Table of contents 1. Technical Information ......................1 1.1. Coils Information ......................1 1.2. Tool Intented Use ......................1 1.3. Working conditions ..................... 1 1.4. Fan Information ......................2 2. Transport and Storage ......................2 2.1. Transport ........................2 2.2. Storage.........................
1. Technical Information 1.1. Coils Information Standard designs of the product are designed as aluminum fins on copper pipes. As a standard lamella spacing, 2,1mm - 2,5mm is designed. In order to increase efficiency, a staggered pipe array has been made. ...
1.4. Fan Information High efficiency Rosenberg, EBM or equivalent fans should be used. Axial fans working in the suction direction are used for the Industrial Condensers specified in this manual. Voltage value for single-phase fans : 220V / 50Hz. ...
If the desired angle cannot be achieved with a single rope mechanism in the product, it is necessary to carry it with the equipment in the image. If the product is to be transported by forklift, check that the forklift blades are lifted in the correct direction and with the necessary clearance so that they do not damage the device.
3. Installation and Location 3.1. Installation In order for the product to work efficiently, there should be no obstacles affecting the air suction and discharge. Appropriate conditions for device placements are given in the following headings. (*) It should be kept away from heat source or devices blowing high temperature air near the device.
Page 7
In some cases, there may be cases where one side of the device is adjacent to the wall. In such cases, it is beneficial to build a chassis with a height of at least half the width of the device under the device and leave a distance of at least 1.5 times the leg space from the 3 sides.
Page 8
there is a certain opening between the wall and the device, it is useful to close it as in the figure below so that the air flow is not bypassed. If the device is located in a hollow environment: To prevent fan air bypass, the air diverter must be adjusted to the level of the pit. Or the device should be raised with an additional chassis.
3.1.2. Vertical Use of Products If the products are to be used vertically, distances that should be between it and the surrounding wall are indicated in the pictures. In addition, if the device is to be placed in an area surrounded by a wall; The Y distance must be at least L*0.5.
3.2. Installation and Assembly 3.2.1. Leg Installation Care should be taken to use appropriate equipment while mounting the feet . Regardless, care must be taken not to use parts, if additions are to be made, to use parts with the same properties. 3.3.
5. Maintenance and Cleaning For safety purposes before maintenance, the gas in the system should be collected in another place and the inlet and outlet valves, if any, should be closed to prevent possible serious injuries and deaths from being disconnected from the system. Since regular maintenance and cleaning will extend the life of the product, it is necessary to establish and follow the maintenance and cleaning period.
(*)Cleaning the lamella surface should be done against the direction of air suction. For this, the fans must be disconnected from the electrical connection and removed. Example of cleaning with water is given below. Check the First Run procedure after all maintenance work is finished 6.