Hallowell Acadia 024 Installation Manual

Hallowell Acadia 024 Installation Manual

Hide thumbs Also See for Acadia 024:

Advertisement

Quick Links

 
Hallowell International 110 Hildreth Street, Bangor, ME 04401
t:(207) 990.5600 --- f:(207) 990.5602 --- info@gotohallowell.com --- www.gotohallowell.com
Last Revised 03.25.09
50‐00394‐E

Advertisement

Table of Contents
loading

Summary of Contents for Hallowell Acadia 024

  • Page 1   Hallowell International 110 Hildreth Street, Bangor, ME 04401 t:(207) 990.5600 --- f:(207) 990.5602 --- info@gotohallowell.com --- www.gotohallowell.com Last Revised 03.25.09 50‐00394‐E...
  • Page 2: Table Of Contents

          Extras      1 5        Hydronic Coil Supplemental Heat      1 5        Hallowell Control Timers      1 6          Troubleshooting    17      Control Code Errors      1 7     ...
  • Page 3 CONTENTS      Hallowell TXV Kit Installation Instructions      2 0      Figure 2 – Air Flow Chart for Air Handler      2 1      Figure 3 – Electric Heat Airflow Taps for Factory Supplied Air Handler      2 1      Figure 4 – Control Jumpers      2 2      Figure 5 – Thermostat Settings      2 3      Thermostat Setting Descriptions      2 4 ...
  • Page 4: Installation Checklist

    INSTALLATION CHECKLIST  Please Check     or fill out as Completed  PIPING CONNECTIONS  Ensure both vapor and liquid lines are fully insulated separately with at least ½” wall insulation.  Ensure the liquid line filter drier is installed near the air handler, and insulated as well.  If a vertical riser of 10’ or more is present on the line set, the line set must be properly trapped to prevent oil  slugging to the compressors; good practice in any riser.   When making brazed connections, trickle nitrogen through the system (e.g. 2 PSI) to maintain clean braze joints  and eliminate carbonization inside the piping during the braze process.  The Acadia system comes pre‐charged  with 50 PSI of dry nitrogen.  This can be used for nitrogen trickling by cracking the service valves slightly.  AIR HANDLER  Install indoor air handler, ensuring proper duct sealing, insulation & distribution.  Ensure all registers, supply and return, are open and unblocked.  Ensure a duct flex connector is used to eliminate vibration transmission to the home.   Ensure a proper air filter is installed on the return side of the air handler.  Ensure condensate drain is installed properly, and trapped.  Run 10‐conductor (minimum), 18 AWG control wiring from air handler to the thermostat, and from air handler  to outside condenser unit.  Connect control wiring following color codes provided in the install manual, Appendix B.  Disconnect the low‐voltage leads from the transformer provided in the air handler from the air handler control  board 24 VAC and Common terminals.  Line‐voltage leads to the transformer must remain connected to power  the ECM blower motor.  Connect 24VAC and 24C provided from outdoor unit to the ¼” terminals labeled COM and 24VAC on the indoor  AHU control board (seen in Appendix A, FIG1).  Ensure the electrical service to the air handler is adequate for both the air handler and electric heat kit, if one is  installed, per NEC and/or local codes.  Ensure appropriate electrical disconnect size is installed, per NEC and/or local codes.  Ensure the HP/AC jumper on the air handler control board is set to HP (Heat Pump).  If an electric heat kit is installed, ensure the HEAT/NO HEAT Jumper on the air handler control board is set to the  HEAT side.  Leaving this jumper on NO HEAT disables all auxiliary heat relays.  Set airflow jumpers in air handler in accordance with Appendix A.  THERMOSTAT  Install thermostat in a location where it will not be directly exposed to conditioned air or drafts from doors  and/or windows.  Insulate between the base plate of the thermostat and the wall to prevent drafts from affecting the thermostat.  Ensure that a jumper between W2 and W/E is not installed on the thermostat.  Ensure that a jumper between RC and RH is installed on the thermostat.  Configure the thermostat’s installer configuration menu as indicated in the installation manual, Appendix A:   ‘Thermostat Settings’. ...
  • Page 5 INSTALLATION CHECKLIST  OUTSIDE CONDENSER UNIT  Ensure proper clearances are observed around the unit in accordance with Appendix D in the installation  manual, making sure to provide appropriate space for accessibility to the compressor compartment’s access  panel (30 inches minimum).  Ensure condenser is placed on appropriate snow stands (not blocks, sleepers, etc.) per climate region with a  minimum of 12” clearance to ground.  Ensure outdoor unit is level.  Ensure the outdoor coil’s drainage holes are not obstructed, providing full drainage runoff during the defrost  cycles.  Check factory tubing to ensure tubes are not rubbing against each other or any sheet metal. Pay close attention  to distributor tubes on both indoor and outdoor coils.  Ensure transformer is wired appropriately for applied line voltage. For correct wiring, see Line Voltage diagram  in Appendix B.  Unit is factory wired for 230VAC.  Ensure the 10 conductor, 18 AWG control harness has been correctly wired between the thermostat, indoor air  handler, and outdoor unit, following color codes and schematics provided in Appendix B.  Ensure the electrical disconnect is properly sized for the outdoor unit, per NEC and/or local codes.  Ensure all electrical connections are weather tight.  Ensure all cabinet and electrical fasteners are secure. Shipping vibration can loosen connections.  Ensure control wiring is not chaffing/grommet is installed.  Charging the System  Ensure both vapor and liquid service valves are open and back‐seated.  Ensure system has been properly evacuated to at least 500 microns.  A triple evacuation is the preferred method  for a clean installation.  Ensure the R‐410A INITIAL CHARGE is weighed in as a liquid through the 3/8” service valve port inside the  compressor compartment.  FINAL CHARGE (if required) is to be weighed in through the ¼” charging port on the  outside of the unit while the system is operating (this port is always reading the low pressure side of the  system).  The vapor service valve port is high‐pressure gas during heating operation and low‐pressure gas during  cooling operation.  Charging operations should always be performed in heating mode.  If the unit must be charged in cooling mode, a  return trip may be required to check the charge during heating season.  Total charge amount is dependent on the total length of the liquid line.  See the Line Set Charging Chart in  Appendix C. ...
  • Page 6 INSTALLATION CHECKLIST    System Startup and Checkout  Ensure the access cover to the air handler is in place to establish proper air flow across the indoor A‐coil while  the system is operating.  After applying power, ensure electrical voltage ratings are within specifications.  If the voltage is outside of  specification, contact your local utility company.  Verify control board heartbeat is active, and no error conditions are present.  Obtain an accurate measurement of the outdoor temperature at the outdoor unit.   Measure liquid line temperature by attaching and insulating an accurate thermistor type or electronic  thermometer to the 3/8” liquid line near the outdoor coil.  Place the system into a Stage 2 heating call (24V on Y2 terminal at outdoor unit).  A minimum anti‐short cycle  timer of 5 minutes will elapse before any compressor operation is permitted by the control board.  Operate the unit for a minimum of 30 minutes before checking charge.  Measure liquid service valve pressure by attaching an accurate R410A rated gauge to the 3/8” service port.  Refer to Appendix C ‘Charging Chart’ for required sub cooling temperatures.  For every 1 lb of additional refrigerant added, allow a sufficient time for the system to settle before  taking another sub cooling indication.  Complete the service sticker on the electrical box cover during installation.  IMPORTANT: Before leaving the job, be sure to do the following:  Ensure that all wiring and tubing is secure in unit before adding panels and covers.  Securely fasten all  panels / covers and ensure all fasteners remain tight.  Tighten service valve stem caps to 1/12‐turn past finger tight.  Leave Owner’s Manual with owner. Explain system operation and periodic maintenance requirements  outlined in manual.  Go over owner’s check list with the new Acadia owner.  Fill out the Dealer Installation Checklist and place in customer file.  Fill out the installation data sheet on the last page and mail or fax it to Hallowell International.                     ...
  • Page 7: Safety Considerations

