INSTALLATION CHECKLIST Please Check or fill out as Completed PIPING CONNECTIONS Ensure both vapor and liquid lines are fully insulated separately with at least ½” wall insulation. Ensure the liquid line filter drier is installed near the air handler, and insulated as well. If a vertical riser of 10’ or more is present on the line set, the line set must be properly trapped to prevent oil slugging to the compressors; good practice in any riser. When making brazed connections, trickle nitrogen through the system (e.g. 2 PSI) to maintain clean braze joints and eliminate carbonization inside the piping during the braze process. The Acadia system comes pre‐charged with 50 PSI of dry nitrogen. This can be used for nitrogen trickling by cracking the service valves slightly. AIR HANDLER Install indoor air handler, ensuring proper duct sealing, insulation & distribution. Ensure all registers, supply and return, are open and unblocked. Ensure a duct flex connector is used to eliminate vibration transmission to the home. Ensure a proper air filter is installed on the return side of the air handler. Ensure condensate drain is installed properly, and trapped. Run 10‐conductor (minimum), 18 AWG control wiring from air handler to the thermostat, and from air handler to outside condenser unit. Connect control wiring following color codes provided in the install manual, Appendix B. Disconnect the low‐voltage leads from the transformer provided in the air handler from the air handler control board 24 VAC and Common terminals. Line‐voltage leads to the transformer must remain connected to power the ECM blower motor. Connect 24VAC and 24C provided from outdoor unit to the ¼” terminals labeled COM and 24VAC on the indoor AHU control board (seen in Appendix A, FIG1). Ensure the electrical service to the air handler is adequate for both the air handler and electric heat kit, if one is installed, per NEC and/or local codes. Ensure appropriate electrical disconnect size is installed, per NEC and/or local codes. Ensure the HP/AC jumper on the air handler control board is set to HP (Heat Pump). If an electric heat kit is installed, ensure the HEAT/NO HEAT Jumper on the air handler control board is set to the HEAT side. Leaving this jumper on NO HEAT disables all auxiliary heat relays. Set airflow jumpers in air handler in accordance with Appendix A. THERMOSTAT Install thermostat in a location where it will not be directly exposed to conditioned air or drafts from doors and/or windows. Insulate between the base plate of the thermostat and the wall to prevent drafts from affecting the thermostat. Ensure that a jumper between W2 and W/E is not installed on the thermostat. Ensure that a jumper between RC and RH is installed on the thermostat. Configure the thermostat’s installer configuration menu as indicated in the installation manual, Appendix A: ‘Thermostat Settings’. ...
Page 5
INSTALLATION CHECKLIST OUTSIDE CONDENSER UNIT Ensure proper clearances are observed around the unit in accordance with Appendix D in the installation manual, making sure to provide appropriate space for accessibility to the compressor compartment’s access panel (30 inches minimum). Ensure condenser is placed on appropriate snow stands (not blocks, sleepers, etc.) per climate region with a minimum of 12” clearance to ground. Ensure outdoor unit is level. Ensure the outdoor coil’s drainage holes are not obstructed, providing full drainage runoff during the defrost cycles. Check factory tubing to ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to distributor tubes on both indoor and outdoor coils. Ensure transformer is wired appropriately for applied line voltage. For correct wiring, see Line Voltage diagram in Appendix B. Unit is factory wired for 230VAC. Ensure the 10 conductor, 18 AWG control harness has been correctly wired between the thermostat, indoor air handler, and outdoor unit, following color codes and schematics provided in Appendix B. Ensure the electrical disconnect is properly sized for the outdoor unit, per NEC and/or local codes. Ensure all electrical connections are weather tight. Ensure all cabinet and electrical fasteners are secure. Shipping vibration can loosen connections. Ensure control wiring is not chaffing/grommet is installed. Charging the System Ensure both vapor and liquid service valves are open and back‐seated. Ensure system has been properly evacuated to at least 500 microns. A triple evacuation is the preferred method for a clean installation. Ensure the R‐410A INITIAL CHARGE is weighed in as a liquid through the 3/8” service valve port inside the compressor compartment. FINAL CHARGE (if required) is to be weighed in through the ¼” charging port on the outside of the unit while the system is operating (this port is always reading the low pressure side of the system). The vapor service valve port is high‐pressure gas during heating operation and low‐pressure gas during cooling operation. Charging operations should always be performed in heating mode. If the unit must be charged in cooling mode, a return trip may be required to check the charge during heating season. Total charge amount is dependent on the total length of the liquid line. See the Line Set Charging Chart in Appendix C. ...
