Goodman MEC96 Series Instruction Manual page 25

Hide thumbs Also See for MEC96 Series:
Table of Contents

Advertisement

Y
C
Remote Condensing Unit
(Single-Stage Cooling)
Thermostat - Single -Stage Heating with Single-Stage
NOTE: To apply a single-stage Heating Thermostat, the thermostat
selector switch on the Integrated Control Module must be set on
single-stage.
Y
C
Remote Condensing Unit
(Single-Stage Cooling)
Thermostat - Two-Stage Heating with Single-Stage Cooling
Y2
Y
Y2
Remote Condensing Unit
(Two-Stage Cooling)
Thermostat - Two-Stage Heating with Two-Stage Cooling
Thermostat Wiring Diagrams
Single-Stage Heating Thermostat
Application
A single-stage thermostat with only one heating stage may be
used to control this furnace. The application of a single-stage
thermostat offers a timed transition from low to high fire. The
furnace will run on low stage for a fixed period of time before
stepping up to high stage to satisfy the thermostat's call for
heat. The delay period prior to stepping up can be set at
either a fixed 10 or 20 minute time delay or a load based
variable time between 1 and 12 minutes (AUTO mode). If
the AUTO mode is selected, the control averages the cycle
times of the previous three cycles and uses the average to
determine the time to transition from low stage to high stage.
R
Furnace
R
Integrated
Control
Module
Cooling
Figure 34
R
Furnace
Integrated
R
Control
Module
Figure 35
W1
W2
Furnace
W1
W2
Integrated
Control
Module
Figure 36
PCBBF139 CONTROL BOARD
SWITCH
PURPOSE
GROUP
1 STG STAT 10 min delay
Thermostat
S3
Setup
1 STG STAT 20 min delay
Heating
Fan Off
S3
Delay
* Factory Setting
Fossil Fuel Applications
This furnace can be used in conjunction with a heat pump
in a fossil fuel application. A fossil fuel application refers to
a combined gas furnace and heat pump installation which
uses an outdoor temperature sensor to determine the most
cost efficient means of heating (heat pump or gas furnace).
A heat pump thermostat with three stages of heat is required
to properly use a two-stage furnace in conjunction with a heat
pump. Refer to the fossil fuel kit installation instructions for
additional thermostat requirements.
Strictly follow the wiring guidelines in the fossil fuel kit instal-
lation instructions. All furnace connections must be made
to the furnace two-stage integrated control module and the
"FURNACE" terminal strip on the fossil fuel control board.
Twinning
Using the "TWIN" terminals and proper wiring enables two
*MEC96 furnaces of the same model and size to be twinned.
Twinning allows simultaneous operation of two furnaces and
forces the indoor blower motors of each furnace to operate
synchronously into a common duct system. Using the twin-
ning function will require only field installed wiring with no
external kits or parts.
·
The staging DIP switches and speed tap DIP
switches must be set the same on both furnaces.
NOTE: Each furnace must be connected to it's own
115 VAC power supply. The L1 connection to each
furnace must be in phase (connected to circuit
breakers on the same 115 VAC service panel phase
leg). To verify that the furnaces are in phase, check
from L1 to L1 on each furnace with a voltmeter. If
the furnaces are in phase, the voltage between both
furnaces will be ZERO.
25
DIP SWITCH
FUNCTION
1
2
2 STAGE STAT
OFF
OFF
ON
OFF
ON
ON
AUTO
OFF* ON*
90
120
150
180
3
4
OFF
OFF
OFF
ON
ON* OFF*
ON
ON