New Outdoor Unit Placement

Remove existing outdoor unit prior to placement of new outdoor unit. See Unit Dimensions on page 2 for sizing mounting
slab, platforms or supports. Refer to figure 4 for mandatory installation clearance requirements.
CLEARANCE ON ALL SIDES
6 (152)
12 (305)
36 (914)
MINIMUM CLEARANCE BETWEEN
TWO UNITS
DETAIL A
Install unit away
from windows .
DETAIL C
If
unit
coil
cannot
be
mounted away from prevail-
ing winter winds, a wind bar-
rier should be constructed.
Size barrier at least the
same height and width as
outdoor unit. Mount barrier
24 inches (610 mm) from the
sides of the unit in the direc-
tion of prevailing winds as il-
lustrated.
506695−01 11/10
INCHES (MILLIMETERS)
ACCESS PANEL
NOTES:
S
30 (762)
S
LINE SET
CONNECTIONS
24 (610)
Figure 4. Installation Clearances
Two 90° elbows
installed in line set will
reduce line set vibration.
PREVAILING WINTER WINDS
WIND BARRIER
INLET AIR
INLET AIR
INLET AIR
Figure 5. Placement, Slab Mounting and Wind Barrier
Clearance to one of the other three
sides must be 36 inches (914mm).
Clearance to one of the remaining
two sides may be 12 inches
(305mm) and the final side may be
6 inches (152mm).
DETAIL B
These units operate under a wide range of weather conditions; therefore,
several factors must be considered when positioning the outdoor unit. The
unit must be positioned to give adequate clearances for sufficient airflow
and servicing.
S
Install unit level or, if on a slope, maintain slope tolerance of 2 degrees
(or 2 inches per 5 feet [50 mm per 1.5 m]) away from building structure.
S
Install the unit high enough above the ground or roof to allow adequate
drainage of defrost water and prevent ice or snow build−up.
S
In heavy snow areas, do not locate the unit where drifting will occur.
The unit base should be elevated above the depth of average snows.
Stand−off kits are available for order using either catalog numbers
94J45 (4 each) or 30K79 (20 each).
S
When installed in areas where low ambient temperatures exist, locate
unit so winter prevailing winds do not blow directly onto outdoor unit.
S
Locate unit away from overhanging roof lines which would allow water
or ice to drop on, or in front of, coil or unto unit.
STRUCTURE
INLET AIR
MOUNTING SLAB MUST SLOPE
AWAY FROM BUILDING.
Page 6
MINIMUM CLEARANCE
ABOVE UNIT
48 (1219)
DISCHARGE AIR
GROUND LEVEL