Page 6
INSTALLATION CHECKLIST System Startup and Checkout Ensure the access cover to the air handler is in place to establish proper air flow across the indoor A‐coil while the system is operating. After applying power, ensure electrical voltage ratings are within specifications. If the voltage is outside of specification, contact your local utility company. Verify control board heartbeat is active, and no error conditions are present. Obtain an accurate measurement of the outdoor temperature at the outdoor unit. Measure liquid line temperature by attaching and insulating an accurate thermistor type or electronic thermometer to the 3/8” liquid line near the outdoor coil. Place the system into a Stage 2 heating call (24V on Y2 terminal at outdoor unit). A minimum anti‐short cycle timer of 5 minutes will elapse before any compressor operation is permitted by the control board. Operate the unit for a minimum of 30 minutes before checking charge. Measure liquid service valve pressure by attaching an accurate R410A rated gauge to the 3/8” service port. Refer to Appendix C ‘Charging Chart’ for required sub cooling temperatures. For every 1 lb of additional refrigerant added, allow a sufficient time for the system to settle before taking another sub cooling indication. Complete the service sticker on the electrical box cover during installation. IMPORTANT: Before leaving the job, be sure to do the following: Ensure that all wiring and tubing is secure in unit before adding panels and covers. Securely fasten all panels / covers and ensure all fasteners remain tight. Tighten service valve stem caps to 1/12‐turn past finger tight. Leave Owner’s Manual with owner. Explain system operation and periodic maintenance requirements outlined in manual. Go over owner’s check list with the new Acadia owner. Fill out the Dealer Installation Checklist and place in customer file. Fill out the installation data sheet on the last page and mail or fax it to Hallowell International. ...
SAFETY SAFETY CONSIDERATIONS 6.) Insure unit is placed away from roof ends where rain, ice, Improper installation, adjustment, alteration, service, snow, where icicles may form, or any other debris may maintenance, or use can cause explosion, fire, electrical fall on top of, and damage unit. shock, or other conditions which may cause death, personal injury, or property damage. 7.) Be sure to add an oil trap to the vapor line for every 10ft of vertical rise. Consult a qualified installer, service agency, or your distribu‐ tor for more information, or assistance. The qualified installer 8.) Avoid direct tubing contact with water pipes, duct work, or agency must use factory‐authorized kits or accessories floor joists, wall studs, floors, walls, brick, or other when modifying this product. Refer to the individual instruc‐ construction material. tions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective cloth‐ 9.) Do not suspend refrigerant tubing from joists and studs ing, and work gloves. with a rigid wire or strap which may come in direct Use quenching cloth for brazing operations to protect system contact with tubing. components. Have fire extinguisher available. Read these instructions thor‐ 10.) When necessary, use hanger straps which conform to oughly and follow all warnings or cautions included in litera‐ shape of tubing insulation. ...
INSTALLATION Step 1—Check Equipment and Job Site safety problem when water refreezes. Note: Do not set unit so that defrost condensate will run across sidewalk. Outdoor condenser unit is heavy. Take the necessary Ensure the unit is not placed directly under roof drains, precautions and use appropriate equipment to move and eaves, or under roof pitches where rain, ice, or falling install. snow may fall on and damage unit. UNPACK UNIT Unit must be mounted on Hallowell Approved snow Move to final location. Remove carton, taking care not to stands to allow water to drain‐out during a defrost cycle, damage unit. and so that ice build up will not interfere with unit operation. INSPECT EQUIPMENT Check over the unit for any signs of shipping damage. If Be sure that the mounting of the snow legs are on the shipment is damaged or incomplete, file a claim with the support rails of the system and not on the base pan so it shipment company as soon as possible. will allow the water to drain out of the unit during Check the unit for nitrogen pressure using a pressure gauge. defrost. The unit should have a charge of 50psi (+/‐ 10%) of nitrogen. If the unit’s nitrogen charge is low, or lacks nitrogen pressure, CAUTION: Do not block drainage holes under outdoor do not install the unit until Hallowell factory service is coil. Ice buildup will damage coil. ...
