Fortress Technologies LI 1.3K Quick Start Manual

Replacing the batteries

Advertisement

Replacing the Batteries in the Fortress LI 1.3K and LI1420
This FTS describes how to replace the batteries in the Fortress LI 1.3K and LI1420. The battery replacement will take
about 40 minutes.
Batteries should be replaced by a qualified technician. If you have any questions or problems, please call
Powerware Global Services at 1-800-356-5737 (U.S. and Canada only).
To replace the batteries, you will need the following:
Tools Needed - Use Insulated Tools:
Phillips Screwdriver
meters
5/16" Open End Wrench
Before you go on to Section 1, read the important safety warnings on the next page.
1.
Removing the Fortress Cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.
Removing the Batteries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3.
Replacing the Batteries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
4.
Replacing the Fortress Cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS
This publication contains important instructions that should be followed during battery replacement.
The batteries used in this system are capable of producing dangerous voltages and high
currents. They may cause severe injury if terminals are shorted together or to ground
(earth). Extreme care must be taken to avoid electrical shock and burns from contacting
battery terminals or shorting terminals during battery replacement.
Powerware batteries come with a one-year warranty. Using batteries not supplied by
Powerware invalidates any Powerware Service agreement.
A qualified technician who is familiar with the Fortress should replace the batteries. The
technician must take these precautions:
1. Protective clothing and eye wear must be worn. Batteries contain caustic acids and toxic
Electrical Tape
Wooden dowel about 7 inches long or wooden pencil
materials and can rupture or leak if mistreated. Remove rings and metal wristwatches or other
Optional torque wrench calibrated in inch pounds or Newton
Contents Index
WARNING
1
FTS 611
June 30, 1992

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LI 1.3K and is the answer not in the manual?

Questions and answers

Summary of Contents for Fortress Technologies LI 1.3K

  • Page 1 June 30, 1992 Replacing the Batteries in the Fortress LI 1.3K and LI1420 This FTS describes how to replace the batteries in the Fortress LI 1.3K and LI1420. The battery replacement will take about 40 minutes. Batteries should be replaced by a qualified technician. If you have any questions or problems, please call Powerware Global Services at 1-800-356-5737 (U.S.
  • Page 2 jewelry. Don’t carry metal objects in pockets where thy can fall into the UPS. 2. Tools must be insulated so that they will not short battery terminals. At no time can a tool be allowed to short a battery terminal to another battery terminal or to the UPS cabinet. Do not lay tools or metal parts on top of batteries.
  • Page 3 Figure 2 7. Disconnect the negative cable. (See Figure 2 for the cable’s location.) NOTE: Disconnect the gray cable attached to the negative cable also. Put a piece of electrical tape over the metal ends of the black and gray cables so they cannot accidentally touch another metal part.
  • Page 4 CAUTION Make sure that the terminals do not touch the cabinet or any metal part. Assume that the old batteries are fully charged, and use the same precautions you would use when handling new batteries. Batteries contain lead. Dispose of the old batteries properly. Do not dispose of a battery or batteries in a fire;...