Temperatur Control Technology www.hb-therm.ch 2020-09 Page Assembly Instructions M8095-EN Spare part unit board GIF-51 (O/ID T25240-X, T27401-X) Contents Purpose ................... 2 Precondition ................... 2 Procedure ..................2 Product group Thermo-5 ............... 3 Product group Treat-5 and Clean-5..........10 Parts list ..................13...
Assembly Instructions M8095-EN Purpose Replacement of control unit board GIF-51 (A 4) Precondition WARNING! Danger for unauthorized persons! Conversion work may only be carried out by specialist staff who have been trained accordingly. Therefore: – Keep unauthorized persons away from the work area.
Assembly Instructions M8095-EN Product group Thermo-5 Switch off master switch and disconnect from mains supply. Loosen the screws in the front panel and hinge it down. Proceed as follows in order to remove the GIF-51 (A 4): Remove all connectors.
Page 4
Assembly Instructions M8095-EN Voltage selection at X 15 with bridge plug (O/ID T21608): Verify mains voltage ( specification on the nameplate) X 15 Place bridge according ( Fig. 3) ATTENTION! Danger if wrongly connected Wrong voltage selection or wrong connections can...
Page 5
Assembly Instructions M8095-EN Carrying out a Complete reset (Software version prior to SW51-1 0849B) Service \ Support using "Support" user profile (From software version SW51-1 0849B onwards) Service \ Configuration using "Support" user profile NOTICE! From software version SW51-1 0916 onwards, the...
Page 6
Assembly Instructions M8095-EN Additionally with special devices Parameter Special device type OEM Special device OEM version under Service / Configuration as stated on rating plate. Exa. device type HB160ZM1LE1 OEM version OEM type Fig. 9: Configuration special devices 11. Check that the unit is free of pressure (...
Page 7
Assembly Instructions M8095-EN 13. Calibrate the pressure sensor with pressure sensor system (BP 1) Read off the current System pressure actual value under Display \ Actual value. Set the parameter Pressure sensor 1 offset under Service \ Calibrating \ Pressure according to the following calculation: ...
Page 8
Assembly Instructions M8095-EN 15. Flow rate calibration (Software versions prior to SW51-1 0849B) Operate unit in regular mode at 40 °C for at least 10 minutes. Flow rate internal offset parameter in Service \ Calibrating \ Flow rate internally to "5 L/min".
Page 9
Assembly Instructions M8095-EN 16. Check flow rate calibration: After calibration, run the unit for at least 5 minutes at 40 °C in normal mode. Close shut-off valve between feed and return lines. Flow rate switches to 0 L/min and alarm indication ‚Flow rate zero’...
Assembly Instructions M8095-EN Product group Treat-5 and Clean-5 Main switch off, remove the plug from the mains and empty the unit. Loosen the screws in the front panel and hinge it down. Proceed as follows in order to remove the GIF-51 (A 4): ...
Page 11
Assembly Instructions M8095-EN Reconnect mains plug and switch on main switch. NOTE! The unit will maybe perform an automatic software update. NOTICE! If configuration is incomplete, the warning text "Wrong entry" will be displayed. By cancelling the configuration, the user can exit configuration mode and subsequently conduct a Reset complete.
Page 12
Assembly Instructions M8095-EN 10. Configure unit (to Software Version SW51-2 1431) menu using the “Support” user profile. Service \ Configuration NOTICE! When configuring note the following: - Select product group according to table below - Check data on the nameplate...
Assembly Instructions M8095-EN 12. Check calibration pressure sensor Parameter System pressure actual value resp. Main line pressure under Display \ Actual value must be 0 bar ± 0,1. If this is not the case, item calibration pressure sensor must be repeated.