Rotary Gas Meter
RRM G010/G016/G025/G040/G65
DN050 Class 150 FF
PRECAUTIONS:
Never use the meter as a spool piece during welding.
The meter must be depressurised before filling or adding oil.
Before removing the meter, the oil should be drained.
The meter should be transported and stored with the rotor axis horizontal.
Use only devices with electrical characteristics as recommended (see connection diagram)
The maximum tightening torque on the Pressure and Temperature tapping connections is: 18 Nm
To tighten the swivel nuts; use 2 wrenches to avoid over tighten and damage the meter body.
Avoid mechanical shock during handling and transportation of the meter.
Avoid strong magnet fields close to the meter (particular the index), since they can affect the metrological
performance and/or interrupt the pulse generators.
Seal all plugs and sight glasses to overcome fraud and/or theft of gas.
INSTALLATION INSTRUCTIONS:
1
Check the meter for damage due to transportation and handling. Insure the impellers turn freely and no objects
or contaminations are in the measuring chamber.
2
The piping on the inlet side of the meter must be clean (free of dirt, welding beads and pipe scale). It is recommended to
install a 100 micron filter upstream of the meter. For new installations it is recommended to install a mesh wire screen (250 micron)
for the first weeks of operation.
3
Connect the meter inlet to the gas supply side of the line, insuring the gas flow will be in the same direction as the arrow on
the meter body type plate. For P and T positions see figures below. The pressure reference connection (Pm) is always located
on the INLET of the meter.
Left to Right
Pressure tapping
Temperature tapping
4
Install the meter without piping strain to prevent a binding of the impellers.
Level the meter to within 5mm/m side-to-side and front-to-back.
Quick Installation Manual (EN)
medium:
operating conditions:
mechanical class: M2 - electromagnetic class: E1
Meter can be installed in open air.
Avoid direct sunshine on the meter.
IP-classification of index: IP67
Right to Left
Natural gas (CH4) - gas family: Group 1
p = 0 - 20 barg / t = -25 - 70 °C
Top to Bottom
High frequency pulser
Lubrication Point

Advertisement

loading

Summary of Contents for Raychem RRM G010

  • Page 1 Quick Installation Manual (EN) medium: Natural gas (CH4) - gas family: Group 1 Rotary Gas Meter RRM G010/G016/G025/G040/G65 operating conditions: p = 0 - 20 barg / t = -25 - 70 °C DN050 Class 150 FF mechanical class: M2 - electromagnetic class: E1 Meter can be installed in open air.
  • Page 2 Quick Installation Manual (EN) Tighten flange bolts evenly in a crosswise pattern with a nominal torque of : 40 Nm maximal torque of : 50 Nm Thread Size (T) : 5/8"UNC 16 - 24 mm Thread Length (L) : The specified tightening moments must be observed as much as possible. The values may be exceeded by a maximum of 20%. These values are determined by means of leakage investigations with gaskets and guarantee the proper functioning of the gas meter.

This manual is also suitable for:

Rrm g016Rrm g025Rrm g040Rrm g65