    SAFETY  SAFETY CONSIDERATIONS    6.) Insure unit is placed away from roof ends where rain, ice,  Improper installation, adjustment, alteration, service,  snow, where icicles may form, or any other debris may  maintenance, or use can cause explosion, fire, electrical  fall on top of, and damage unit.  shock, or other conditions which may cause death, personal    injury, or property damage.   7.) Be sure to add an oil trap to the vapor line for every 10ft    of vertical rise.  Consult a qualified installer, service agency, or your distribu‐   tor for more information, or assistance. The qualified installer  8.) Avoid direct tubing contact with water pipes, duct work,  or agency must use factory‐authorized kits or accessories  floor joists, wall studs, floors, walls, brick, or other  when modifying this product. Refer to the individual instruc‐ construction material.  tions packaged with the kits or accessories when installing.    Follow all safety codes. Wear safety glasses, protective cloth‐ 9.) Do not suspend refrigerant tubing from joists and studs  ing, and work gloves.  with a rigid wire or strap which may come in direct  Use quenching cloth for brazing operations to protect system  contact with tubing.  components.    Have fire extinguisher available. Read these instructions thor‐ 10.) When necessary, use hanger straps which conform to  oughly and follow all warnings or cautions included in litera‐ shape of tubing insulation. ...
  • Page 8: Installation

