly at the main set point, the differential setting separates this ON / OFF threshold into two: one ON threshold and one OFF.
Adjustor dial counterclockwise to decrease the delay, and clockwise to increase it. The delay timer is displayed on the CPS-2M. Example: The open delay timer is set to 1 minute. The actuator motor, when called upon to open the air inlet, will operate after 1 minute has passed.
Adjustor dial counterclockwise to decrease the delay, and clockwise to increase it. The delay timer is displayed on the CPS-2M. Example: The close delay timer is set to 1 minute. The actuator motor, when called upon to close the air inlet, will operate after 1 minute has passed.
/ pressure alarm is signalled. When a high temperature / pressure alarm occurs the alarm relay is activated and the alarm LED lights on the CPS-2M. Alarm When a temperature probe is installed the high temperature / pressure alarm is adjusted in 0.5 degree increments from a minimum setting of 0.0°F (0.0°C) to a maximum setting of 30.0°F...
• rotate the Selector dial to position (6), • rotate the Adjustor dial counterclockwise to decrease the setting, and clockwise to increase it. The low temperature alarm setting is displayed on the CPS-2M. Page 33 www.monitrol.com...
• rotate the Selector dial to position (7), • rotate the Adjustor dial counterclockwise to decrease the setting, and clockwise to increase it. The low temperature alarm setting is displayed on the CPS-2M. Page 34 www.monitrol.com...
/ pressure alarm is signalled. When a high temperature / pressure alarm occurs the alarm relay is activated and the alarm LED lights on the CPS-2M. Alarm When a temperature probe is installed the high temperature / pressure alarm is adjusted in 0.5 degree increments from a minimum setting of 0.0°F (0.0°C) to a maximum setting of 30.0°F...
Adjustor dial counterclockwise to decrease the delay, and clockwise to increase it. The delay timer is displayed on the CPS-2M. Example: The close delay timer is set to 1 minute. The actuator motor, when called upon to close the air inlet, will operate after 1 minute has passed.
Adjustor dial counterclockwise to decrease the delay, and clockwise to increase it. The delay timer is displayed on the CPS-2M. Example: The open delay timer is set to 1 minute. The actuator motor, when called upon to open the air inlet, will operate after 1 minute has passed.
CPS-2M STAGE 1 ACTUATOR MOTOR DIFFERENTIAL In order to minimize erratic behavior of the actuator motor when the room temperature or static pressure is exactly at the main set point, the differential setting separates this ON / OFF threshold into two: one ON threshold and one OFF.
CPS-2M TROUBLESHOOTING SYMPTOM CAUSE and REMEDY − Lo is Temperature or pressure is below continually minimum. displayed − Probe is disconnected or defective. − Hi is Temperature or pressure is above continually maximum. displayed − Probe is short circuited. −...
CPS-2M RECORD FORM STAGE 1 Option User Default Setting Setting Main Set Point 77.0°F 25.0°C 0.02” H Open Run Timer #1 3 seconds Close RunTimer #1 3 seconds Close Run Timer #2 3 seconds Open Run Timer #2 3 seconds Main Set Point 77.0°F...
Page 43
Limited Warranty manufacturered equipment supplied components have gone through rigorous inspection to assure optimal quality of product and reliability. Individual controls are factory tested under load, however the possibility of equipment failure and/or malfunction may still exist. For service, contact your local retailer or supplier. The warranty period shall be for two years from manufacturing date.
Page 44
MAV CPS-2M Ver: 4.1 July 2001 2-wire DC actuator www.monitrol.com...