Do not run the system / air handler fan while construction is in progress. All ductwork must be properly sized for proper airflow. Undersized ducts will reduce the system’s performance, resulting in unit damage, a reduced life and higher operational costs. Ensure that all air registers are in the fully open position. Insulate and seal all ductwork. Ensure ductwork does not come in contact with structural building members. Utilize flex connections at the main ductwork supply and return to isolate potential vibrations and noise. Be sure the filter cover is installed on the Hallowell Figure a ‐ Clearance Requirements matched air handler, ensuring easy access to the filter for routine maintenance of filter change. Any gaps, holes Step 4—Check Indoor Expansion Device and and joints should be properly sealed to prevent air Install in Air Handling Unit leakage. Be sure the condensate drain or the line set do not block For proper unit operation, reliability, and performance the access to the filter door, or any of the access panels of units must be installed with a balance port, bi‐directional the air handler. heat pump TXV specifically designed to operate with R‐410A refrigerant. Do not install an air handler with evaporator coils IMPORTANT: Due to the high output capacity of the Acadia having capillary tube or orifice metering devices. ...
INSTALLATION The Hallowell Matched air handlers come from the factory with bi‐flow TXVs specifically designed for R‐410A. NOTE: The filter dryer must be installed at the air handler and insulated to prevent heat loss. The Acadia uses waste Installation is required. heat off the liquid line. IMPORTANT: If replacing an existing hot air furnace make The filter dryer must be installed in the liquid line as close to sure the duct work is sized appropriately for the air flow the Hallowell Matched air handing unit as possible. DO NOT needed by the Acadia, sealed and insulated. install a liquid line sight glass. IMPORTANT: When matching the outdoor unit with the IMPORTANT: Insulate the filter dryer with ½ inch thick Hallowell factory air handler, an R‐410A rated TXV must be insulation after installation to help retain heat in the liquid installed. NO OTHER TYPE OF METERING DEVICE MAY BE line. USED! Contact the factory for any questions about sizing or applications. PRECAUTIONS DURING LINE SET INSTALLATION IMPORTANT: The TXV should be mounted as close to the CAUTION: Be sure Nitrogen is flowing through the system indoor coil as possible with the thermal bulb securely prior to any brazing for the prevention of oxidation and mounted and insulated. contamination of the system. NOTE: When you are using the Hallowell approved air CAUTION: System uses POE oil for the compressor ...
INSTALLATION insulated with a minimum of ½” foam rubber insulation 8. Insert the 3/8” line from the line‐set into the other end separately from the vapor line. of the filter dryer and braze in place. Use PVC or other suitable piping as a conduit for all 9. The last braze joint is at the outdoor unit’s 3/8” underground installations. connection. To do the last braze joint remove the Pack fiberglass insulation and a sealing material such as Schrader valve core from the 3/8” service valve. permagum, or RTV around refrigerant lines where they penetrate a wall to reduce vibration and to retain 10. Wrap the service valve with a wet rag, preventing the flexibility. service valve from overheating. Insert the pipe and Use only long radius 90° for any hard drawn copper. braze into place. The use of a brazing shield may need to be used to keep from burning the unit. SWEAT CONNECTION CAUTION: Purge line sets with nitrogen before and while 11. Re‐install the Schrader valve cores into the vapor and brazing occurs to prevent internal oxidizing contaminants liquid service valves. from entering the system and to protect the POE oil. 12. Leak test the line set by adding 400 psi of nitrogen to the 1. Run the line‐set from the Air Handler Unit (AHU) to the line‐set and AHU coil. outdoor unit. Be sure to keep the ends of the pipe ...