    INSTALLATION    Step 1—Check Equipment and Job Site  safety problem when water refreezes. Note: Do not set  unit so that defrost condensate will run across sidewalk.      Outdoor condenser unit is heavy. Take the necessary  Ensure the unit is not placed directly under roof drains,  precautions and use appropriate equipment to move and  eaves, or under roof pitches where rain, ice, or falling  install.  snow may fall on and damage unit.      UNPACK UNIT  Unit must be mounted on Hallowell Approved snow  Move to final location. Remove carton, taking care not to  stands to allow water to drain‐out during a defrost cycle,  damage unit.  and so that ice build up will not interfere with unit    operation.  INSPECT EQUIPMENT    Check over the unit for any signs of shipping damage.  If  Be sure that the mounting of the snow legs are on  the  shipment is damaged or incomplete, file a claim with the  support rails of the system and not on the base pan so it  shipment company as soon as possible.  will allow the water to drain out of the unit during  Check the unit for nitrogen pressure using a pressure gauge.   defrost.  The unit should have a charge of 50psi (+/‐ 10%) of nitrogen.     If the unit’s nitrogen charge is low, or lacks nitrogen pressure,  CAUTION: Do not block drainage holes under outdoor  do not install the unit until Hallowell factory service is  coil. Ice buildup will damage coil.  ...
  • Page 9: Step 4 - Check Indoor Expansion Device And Install Air Handling Unit

      Do not run the system / air handler fan while  construction is in progress.    All ductwork must be properly sized for proper airflow.   Undersized ducts will reduce the system’s performance,  resulting in unit damage, a reduced life and higher  operational costs.    Ensure that all air registers are in the fully open position.    Insulate and seal all ductwork.    Ensure ductwork does not come in contact with  structural building members.    Utilize flex connections at the main ductwork supply and  return to isolate potential vibrations and noise.      Be sure the filter cover is installed on the Hallowell  Figure a ‐ Clearance Requirements  matched air handler, ensuring easy access to the filter for  routine maintenance of filter change.  Any gaps, holes  Step 4—Check Indoor Expansion Device and  and joints should be properly sealed to prevent air  Install in Air Handling Unit  leakage.      Be sure the condensate drain or the line set do not block  For proper unit operation, reliability, and performance the  access to the filter door, or any of the access panels of  units must be installed with a balance port, bi‐directional       the air handler.  heat pump TXV specifically designed to operate with R‐410A    refrigerant. Do not install an air handler with evaporator coils  IMPORTANT:  Due to the high output capacity of the Acadia  having capillary tube or orifice metering devices. ...
  • Page 10: Step 5-Make Piping Connections

    INSTALLATION    The Hallowell Matched air handlers come from the factory  with bi‐flow TXVs specifically designed for R‐410A.  NOTE: The filter dryer must be installed at the air handler  and insulated to prevent heat loss. The Acadia uses waste  Installation is required.  heat off the liquid line.      IMPORTANT: If replacing an existing hot air furnace make  The filter dryer must be installed in the liquid line as close to  sure the duct work is sized appropriately for the air flow  the Hallowell Matched air handing unit as possible.  DO NOT  needed by the Acadia, sealed and insulated.     install a liquid line sight glass.      IMPORTANT: When matching the outdoor unit with the  IMPORTANT: Insulate the filter dryer with ½ inch thick  Hallowell factory air handler, an R‐410A rated TXV must be  insulation after installation to help retain heat in the liquid  installed. NO OTHER TYPE OF METERING DEVICE MAY BE  line.   USED! Contact the factory for any questions about sizing or  applications.  PRECAUTIONS DURING LINE SET INSTALLATION      IMPORTANT: The TXV should be mounted as close to the  CAUTION: Be sure Nitrogen is flowing through the system  indoor coil as possible with the thermal bulb securely  prior to any brazing for the prevention of oxidation and  mounted and insulated.  contamination of the system.      NOTE: When you are using the Hallowell approved air  CAUTION:   System uses POE oil for the compressor ...
  • Page 11: Sweat Connection 1

    INSTALLATION  insulated with a minimum of ½” foam rubber insulation  8. Insert the 3/8” line from the line‐set into the other end  separately from the vapor line.  of the filter dryer and braze in place.    Use PVC or other suitable piping as a conduit for all  9. The last braze joint is at the outdoor unit’s 3/8”  underground installations.   connection.  To do the last braze joint remove the  Pack fiberglass insulation and a sealing material such as  Schrader valve core from the 3/8” service valve.   permagum, or RTV around refrigerant lines where they    penetrate a wall to reduce vibration and to retain  10.  Wrap the service valve with a wet rag, preventing the  flexibility.  service valve from overheating.   Insert the pipe and  Use only long radius 90° for any hard drawn copper.  braze into place.  The use of a brazing shield may need to  be used to keep from burning the unit.  SWEAT CONNECTION    CAUTION: Purge line sets with nitrogen before and while  11. Re‐install the Schrader valve cores into the vapor and  brazing occurs to prevent internal oxidizing contaminants  liquid service valves.  from entering the system and to protect the POE oil.    12. Leak test the line set by adding 400 psi of nitrogen to the  1. Run the line‐set from the Air Handler Unit (AHU) to the  line‐set and AHU coil.  outdoor unit.  Be sure to keep the ends of the pipe   ...
  • Page 12: Final Tubing Check 1

