Portable Commissioning Tool Pro 1 Safety Notices (Please be sure to abide them) WARNING: If not abide them strictly, it may cause severe damage to the unit or the people. NOTE: If not abide them strictly, it may cause slight or medium damage to the unit or the people.
Portable Commissioning Tool Pro 2 Wiring Instructions Fig.2.1 Parts of Controller ① ② ③ ④ ⑤ Touch Rear cover Short Long Adapter Name screen of connection connection board controller controller wire wire Quantity Unit: mm Fig.2.2 Outline Dimension...
Portable Commissioning Tool Pro 2.1 Requirements of Operation Environment Never operate this product in the following surroundings: (1) Places with corrosive gas or serious dust, salt mist or oil smoke; (2) Wet and damp places or places with direct sunlight; (3) Places near high temperature objects or places where units might be splashed by water.
Page 7
Portable Commissioning Tool Pro Fig.2.3 Connected with IDU Network of CAN Comunication Unit Fig.2.4 Debugger Interface in IDU Mainboard of CAN Comunication Unit...
Page 8
Portable Commissioning Tool Pro Method 2: Connect with ODU network of CAN comunication unit Fig.2.5 Connected with ODU Network of CAN Comunication Unit Fig.2.6 Debugger Interface in ODU Mainboard of CAN comunication unit...
Page 9
Portable Commissioning Tool Pro Wiring instructions: (1) This product is applicable to multi VRF units, connectable with IDU network or ODU network. (2) If this product is to be connected with IDU network, connect according to Fig.2.3. This product can connect with any one indoor unit in series. During connection, one end of 4-core long connection wire is connected with COM interface of this product;...
Page 10
Portable Commissioning Tool Pro 2.2.4 RS485 AC Unit(U-match) Wiring Methods Fig.2.7 Connected with RS485 AC Unit Network Fig.2.8 Interface in IDU Mainboard of RS485 AC Unit Wiring instructions: (1) This product is applicable to the RS485 AC unit and can be connected to the unit network through the IDU;...
Page 11
Portable Commissioning Tool Pro 2.2.5 RS485 Water Heater Unit Wiring Methods Fig.2.9 Connected with RS485 Water Heater Unit Network Wiring instructions: (1) This product is applicable to RS485 water heater unit, which can be connected to the unit network through the wired controller; (2) When the product is connected to the network through the wired controller, connect according to Fig.2.9.
Portable Commissioning Tool Pro 3 Display and Operation Instructions 3.1 Unit Type Selection Fig.3.1 Unit Type Selection Page This product supports CAN communication unit(Multi-VRF), RS485 AC unit(U-match), RS485 Water Heater three types of units; after the product is powered on, automatically determine the connected unit type, without the user to manually select.
Portable Commissioning Tool Pro NOTE: The homepages of the three unit types are slightly different. Fig.3.2 shows the home page of the CAN communication unit. Name Instructions When the controller is connected with communication ① System time network, current day, hour, minute, a.m./ p.m.(12-hour clock) will be display;...
Portable Commissioning Tool Pro 3.4 Buttons Operation Instructions This product uses a capacitive touch screen so that user can operate the units by just touching the screen. Buttons on the screen are presented in the following ways: (1) Icon Icon button can be operated directly. See section 3.3 for more details. (2) Text Press Text button to enter corresponding page;...
Page 15
Portable Commissioning Tool Pro 4.1.2 ODU Status On the home page of CAN communication unit, press to enter into viewing ODU status of CAN communication unit. Fig.4.2 CAN Communication Unit Viewing ODU Parameters NOTE: When the module has error, click at the right lower corner to enter into viewing module error.
Page 16
Portable Commissioning Tool Pro NOTE: ① Note: When the indoor unit of current system has error, click at the right lower corner to enter into viewing IDU error; ② Select the indoor unit for viewing through clicking at the right upper corner on this page; ③...
Page 17
Portable Commissioning Tool Pro Fig.4.5 CAN Communication Unit Unit Control Select the indoor unit for controlling through clicking at the right upper corner on this page. When you need to control indoor unit, after finishing operating mode, temperature and other parameters, click control button to release control data.
Page 18
Portable Commissioning Tool Pro (5) Swing setting Pressing the button Left-Right Swing or Up-Down Swing or can turn on or off the swing function. NOTE: Swing types for indoor units of different series are not all the same. (6) E-Heater enable This feature is always disabled.
Portable Commissioning Tool Pro Fig.4.7 CAN Communication Unit IDU Program List Fig.4.8 CAN Communication Unit IDU Program Upgrade File Information WARNING: ① Please ensure the correctness of the program file, otherwise the upgrade product will not be used; ② During the program upgrade process, please keep the product powered on.
Page 20
Portable Commissioning Tool Pro Fig.4.9 RS485 AC Unit Viewing ODU Parameters 4.2.2 IDU Status On the home page of RS485 AC unit, press to enter into viewing IDU status of of RS485 AC unit. Fig.4.10 RS485 AC Unit Viewing IDU Parameters 4.2.3 Unit Control On the home page of RS485 AC unit, press to enter into the page of...
Portable Commissioning Tool Pro Fig.4.11 RS485 AC Unit Unit Control 4.2.4 Project Setting On the home page of RS485 AC unit, press to enter into project setting interface of RS485 AC unit. Fig.4.12 RS485 AC Unit Project Setting NOTE: The IDU program upgrade, the ODU program upgrade, and the system time setting are set to the reserved function.
Page 22
Portable Commissioning Tool Pro Fig.4.13 RS485 Water Heater Viewing ODU Parameters 4.3.2 Wired Controller Parameters On the home page of RS485 Water Heater, press to enter into viewing Wired Controller Parameters of RS485 Water Heater. Fig.4.14 RS485 Water Heater Viewing Wired Controller Parameters 4.3.3 Project Setting On the home page of RS485 Water Heater, press to enter into project...
Portable Commissioning Tool Pro Fig.4.15 RS485 Water Heater Project Setting 4.4 Controller Setting There are three entrances in this product, which are respectively on the project setting page of CAN communication unit(Multi-VRF), RS485 AC unit(U-match), RS485 Water Heater. On the project setting page, click to enter the controller setting page.
Page 24
Portable Commissioning Tool Pro Controller setting includes: (1) Sound, temperature unit Press the button to select one kind of setting. (2) Backlight setting Pressing this button can set the timeout period of screen backlight. Screen will be shut off and this product will enter sleep mode when the timeout period is over. Pressing backlight degree can adjust the backlight degree.
Page 25
Portable Commissioning Tool Pro Fig.4.18 Program Upgrade File Information Click the OK button to enter the program upgrade; otherwise the program will not be upgraded. WARNING: ① Please ensure the correctness of the program file, otherwise the product will be unusable; ②...
Portable Commissioning Tool Pro Fig.4.19 USB Device Switch Page WARNING: ① The storage space of the product stores the configuration files and other files necessary for the operation of the product. After being deleted or other changes, the unit may fail to start, operate abnormally, etc.;...