INSTALLATION Refrigerant system must be evacuated down to a minimum of within sight from and readily accessible from unit, per 500 microns. Once 500 microns has been reached, the Section 440 of NEC. system should be sealed off and held at 500 microns for a ROUTE GROUND AND POWER WIRES minimum of 15 minutes to perform a free air test. IMPORTANT: Break any system under a vacuum with DANGER: The unit cabinet must have an uninterrupted or nitrogen pressure for repairs, preventing ambient air from unbroken ground to minimize personal injury if an electrical entering the system. fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing FINAL TUBING CHECK electrical codes. Failure to follow this warning can result in an electric shock, fire, or death. IMPORTANT: Ensure both indoor and outdoor units have not shifted during shipment. Ensure tubes are not rubbing against Remove access panel and electrical box cover to gain access each other or any sheet metal. Pay close attention to to unit wiring. Extend wires from disconnect through power distributor tubes and service port stems. Check insulation on wiring hole provided and into unit control box. Size wires per vapor and liquid lines, and make sure it is sealed properly NEC. with tape or glue. CONNECT GROUND AND POWER WIRES Step 6 – Make Electrical Connections Line Voltage and Control wires must be routed CAUTION: clear of any system components to prevent wiring chafing / DANGER: To avoid personal injury or death, do not electrical shorts. ...
Minimum air flow for the 24A is 800cfm on a Y2 call. Set transformer is connected to the system. Use only the 75VA the control jumpers in the air handler accordingly. If transformer supplied in the outdoor unit. using factory supplied air handling unit see Figures 1‐2, Appendix A. Jumper settings of Heat:A Delay:A Cool:B IMPORTANT: Make sure to adjust the line voltage leads to Adjust:B. the 75VA transformer if the line voltage is other than 240V. If electric heat is installed in the AHU, be sure the air IMPORTANT: Disconnect the secondary leads (control voltage handler unit is properly configured for electric heat. Be wires) from the air handler control transformer to the air sure the Heat/No Heat jumper on the AHU unit is set to handler control board. Heat. If using the factory supplied air handling unit, see Figure 1, Appendix A. Using 10 or 12‐conductor, 18 AWG, color‐coded, insulated (35C minimum) wire, connect the control system components Using the table in Figure 5, Appendix A, program the between the heat pump, Hallowell Matched air handler, and thermostat for proper operation with the Hallowell thermostat (as shown in Figure 9, Appendix B). If the distance Acadia. between the thermostat and the heat pump unit is more than 100 feet (as measured by the control wiring) 16 AWG wire It is essential to place the jumper between RC and RH as should be utilized to avoid unnecessary voltage drop. All indicated on the thermostat diagram (Figure 9, Appendix wiring must be NEC Class 1 and must be separated from the B) to allow correct operation. incoming power leads. The outdoor unit provides a maximum Ensure the jumpers on the outdoor control board are in of 75VA, 24VAC for control power. To ensure correct the proper position; JMP2 Manual Defrost on one pin, operation of the system, the 40VA transformer located in the and JMP1 Economy jumper on both pins. Indoor Air Handler must be disconnected from the control board, and properly insulated to prevent possible shorts. If the system is using the factory recommended zone ...
Page 14
INSTALLATION Do not operate the unit in a vacuum or at negative The initial unit charge depends on the length of the liquid pressure. line used. Be sure to accurately measure the liquid line length. After evacuation is complete, charge the unit Do not disable the low‐pressure or high‐pressure with R410A refrigerant through the liquid line service switches. port, using the amounts on the chart shown below. Ensure the Air Handler filter is clean Hallowell ACHP Line Set Charging Chart Line set Ensure the Air Handler Adjustments are set correctly. Acadia 036 & length Acadia 024 Acadia 048 (ft) Check that all supply and return registers are clear and 0‐10 9lb 12lb ‐ 8.0oz not blocked. 11 9lb ‐ 0.6oz 12lb ‐ 8.6oz 12 9lb ‐ 1.2oz 12lb ‐ 9.2oz To prevent personal injuries, wear safety glasses, protective 13 9lb ‐ 1.8oz 12lb ‐ 9.8oz clothing, and gloves when handling refrigerant and observe 14 9lb ‐ 2.4oz 12lb ‐ 10.4oz the following: 15 ...