    INSTALLATION  Refrigerant system must be evacuated down to a minimum of  within sight from and readily accessible from unit, per  500 microns.  Once 500 microns has been reached, the  Section 440 of NEC.   system should be sealed off and held at 500 microns for a  ROUTE GROUND AND POWER WIRES  minimum of 15 minutes to perform a free air test.    IMPORTANT:  Break any system under a vacuum with  DANGER:  The unit cabinet must have an uninterrupted or  nitrogen pressure for repairs, preventing ambient air from  unbroken ground to minimize personal injury if an electrical  entering the system.  fault should occur. The ground may consist of electrical wire  or metal conduit when installed in accordance with existing  FINAL TUBING CHECK  electrical codes. Failure to follow this warning can result in    an electric shock, fire, or death.  IMPORTANT: Ensure both indoor and outdoor units have not  shifted during shipment. Ensure tubes are not rubbing against  Remove access panel and electrical box cover to gain access  each other or any sheet metal. Pay close attention to  to unit wiring. Extend wires from disconnect through power  distributor tubes and service port stems. Check insulation on  wiring hole provided and into unit control box. Size wires per  vapor and liquid lines, and make sure it is sealed properly  NEC.   with tape or glue. CONNECT GROUND AND POWER WIRES  Step 6 – Make Electrical Connections      Line Voltage and Control wires must be routed  CAUTION:   clear of any system components to prevent wiring chafing /  DANGER:  To avoid personal injury or death, do not  electrical shorts. ...
  • Page 13: Configuring Your Heat Pump Components 1

    Minimum air flow for the 24A is 800cfm on a Y2 call.  Set  transformer is connected to the system.  Use only the 75VA  the control jumpers in the air handler accordingly. If  transformer supplied in the outdoor unit.  using factory supplied air handling unit see Figures 1‐2,  Appendix A.  Jumper settings of Heat:A Delay:A Cool:B  IMPORTANT: Make sure to adjust the line voltage leads to  Adjust:B.  the 75VA transformer if the line voltage is other than 240V.  If electric heat is installed in the AHU, be sure the air  IMPORTANT: Disconnect the secondary leads (control voltage  handler unit is properly configured for electric heat. Be  wires) from the air handler control transformer to the air  sure the Heat/No Heat jumper on the AHU unit is set to  handler control board.  Heat. If using the factory supplied air handling unit, see  Figure 1, Appendix A.  Using 10 or 12‐conductor, 18 AWG, color‐coded, insulated  (35C minimum) wire, connect the control system components  Using the table in Figure 5, Appendix A, program the  between the heat pump, Hallowell Matched air handler, and  thermostat for proper operation with the Hallowell  thermostat (as shown in Figure 9, Appendix B). If the distance  Acadia.  between the thermostat and the heat pump unit is more than  100 feet (as measured by the control wiring) 16 AWG wire  It is essential to place the jumper between RC and RH as  should be utilized to avoid unnecessary voltage drop. All  indicated on the thermostat diagram (Figure 9, Appendix  wiring must be NEC Class 1 and must be separated from the  B) to allow correct operation.  incoming power leads. The outdoor unit provides a maximum  Ensure the jumpers on the outdoor control board are in  of 75VA, 24VAC for control power. To ensure correct  the proper position; JMP2 Manual Defrost on one pin,  operation of the system, the 40VA transformer located in the  and JMP1 Economy jumper on both pins.  Indoor Air Handler must be disconnected from the control  board, and properly insulated to prevent possible shorts.   If the system is using the factory recommended zone ...
  • Page 14 INSTALLATION  Do not operate the unit in a vacuum or at negative  The initial unit charge depends on the length of the liquid  pressure.  line used. Be sure to accurately measure the liquid line  length.  After evacuation is complete, charge the unit  Do not disable the low‐pressure or high‐pressure  with R410A refrigerant through the liquid line service  switches.  port, using the amounts on the chart shown below.  Ensure the Air Handler filter is clean  Hallowell ACHP Line Set Charging Chart  Line set  Ensure the Air Handler Adjustments are set correctly.  Acadia 036 &   length  Acadia 024  Acadia 048  (ft)  Check that all supply and return registers are clear and  0‐10  9lb   12lb ‐ 8.0oz  not blocked.  11  9lb ‐ 0.6oz  12lb ‐ 8.6oz  12  9lb ‐ 1.2oz  12lb ‐ 9.2oz  To prevent personal injuries, wear safety glasses, protective  13  9lb ‐ 1.8oz  12lb ‐ 9.8oz  clothing, and gloves when handling refrigerant and observe  14  9lb ‐ 2.4oz  12lb ‐ 10.4oz  the following:   15 ...
  • Page 15: Step 8 - Check Charge 1

