———————————————————— ———————————————————— CONTENTS INTRODUCTION ———————————————————— PRODUCT MANUAL The Q-C and Q-CS units are direct chill ———————————————————— cooler systems designed to provide chilled water by passing water through Safety, Introduction & Specification a stainless steel water coil in the “cold Installation & Commissioning block”.
Page 3
I N T R O D U C T I O N & S P E C I F I C AT I O N...
—————————————————————————————————————————— INSTALLATION AND COMMISSIONING —————————————————————————————————————————— Locate the machine in a suitable enclosure, ensuring that there is suitable ventilation. Care must be taken to ensure that hot air from the exhaust vent is not recirculated into the air intake. This will have an adverse effect on performance and will reduce fridge life. During operation air is drawn into the unit through the ventilation openings in the base (and unit sides for the Q-C20) and then exhausted through the ventilation openings to the rear of the unit.
Page 5
———————————————————— ———————————————————— MODEL: Q-C-20 / Q-C-50 MODEL: Q-CS-20 / Q-CS-50 NOTE: At this stage do not connect the NOTE: At this stage do not connect the unit to the electrical supply. unit to the electrical supply. ———————————————————— ———————————————————— • Using 1/4” PE pipe, connect the •...
———————————————————— where spillage could have ingressed SODA FLOW RATE ADJUSTMENT & UNIT and the area around the base of the CLEANING unit. If necessary, remove the unit and ———————————————————— thoroughly clean around the base and The Soda flow rate is factory set to floor.
———————————————————— If the above are satisfied, ensure that the FAULT FINDING chiller has had adequate time to reach ———————————————————— operating temperature. Prior to any fault finding, please ensure all water connections to the chiller are sound and that the incoming water is turned on. NOTE: When checking electrical Also ensure that all electrical connections connections ensure the unit is...
Page 10
MODEL Q-CS-20/50 —————————————————————————————————————————— SYMPTOM POSSIBLE CAUSE CORRECTIVE ACTION —————————————————————————————————————————— No water Frozen block Temperature probe not fully inserted dispensing into chiller block. Temperature probe out of calibration or faulty. Replace if necessary. PCB Faulty. Replace if necessary. —————————————————————————————————————————— No carbonated No CO2 pressure, Check CO2 bottle, regulator and non- water check by...
Page 11
MODEL Q-CS-20/50 —————————————————————————————————————————— SYMPTOM POSSIBLE CAUSE CORRECTIVE ACTION —————————————————————————————————————————— Poor quality Residue in carbonator After prolonged use, a surface film can carbonation develop within the carbonator can. This can be removed by flushing the system using a solution of citric acid. —————————————————————————————————...
24 hours before a specialist using special equipment. attempting to run the system. Please contact Pure H2O, who will be Failure to observe the above precautions happy to provide a quotation for disposal. could seriously damage the system, and would void any warranty.