INSTALLATION The thermostat must be setup at this time to properly NOTE: Above 60°F, charge the unit using the line set chart work with your Hallowell Acadia. See the tables in Figure (see step 7 or Appendix C). You may have to return in 5, Appendix A. heating season and double check charge amount for optimal efficiency. Set the thermostat to Fan ON, ensuring air flow and HEATING CHECK CHARGE PROCEDURE jumpers are properly placed in the Hallowell Matched air handler. Test the emergency heat settings. : R410A is miscible with POE oil in the CAUTION Set the Fan to AUTO or ON as desired, then set the room system. Let the system run in normal operation for an thermostat to COOL or HEAT. Wait for the appropriate adequate amount of time after startup or a defrost cycle to ensure an accurate subcooling reading. time delay(s). Operate the unit for 30 minutes after initial charge, continuously ensuring the thermostat setting will not be satisfied. (Open windows or doors if necessary) Operate the unit a minimum of 30 minutes before checking charge. NOTE: While waiting, be sure the line set is secure and insulated separately. This is a good time to Measure the liquid service valve pressure by attaching an double check the installation procedure. Check accurate R410A rated gauge to 3/8” service port. over the system for any unusual vibrations / noises. Measure the liquid line temperature by attaching and Set the room thermostat 10 degrees or more above or insulating an accurate thermistor type or electronic below desired room temperature allowing second stage thermometer to the liquid line near the outdoor coil. operation while charging. This may bring on a third Use the pressure – temperature chart to calculate sub‐ stage call from the thermostat and turn on auxiliary heat. ...
INSTALLATION Extras Ensure that all wiring and tubing is secure in the unit before adding panels and covers. Securely fasten all panels / covers and ensure all fasteners remain tight. Zone Controls. The only zone control that is factory authorized is the EWC Tighten the service valve stem caps to 1/12‐turn past UZC series of zone control. The zone control will be wired finger tight. and set up according to the drawing in Appendix F. This zone control works very well with the Acadia as long as some rules Leave the Owner’s Manual as well as the Installation Manual with the customer. Explain the system operation and periodic maintenance requirements outlined in the manual. Fill out the Dealer Installation Checklist and place in a customer file. Be sure to talk to the customer about the general maintenance, shoveling around the unit and keeping it clear of debris, basic thermostat use and the importance of periodical filter changes. Discourage the customer from set backs of the thermostat program. Ensure the supply registers are diffused properly. Ensure the charge amount is written on the service sticker provided on the electrical box cover of the outdoor unit. Talk to the customer about the defrost operation and how it will effect the register temperature. Be sure the customer knows where to purchase more air filters. Ensure the supply registers are defused away from heavy traffic areas and not directly on the customer. CARE AND MAINTENANCE For continuing high performance, and to minimize possible equipment failure, periodic maintenance must be performed on this equipment. Frequency of maintenance may vary de‐ pending upon geographic areas, such as coastal applications. Pay close attention to cleanliness of indoor / outdoor coils ...
INSTALLATION 6. To protect the coil from damage, use anti‐freeze in efficient operation of the unit. If there are any questions the hydronic loop to prevent freezing. A freeze‐stat about how the unit is operating, contact Hallowell factory can also be used to protect the coil. support. 7. Hydronic coils added internally to the Hallowell AHU are not approved. Installing the system with a hot air furnace Hallowell will approve a parallel furnace installation pending a factory consultation. The duct work must be installed with dampers so that the air flow will not short cycle through either system when it is on. An isolation relay must be used so that the furnace is not allowed to operate when the Acadia is running. Hallowell Control Timers 1. Temperature Stability Timer (5 Min)– In order for the system to change operational BINS from one to another, the system must sense a temperature change in the new BIN for at least five minutes. 2. Defrost Lockout Timer (45 Min) – This timer prevents the system from going into another defrost within 45 minutes of the prior defrost. 3. Y2 Validation Timer (1 Min) – The outdoor unit must sense a Y2 call from the thermostat for at least 1 minute before it will change stages. This will prohibit nuisance staging of the outdoor unit. ...