    INSTALLATION  The thermostat must be setup at this time to properly  NOTE: Above 60°F, charge the unit using the line set chart  work with your Hallowell Acadia. See the tables in Figure  (see step 7 or Appendix C). You may have to return in  5, Appendix A.  heating season and double check charge amount for optimal  efficiency.  Set the thermostat to Fan ON, ensuring air flow and  HEATING CHECK CHARGE PROCEDURE  jumpers are properly placed in the Hallowell Matched air    handler.  Test the emergency heat settings.  : R410A is miscible with POE oil in the  CAUTION Set the Fan to AUTO or ON as desired, then set the room  system.  Let the system run in normal operation for an  thermostat to COOL or HEAT. Wait for the appropriate  adequate amount of time after startup or a defrost  cycle to ensure an accurate sub­cooling reading.  time delay(s). Operate the unit for 30 minutes after initial    charge, continuously ensuring the thermostat setting will  not be satisfied. (Open windows or doors if necessary)  Operate the unit a minimum of 30 minutes before  checking charge.  NOTE: While waiting, be sure the line set is secure  and insulated separately. This is a good time to  Measure the liquid service valve pressure by attaching an  double check the installation procedure.  Check  accurate R410A rated gauge to 3/8” service port.  over the system for any unusual vibrations / noises.  Measure the liquid line temperature by attaching and  Set the room thermostat 10 degrees or more above or  insulating an accurate thermistor type or electronic  below desired room temperature allowing second stage  thermometer to the liquid line near the outdoor coil.   operation while charging.   This may bring on a third  Use the pressure – temperature chart to calculate sub‐ stage call from the thermostat and turn on auxiliary heat. ...
  • Page 16: Extras 1

    INSTALLATION  Extras  Ensure that all wiring and tubing is secure in the unit  before adding panels and covers. Securely fasten all    panels / covers and ensure all fasteners remain tight.  Zone Controls.  The only zone control that is factory authorized is the EWC  Tighten the service valve stem caps to 1/12‐turn past  UZC series of zone control.  The zone control will be wired  finger tight.  and set up according to the drawing in Appendix F.  This zone  control works very well with the Acadia as long as some rules  Leave the Owner’s Manual as well as the Installation  Manual with the customer. Explain the system operation  and periodic maintenance requirements outlined in the  manual.  Fill out the Dealer Installation Checklist and place in a  customer file.  Be sure to talk to the customer about the general  maintenance, shoveling around the unit and keeping it  clear of debris, basic thermostat use and the importance  of periodical filter changes.  Discourage the customer from set backs of the  thermostat program.  Ensure the supply registers are diffused properly.  Ensure the charge amount is written on the service  sticker provided on the electrical box cover of the  outdoor unit.  Talk to the customer about the defrost operation and  how it will effect the register temperature.  Be sure the customer knows where to purchase more air  filters.  Ensure the supply registers are defused away from heavy  traffic areas and not directly on the customer.  CARE AND MAINTENANCE  For continuing high performance, and to minimize possible  equipment failure, periodic maintenance must be performed  on this equipment. Frequency of maintenance may vary de‐ pending upon geographic areas, such as coastal applications.  Pay close attention to cleanliness of indoor / outdoor coils ...
  • Page 17: Hallowell Control Timers 1

    INSTALLATION  6. To protect the coil from damage, use anti‐freeze in  efficient operation of the unit.  If there are any questions  the hydronic loop to prevent freezing.  A freeze‐stat  about how the unit is operating, contact Hallowell factory  can also be used to protect the coil.    support. 7. Hydronic coils added internally to the Hallowell AHU  are not approved.    Installing the system with a hot air furnace    Hallowell will approve a parallel furnace installation pending  a factory consultation.   The duct work must be installed with  dampers so that the air flow will not short cycle through  either system when it is on.  An isolation relay must be used  so that the furnace is not allowed to operate when the Acadia  is running.    Hallowell Control Timers    1. Temperature Stability Timer (5 Min)– In order for the  system to change operational BINS from one to another,  the system must sense a temperature change in the new  BIN for at least five minutes.    2. Defrost Lockout Timer (45 Min) – This timer prevents the  system from going into another defrost within 45  minutes of the prior defrost.    3. Y2 Validation Timer (1 Min) – The outdoor unit must  sense a Y2 call from the thermostat for at least 1 minute  before it will change stages.  This will prohibit nuisance  staging of the outdoor unit.   ...
  • Page 18: Troubleshooting

