6400 Power Pack
♦ GENERAL INFORMATION
Ratings:
Voltages: 120/230/277VAC, 50/60 Hz
Loads:
20A - 120/277VAC Ballast
20A - 120VAC Incandescent
1HP - 120/240VAC Motor
Output:
150mA @ 24VDC (with relay
connected)
Low Voltage Input:
Control ON:
12-24VDC
Hold ON:
12-24VDC
Hold OFF:
12-24VDC
Manual ON:
12-24VDC (momentary switch required)
Switching: SPST
Operating temperature: 0°C to 55°C (32°F to 131°F )
NOTES:
- Keep these instructions available for future reference.
- Indoor use only.
DESCRIPTION:
The 6400 Power Pack is the core for any low-voltage lighting control
system. It supplies low-voltage power to occupancy sensors and other
control devices and switches line voltage in response to signals from those
devices. It can be attached to existing junction boxes or mounted into
fixture wiring trays.
Low-voltage wiring should use at least 22 AWG wire. High-voltage
connections should use at least 14 AWG (12 AWG for 20A loads). Always
check local building codes.
The power pack features zero-crossing circuitry to maximize relay life.
♦ INSTALLATION
CAUTION: INSTALLATION BY A LICENSED ELECTRICIAN IS RECOMMENDED.
INSTALLATION AND USE OF THIS EQUIPMENT SHOULD BE IN ACCORDANCE WITH
PROVISIONS OF THE U.S. NATIONAL ELECTRICAL CODE, APPLICABLE LOCAL
CODES, AND PERTINENT INDUSTRY STANDARDS.
CAUTION: USE THIS DEVICE WITH COPPER WIRE ONLY.
CAUTION: IMPROPER WIRING CAN CAUSE DAMAGE TO THE POWER PACK,
LIGHTING SYSTEM, OCCUPANCY SENSOR(S), AND OTHER CONTROL DEVICES.
NOTE: POWER PACKS ARE DESIGNED TO ATTACH TO EXISTING OR NEW
ELECTRICAL ENCLOSURES WITH 1/2 INCH KNOCKOUTS.
NOTE: MOST APPLICATIONS REQUIRE UL LISTED, 18-22 AWG, 3-CONDUCTOR,
CLASS 2 CABLE FOR LOW-VOLTAGE WIRING. FOR PLENUM RETURN CEILINGS,
USE UL LISTED PLENUM-APPROVED CABLES.
NOTE: THIS POWER PACK IS A CLASS 2 OUTPUT POWER SUPPLY SUITABLE FOR
PARALLEL INTERCONNECTION OF UP TO 6 UNITS MAXIMUM. THIS POWER PACK
IS UL LISTED FOR INTERCONNECTION OF POWER SOURCES IN ACCORDANCE
WITH THE NATIONAL ELECTRICAL CODE.
WARNING: TO AVOID FIRE, SHOCK, OR DEATH, TURN OFF POWER
AT CIRCUIT BREAKER OR FUSE AND TEST THAT POWER IS OFF
BEFORE WIRING!
1) Verify power has been turned off at the circuit breaker.
2) Refer to the mounting and wiring diagrams (Figure 1, and Figure 2 or
Figure 3 as appropriate) and connect the wires as shown. Be sure all
wire nuts are secure. Refer to the LOW-VOLTAGE INPUTS section for a
description of the available switching options.
NOTE: AFTER INITIAL WIRING IS COMPLETED, DOUBLE-CHECK WIRING
DIAGRAMS TO VERIFY THE POWER PACK IS WIRED CORRECTLY.
3) Restore power at the circuit breaker.
♦ WIRING DIAGRAMS
Figure 1: Typical Mounting & Wire Connections
Figure 2: Basic Wiring
Figure 3: Multi-Sensor Wiring and Optional "Hold ON" Wiring
INSTRUCTIONS
BX1268A, 02/17/14

Advertisement

loading

Summary of Contents for Marktime 6400

  • Page 1 - Keep these instructions available for future reference. - Indoor use only. DESCRIPTION: The 6400 Power Pack is the core for any low-voltage lighting control system. It supplies low-voltage power to occupancy sensors and other control devices and switches line voltage in response to signals from those devices.