Sensor Fault motor. Coil Temperature Sensor 8 Flashes, OFF for 3 Seconds Fault Temperature Sensor Fault Interstage Temperature NOTE: Make sure the system power is off before 9 Flashes, OFF for 3 Seconds Sensor Fault troubleshooting the temperature sensors. 10 Flashes, OFF for 3 Spare Temperature Sensor Seconds Fault On the upper right hand corner of the outdoor unit control board is the plug for the temperature RTD sensors. You will If the Hallowell Acadia has encountered an operational error, need to unplug the sensors from the control board by pulling the outdoor unit will shut down for a period of 10 minutes, the plug straight off the control board. Check the connection after which it will attempt to restart in its last known operat‐ of the wires in the plug making sure that the wire is not ing mode. If the unit is able to restart and run for 30 continu‐ broken or the insulation is in the plug. You will need a ous minutes without an error, all error codes will be cleared thermocouple reader and sensor, and a multi‐meter. Using and normal operation shall continue. If, however, this the thermocouple take the temperature at each sensor. attempt to restart fails, the outdoor unit will shut down for The Blue wire sensor is the coil sensor and is located on the another 10 minutes. If a third error occurs within 30 minutes second distributor tube from the bottom of the coil. The of the original error, the unit will shut down all operation and Yellow wire sensor is the inter stage sensor and it is located activate a MAINTENANCE REQUIRED output. This should on the suction line going to the primary compressor. The ...
Troubleshooting See the chart below. If the unit is not changing mode, do the Resistance Vs Temperature Temperature sensor fault test. Temperature (°F) Resistance (Ω) Heating Mode Operation ‐40 84.21 The Hallowell Acadia operates with 6 modes of heating ‐30 86.41 capacity available. These modes are as follows: ‐20 88.61 Mode 1: Single cylinder primary compressor ‐10 90.81 0 93.01 Mode 2: Two cylinder primary compressor 10 95.2 Mode 3: Primary Two cylinder plus W1 (1 stage auxiliary 20 97.38 heat) 30 99.57 Mode 4: Primary Two cylinder and Booster compressors. 40 101.74 Mode 5: Primary Two cylinder and Booster compressors plus ...
Y2O Y2O Y2O Y2O Y2O the input signal from the thermostat. If you have an input Table 2: State of Y2OUT and Heat Mode vs. Bins from the thermostat and one of the LEDs is lit, verify the output to that LED on the output plug on the upper left of At any time while the thermostat is in heating mode, the control board for 24VAC. If 24VAC is not present, replace the system can be placed into emergency heating mode, control board. energizing the installed auxiliary heating system. If the contactor is not pulled in, check for 24VAC at the contactor coil. If you have 24VAC, replace the contactor. If Cooling Mode Operation you do not have 24VAC, replace the wiring to the contactor. The Hallowell Acadia operates with 2 stages of cooling Check the contactor. If it is pulled in, check the starting gear capacity available, based on the level of demand from the of the compressor. Check the start and run caps and the thermostat. Cooling mode is limited to operation when the starting relays. If you find a problem with the starting gear, outdoor air temperature is above 50F to ensure correct replace the component. If it is all ok, check the compressor operation of all components in the system. The 2 stages of windings for an open or shorted winding. If the compressor is cooling capacity are illustrated below, with the modes of bad, contact Hallowell International LLC for a new operation being identical to the modes of operation used in compressor with the provisions for the Oil Equalization Line. heating mode. COOLING Booster Compressor will not start Check the control board for the BE output LED. ...