    Sensor Fault  motor.  Coil Temperature Sensor    8 Flashes, OFF for 3 Seconds  Fault  Temperature Sensor Fault  Interstage Temperature  NOTE:  Make sure the system power is off before  9 Flashes, OFF for 3 Seconds  Sensor Fault  troubleshooting the temperature sensors.  10 Flashes, OFF for 3  Spare Temperature Sensor    Seconds  Fault  On the upper right hand corner of the outdoor unit control    board is the plug for the temperature RTD sensors.  You will  If the Hallowell Acadia has encountered an operational error,  need to unplug the sensors from the control board by pulling  the outdoor unit will shut down for a period of 10 minutes,  the plug straight off the control board.  Check the connection  after which it will attempt to restart in its last known operat‐ of the wires in the plug making sure that the wire is not  ing mode. If the unit is able to restart and run for 30 continu‐ broken or the insulation is in the plug.  You will need a  ous minutes without an error, all error codes will be cleared  thermocouple reader and sensor, and a multi‐meter.  Using  and normal operation shall continue. If, however, this  the thermocouple take the temperature at each sensor.  attempt to restart fails, the outdoor unit will shut down for  The Blue wire sensor is the coil sensor and is located on the  another 10 minutes. If a third error occurs within 30 minutes  second distributor tube from the bottom of the coil.  The  of the original error, the unit will shut down all operation and  Yellow wire sensor is the inter stage sensor and it is located  activate a MAINTENANCE REQUIRED output. This should  on the suction line going to the primary compressor.  The ...
  • Page 19: Heating Mode Operation 1

    Troubleshooting  See the chart below.  If the unit is not changing mode, do the  Resistance Vs Temperature  Temperature sensor fault test.   Temperature (°F)  Resistance (Ω)    Heating Mode Operation  ‐40  84.21  The Hallowell Acadia operates with 6 modes of heating  ‐30  86.41  capacity available.  These modes are as follows:  ‐20  88.61    Mode 1: Single cylinder primary compressor  ‐10  90.81    0  93.01  Mode 2: Two cylinder primary compressor    10  95.2  Mode 3: Primary Two cylinder plus W1 (1  stage auxiliary  20  97.38  heat)    30  99.57  Mode 4: Primary Two cylinder and Booster compressors.  40  101.74    Mode 5: Primary Two cylinder and Booster compressors plus ...
  • Page 20: Cooling Mode Operation 1

    Y2O  Y2O  Y2O  Y2O  Y2O  the input signal from the thermostat.  If you have an input  Table 2: State of Y2OUT and Heat Mode vs. Bins  from the thermostat and one of the LEDs is lit, verify the    output to that LED on the output plug on the upper left of  At any time while the thermostat is in heating mode, the  control board for 24VAC.  If 24VAC is not present, replace the  system can be placed into emergency heating mode,  control board.  energizing the installed auxiliary heating system.  If the contactor is not pulled in, check for 24VAC at the    contactor coil.  If you have 24VAC, replace the contactor. If  Cooling Mode Operation  you do not have 24VAC, replace the wiring to the contactor.  The Hallowell Acadia operates with 2 stages of cooling  Check the contactor. If it is pulled in, check the starting gear  capacity available, based on the level of demand from the  of the compressor.  Check the start and run caps and the  thermostat.  Cooling mode is limited to operation when the  starting relays.  If you find a problem with the starting gear,  outdoor air temperature is above 50F to ensure correct  replace the component.   If it is all ok, check the compressor  operation of all components in the system.  The 2 stages of  windings for an open or shorted winding.  If the compressor is  cooling capacity are illustrated below, with the modes of  bad, contact Hallowell International LLC for a new  operation being identical to the modes of operation used in  compressor with the provisions for the Oil Equalization Line.   heating mode.    COOLING  Booster Compressor will not start    Check the control board for the BE output LED.   ...
  • Page 21: Appendix A - Settings

