H Danger to life from poisoning by flue gas There is a danger to life from escaping flue gas. ▶ Ensure that flues and gaskets are not damaged. Greenstar 80mm Flexi RF Flue – 6721814542 2019/09...
Requirements Installation The flue installation must be fitted and terminated in accordance with your local regulations. Support Flues require adequate support throughout their entire run. Flue System Greenstar 80mm Flexi RF Flue – 6721814542 2019/09...
7. Fig. 3 Extension components Type of building Fire resistance single storey 30 minutes multi storey 90 minutes Table 7 Fire resistance of chimney material Greenstar 80mm Flexi RF Flue – 6721814542 2019/09...
▶ Mark the position of elbow support, ensuring that the mark is centred within the opening made in the chimney wall. ▶ Drill a Ø 10mm hole 60mm deep into the chimney wall. Fig. 8 Drilling security hole Greenstar 80mm Flexi RF Flue – 6721814542 2019/09...
▶ Place the elbow assembly in the chimney. ▶ Ensure that the elbow support is horizontal and the elbow centrally positioned with the chimney space. ▶ Secure the assembly with a screw as shown in fig. 11 Greenstar 80mm Flexi RF Flue – 6721814542 2019/09...
Page 9
Snap off the centralising spacer at the perforated section marked 80mm to suit the flue. Secure the centralising spacer around the flexible liner as shown in fig. 14 0010029250-001 Fig. 13 Flue spacer 0010029255-001 Fig. 15 Positioning spacers Greenstar 80mm Flexi RF Flue – 6721814542 2019/09...
1. Feed the flexible liner assembly into the chimney from the top. out. 2. Insert the adaptor into the support elbow. 4. Push the locking tabs in until they click into place and are locked. 0010028890-001 Fig. 17 0010029153-001 Fig. 16 Greenstar 80mm Flexi RF Flue – 6721814542 2019/09...
Secure the cowl (7) with the screws provided. If the chimney cowl is too large: ▶ Cut the chimney cowl down along the moulded marks and use the inner set of securing points. 0010029268-001 Fig. 20 Greenstar 80mm Flexi RF Flue – 6721814542 2019/09...
Fitting the flue adaptor To ease the assembly of the flue components: ▶ Grease all seals lightly with solvent-free grease. ▶ Ensure all seals are seated properly and are in good condition. Greenstar 80mm Flexi RF Flue – 6721814542 2019/09...
▶ Do not modify flue elbows or the tee piece. Fig. 28 Assembling extensions and elbow 0010029160-001 Fig. 26 Cutting the flue extension The flue pipe must not be closer than 25mm to any combustible material. Greenstar 80mm Flexi RF Flue – 6721814542 2019/09...
Fig. 31 Connecting tee piece to appliance flue outlet 5. Align the two inspection plates with the seal. 6. Screw the two plates together with four self tapping screws. 0010029166-001 Fig. 33 Fixing inspection plates to chimney Greenstar 80mm Flexi RF Flue – 6721814542 2019/09...
3. Remove the screws that secure the inspection plate and slide the inspection plate away from the chimney. 0010029322-001 Fig. 35 Spare parts 0010029321-001 Fig. 34 Visual check Replace all end covers and the inspection plate after visual inspection of the flue system. Greenstar 80mm Flexi RF Flue – 6721814542 2019/09...
Need help?
Do you have a question about the Greenstar 80mm Flexi RF Flue and is the answer not in the manual?
Questions and answers