APPENDIX A SETTINGS Figure 1 – Factory Supplied Air Handler Control Board. Hallowell TXV Kit installation Instructions: 1. Ensure coil has not been exposed to atmospheric pressure for more than 15 minutes. 2. Remove indoor coil inlet cover at the distributor body inlet. Use back‐up wrench to prevent damage. 3. Install the TXV to the distributor using a back‐up wrench to prevent damage. Tighten finger tight then ¼ turn more. 4. Connect equalizer tube of the TXV to ¼ in equalizer fitting on the vapor line. Be sure to remove the Schrader valve located in the fitting on the coil. 5. Install the indoor coil inlet tube. Use back‐up wrench to prevent damage. 6. Attach TXV bulb to horizontal section of suction line using bulb strap and insulate. 7. Proceed with remainder of unit installation. 8. Refer to air handler installation manual for further installation of air handler unit. ‐ 20 ‐...
Page 22
APPENDIX A SETTINGS Figure 2 – Air Flow Chart for Air Handler HIGH SPEED COOLING AND HEAT PUMP AIRFLOW (CFM) Model Jumper Settings Cool Adjust m3/min m3/min m3/min 1010 28.6 1230 34.8 2020 57.2 23.1 1007 28.5 1759 49.8 26.4 1202 34.0 1989 56.3 20.0 25.6 1607 45.5 26.2 1076...
Page 23
APPENDIX A SETTINGS Figure 4 – Control Jumpers When the Economy Jumper is shorted it will disable the W1 output on a second stage call when outdoor temperature is between 35˚F to 25˚F. ‐ 22 ‐...
Page 24
APPENDIX A SETTINGS Figure 5 – Thermostat Settings Menu FACTORY DEFAULT CORRECT SETTING COMMENTS Number SETTING 1 MS 2 HP 2 Selects appropriate control style (2 stage heat pump) 2 (GAS) ELE Indoor blower control (furnace or thermostat) 3 DAYS(7) 0 7 day, 5 day plus weekend, or no program 4 PS (4) n/a Program set points during each day COOL OFF HEAT (EMER) System switchover or operating mode with heating, 5 COOL OFF HEAT AUTO AUTO cool, auto changeover, or off. Pre‐Stage heating/cooling steps to reach desired 6 E (ON) ON ...
Page 25
APPENDIX A SETTINGS 1.) Control System Type: 14.) Beeper On/Off: This control can be adapted for many uses; however, operation of Turn the key press beeper On or Off. the Hallowell Acadia requires the HP2 setting. 15.) Heat Temperature Limit: 2.) Indoor Fan Operation: The highest allowable temperature for heating mode may be GAS or Electric (ELE) fan operation. The system requires the changed here. The allowable range for the Hallowell Acadia is 62°F thermostat to energize the indoor fan. If a separate heating system to 80°F. When this is active, the “temperature limit” icon is controls the fan, select GAS. displayed to the left of the set point temperature, and if an attempt is made to adjust the set point above the limit, the “temperature 3.) Programming: limit” icon will flash. The control can be setup to run individual programs for each day of the week, a 5‐day block with separate weekend parameters, or a 0‐ 16.) Cool Temperature Limit: day block to disable programming. For the system to operate most The lowest allowable temperature for cooling mode may be efficiently, 0‐day block, or no programming, is recommended. changed here. The allowable range for the Hallowell Acadia is 65°F to 85°F. When this is active, the “temperature limit” icon is 4.) Program Set Points: displayed to the left of the set point temperature, and if an attempt This control can be programmed with 2 or 4 set points during the is made to adjust the set point below the limit, the “temperature day. If using 0‐day block, or no programming, this setting is not limit” icon will flash. applicable. ...
APPENDIX C – ACADIA CHARGING R410A Figure 11 – Hallowell Acadia Charging Chart HALLOWELL ACADIA Charging Chart Outdoor Air Temp. Sub‐Cooling Liquid Line Temp. 3/8" Service Valve 7/8" Service Valve Charging Port (Deg F) (Deg F) (Deg F) (PSIG) (PSIG) (PSIG) 60 to 50 12 to 15 90 to 100 325 to 390 330 to 400 100 to 140 50 to 40 13 to 18 90 to 80 280 to 360 290 to 365 80 to 115 40 to 30 18 to 25 75 to 85 280 to 350 280 to 350 95 to 65 30 to 25 18 to 27 70 to 80 280 to 340 275 to 345 75 to 60 25 to 20 ...