    APPENDIX A ­ SETTINGS  Figure 1 – Factory Supplied Air Handler Control Board.        Hallowell TXV Kit installation Instructions:    1. Ensure coil has not been exposed to atmospheric pressure for more than 15 minutes.    2. Remove indoor coil inlet cover at the distributor body inlet.  Use back‐up wrench to prevent damage.    3. Install the TXV to the distributor using a back‐up wrench to prevent damage.  Tighten finger tight then ¼ turn more.    4. Connect equalizer tube of the TXV to ¼ in equalizer fitting on the vapor line.  Be sure to remove the Schrader valve located in  the fitting on the coil.    5. Install the indoor coil inlet tube.  Use back‐up wrench to prevent damage.    6. Attach TXV bulb to horizontal section of suction line using bulb strap and insulate.    7. Proceed with remainder of unit installation.    8. Refer to air handler installation manual for further installation of air handler unit.  ‐ 20 ‐...
  • Page 22 APPENDIX A ­ SETTINGS  Figure 2 – Air Flow Chart for Air Handler        HIGH SPEED COOLING AND HEAT PUMP AIRFLOW (CFM) Model Jumper Settings Cool Adjust m3/min m3/min m3/min 1010 28.6 1230 34.8 2020 57.2 23.1 1007 28.5 1759 49.8 26.4 1202 34.0 1989 56.3 20.0 25.6 1607 45.5 26.2 1076...
  • Page 23 APPENDIX A ­ SETTINGS  Figure 4 – Control Jumpers                  When the Economy Jumper is shorted it will disable the W1 output on a second stage call when outdoor temperature is between  35˚F to 25˚F.  ‐ 22 ‐...
  • Page 24 APPENDIX A ­ SETTINGS  Figure 5 – Thermostat Settings                Menu  FACTORY DEFAULT  CORRECT SETTING  COMMENTS  Number  SETTING  1  MS 2  HP 2  Selects appropriate control style (2 stage heat pump)  2  (GAS)  ELE  Indoor blower control (furnace or thermostat)  3  DAYS(7)  0  7 day, 5 day plus weekend, or no program  4  PS (4)  n/a  Program set points during each day  COOL OFF HEAT (EMER)  System switchover or operating mode with heating,  5  COOL OFF HEAT AUTO  AUTO  cool, auto changeover, or off.  Pre‐Stage heating/cooling steps to reach desired  6  E (ON)  ON ...
  • Page 25 APPENDIX A ­ SETTINGS  1.) Control System Type:  14.) Beeper On/Off:  This control can be adapted for many uses; however, operation of  Turn the key press beeper On or Off.  the Hallowell Acadia requires the HP2 setting.      15.) Heat Temperature Limit:  2.) Indoor Fan Operation:  The highest allowable temperature for heating mode may be  GAS or Electric (ELE) fan operation.  The system requires the  changed here.  The allowable range for the Hallowell Acadia is 62°F  thermostat to energize the indoor fan.  If a separate heating system  to 80°F.  When this is active, the “temperature limit” icon is  controls the fan, select GAS.  displayed to the left of the set point temperature, and if an attempt    is made to adjust the set point above the limit, the “temperature  3.) Programming:  limit” icon will flash.  The control can be setup to run individual programs for each day of    the week, a 5‐day block with separate weekend parameters, or a 0‐ 16.) Cool Temperature Limit:  day block to disable programming.  For the system to operate most  The lowest allowable temperature for cooling mode may be  efficiently, 0‐day block, or no programming, is recommended.  changed here.    The allowable range for the Hallowell Acadia is 65°F    to 85°F.  When this is active, the “temperature limit” icon is  4.) Program Set Points:  displayed to the left of the set point temperature, and if an attempt  This control can be programmed with 2 or 4 set points during the  is made to adjust the set point below the limit, the “temperature  day.  If using 0‐day block, or no programming, this setting is not  limit” icon will flash.  applicable.     ...
  • Page 26: Appendix B - Wiring Diagrams

    APPENDIX B – WIRING DIAGRAMS  Figure 6 – Line Voltage        ‐ 25 ‐...
  • Page 27 APPENDIX B – WIRING DIAGRAMS  Figure 7 – Hallowell Proprietary Control      ‐ 26 ‐...
  • Page 28 APPENDIX B – WIRING DIAGRAMS  Figure 8 – Air Handling Unit          Figure 9 – Thermostat    ‐ 27 ‐...
  • Page 29 APPENDIX B – WIRING DIAGRAMS  Figure 10 – Entire Control          ‐ 28 ‐...
  • Page 30: Appendix C - Acadia Charging R410A

    APPENDIX C – ACADIA CHARGING R410A  Figure 11 – Hallowell Acadia Charging Chart  HALLOWELL ACADIA Charging Chart Outdoor Air Temp.  Sub‐Cooling  Liquid Line Temp.  3/8" Service Valve  7/8" Service Valve  Charging Port  (Deg F)  (Deg F)  (Deg F)  (PSIG)  (PSIG)  (PSIG)  60 to 50  12 to 15  90 to 100 325 to 390 330 to 400  100 to 140 50 to 40  13 to 18  90 to 80 280 to 360 290 to 365  80 to 115 40 to 30  18 to 25  75 to 85 280 to 350 280 to 350  95 to 65 30 to 25  18 to 27  70 to 80 280 to 340 275 to 345  75 to 60 25 to 20 ...
  • Page 31 APPENDIX C – ACADIA CHARGING R410A  Figure 12 – Pressure/Temperature Chart R410A    Deg  Deg  Deg  Deg  Deg  Deg  Deg  Deg  Deg  PSIG  PSIG  PSIG  PSIG  PSIG  PSIG  PSIG  PSIG  PSIG  F  F  F  F  F  F  F  F  F        40  ‐7  82  22  124  109  444       ...
  • Page 32: Appendix D - Outdoor Unit Mounting

    APPENDIX D – OUTDOOR UNIT MOUNTING  Figure 13 – Typical Unit Mounting      ‐ 31 ‐...
  • Page 33: Appendix E - Acadia Components

    APPENDIX E – ACADIA COMPONENTS  Figure 14 – Acadia Components          ‐ 32 ‐...
  • Page 34: Appendix F - Ewc Zone Control

    APPENDIX F – EWC ZONE CONTROL  Figure 15 – EWC Zone Control Wiring                ‐ 33 ‐...
  • Page 35: Appendix G - Specification Sheets

    7/8 in  2  R410A Initial Charge  (Field Charge)  9 lbs  12 lbs  12 lbs  Charge per ft of line set after 10ft    0.6 oz  0.6 oz  0.6 oz  Handling Weight  460lbs  475lbs  500lbs  Matched Variable Speed Air Handler  AVG24B3XH21  AVG36C3XH21  AVG48D3XH21  Coil Model Number  373‐23793‐011  373‐23793‐002  373‐23793‐006  dBA Cooling and Heating (Mode 2 / Mode 3)   60/61  60/61  61/62  1.  Use dual element fuses or HACR circuit breakers  2.  The unit does NOT come pre‐charged with R410A refrigerant from the factory.  The unit comes from the factory with a 50 PSI charge of nitrogen.  After install evacuation; units with line sets of 10 feet or less receive 12 lbs of liquid R410A refrigerant.  For line sets greater than 10 feet, admit  .6oz of refrigerant for each additional foot.  3.  The Acadia Systems require both liquid and vapor lines to be insulated for maximum heating performance.  4.  Sound pressure level re: 20µPA measured at 10 feet. Noise levels were measured in an installed condition in the field with a Type I sound level  meter. These measurements are intended to be used in a precursory review; actual levels vary per each individual installation.  Inquiries and  Concerns regarding specific applications should be reviewed by a qualified acoustical consultant.  5. All specifications are subject to change at the sole discretion of Hallowell International without notice and without inducing obligation or liability.   ‐ 34 ‐...
  • Page 36 APPENDIX G – SPECIFICATION SHEETS                                                                                 ...
  • Page 37 APPENDIX G – SPECIFICATION SHEETS  Physical Dimensions of the Outdoor Unit      Model  Dimensions (Inches)  Service Valve Size     A  B  C  Liquid  Vapor  ACADIA024  48‐1/2  27‐7/8  31  3/8  3/4  ACADIA036  48‐1/2  27‐7/8  31  3/8  7/8  ACADIA048  48‐1/2  33‐7/8  31  3/8  7/8    Physical Dimensions of the Matched Variable Speed Air Handler      Dimensions (Inches) Wiring Knockouts   Refrigerant  Connection Line  Models ...
  • Page 38 APPENDIX G – SPECIFICATION SHEETS  Configurations of the Matched Variable Speed Air Handler        Configuration of the Matched Hallowell Outdoor Split System Heat Pump        ‐ 37 ‐...
  • Page 39: Contractor Check List

    Contractor Check List  Check list for the contractor to discuss with the home owner.  1. Review thermostat operation with the owner.  a. How the system works. (Staging of the system)_________  b. How to clear the change filter reminder.___________  c. How to set the mode of operation for cooling or heating.__________  d. How to set the time on the thermostat.____________  e. What the icons mean on the thermostat “call for service”, “stage 1”, “stage 1+2”.________  When you should see the different icons.___________  2. Go over the programming of the thermostat the consequences of setbacks.  a. What happens when the thermostat is programmed for setbacks.___________  3. Go over coil maintenance with the owner.  a. How to change the filter(s).__________  b. When to change the filter(s).___________  c. How to brush or vacuum down the outdoor coil from grass clippings.__________  d. How to rinse down the outdoor coil 2 to 3 times a year.___________  4. Where the owner can pick up replacement filters.  a. Size of the filter(s).________  b. Type of filters recommended.__________  c. Best place to get the filters._________  5. Maintenance of the outdoor system; keeping the coil clear of snow and ice.  a. Keep the unit shoveled out._________  b.
  • Page 40: Data Sheet

    DATA SHEET  Homeowner Information  Installer Information    Name    Company Address Line 1    Address Line 1 Address Line 2    Address Line 2 City    City State / Prov.    State / Prov. Postal Code    Postal Code Phone #    Phone #     Equipment Information  Outdoor Unit Model #    Outdoor Unit Serial #    Air Handler Model #    Air Hander Serial #        Installation Information  Heat Kit Installed (Y/N)  ...

This manual is also suitable for:

Acadia 036Acadia 048

Table of Contents