Page 31
APPENDIX C – ACADIA CHARGING R410A Figure 12 – Pressure/Temperature Chart R410A Deg Deg Deg Deg Deg Deg Deg Deg Deg PSIG PSIG PSIG PSIG PSIG PSIG PSIG PSIG PSIG F F F F F F F F F 40 ‐7 82 22 124 109 444 ...
7/8 in 2 R410A Initial Charge (Field Charge) 9 lbs 12 lbs 12 lbs Charge per ft of line set after 10ft 0.6 oz 0.6 oz 0.6 oz Handling Weight 460lbs 475lbs 500lbs Matched Variable Speed Air Handler AVG24B3XH21 AVG36C3XH21 AVG48D3XH21 Coil Model Number 373‐23793‐011 373‐23793‐002 373‐23793‐006 dBA Cooling and Heating (Mode 2 / Mode 3) 60/61 60/61 61/62 1. Use dual element fuses or HACR circuit breakers 2. The unit does NOT come pre‐charged with R410A refrigerant from the factory. The unit comes from the factory with a 50 PSI charge of nitrogen. After install evacuation; units with line sets of 10 feet or less receive 12 lbs of liquid R410A refrigerant. For line sets greater than 10 feet, admit .6oz of refrigerant for each additional foot. 3. The Acadia Systems require both liquid and vapor lines to be insulated for maximum heating performance. 4. Sound pressure level re: 20µPA measured at 10 feet. Noise levels were measured in an installed condition in the field with a Type I sound level meter. These measurements are intended to be used in a precursory review; actual levels vary per each individual installation. Inquiries and Concerns regarding specific applications should be reviewed by a qualified acoustical consultant. 5. All specifications are subject to change at the sole discretion of Hallowell International without notice and without inducing obligation or liability. ‐ 34 ‐...
Page 37
APPENDIX G – SPECIFICATION SHEETS Physical Dimensions of the Outdoor Unit Model Dimensions (Inches) Service Valve Size A B C Liquid Vapor ACADIA024 48‐1/2 27‐7/8 31 3/8 3/4 ACADIA036 48‐1/2 27‐7/8 31 3/8 7/8 ACADIA048 48‐1/2 33‐7/8 31 3/8 7/8 Physical Dimensions of the Matched Variable Speed Air Handler Dimensions (Inches) Wiring Knockouts Refrigerant Connection Line Models ...
Page 38
APPENDIX G – SPECIFICATION SHEETS Configurations of the Matched Variable Speed Air Handler Configuration of the Matched Hallowell Outdoor Split System Heat Pump ‐ 37 ‐...
Contractor Check List Check list for the contractor to discuss with the home owner. 1. Review thermostat operation with the owner. a. How the system works. (Staging of the system)_________ b. How to clear the change filter reminder.___________ c. How to set the mode of operation for cooling or heating.__________ d. How to set the time on the thermostat.____________ e. What the icons mean on the thermostat “call for service”, “stage 1”, “stage 1+2”.________ When you should see the different icons.___________ 2. Go over the programming of the thermostat the consequences of setbacks. a. What happens when the thermostat is programmed for setbacks.___________ 3. Go over coil maintenance with the owner. a. How to change the filter(s).__________ b. When to change the filter(s).___________ c. How to brush or vacuum down the outdoor coil from grass clippings.__________ d. How to rinse down the outdoor coil 2 to 3 times a year.___________ 4. Where the owner can pick up replacement filters. a. Size of the filter(s).________ b. Type of filters recommended.__________ c. Best place to get the filters._________ 5. Maintenance of the outdoor system; keeping the coil clear of snow and ice. a. Keep the unit shoveled out._________ b.
DATA SHEET Homeowner Information Installer Information Name Company Address Line 1 Address Line 1 Address Line 2 Address Line 2 City City State / Prov. State / Prov. Postal Code Postal Code Phone # Phone # Equipment Information Outdoor Unit Model # Outdoor Unit Serial # Air Handler Model # Air Hander Serial # Installation Information Heat Kit Installed (Y/N) ...