TX7322 Addressable Sounder Base Installation & Operation Manual Product Safety To prevent severe injury and loss of life or property, read the instruction carefully before installing the Addressable Sounder Base to ensure proper and safe operation of the system. European Union directive...
1 Introduction 1.1 Overview The TX7322 Addressable Sounder Base is an alarm warning device used to notify persons in the vicinity of the occurrence fire emergency in order the person to take appropriate measures. The unit adopt multi-application device starting from the types, parameters and wiring layout in single unit.
TX7322 Addressable Sounder Base Installation & Operation Manual a jurisdiction in your area or BS 5839 Part 1 and EN54. 2.2 Installation and Wiring 1. Install the TX3980-type base in the position where the Addressable Sounder Base will be installed. Following the arrow mark for the correct position. Do not over-tighten the screws otherwise the base will twist.
TX7322 Addressable Sounder Base Installation & Operation Manual Base Base Fig.4 Addressable Sounder Base with an upper cover or a detector 3 Addressable Sounder Base Configuration 3.1 Preparation The TX7930 handheld programmer is used to configure the address and other parameters of the Addressable Sounder Base.
Fig.10 Configuration information 3.3 Encoding Mode Setting The TX7322 Addressable Sounder Base has three different encoding modes such as non- coding mode, single-encoding mode and dual-encoding mode. Different encoding modes correspond to different ways of operation. It can be change the encoding mode by a programming tool.
3.4 Tone Setting The TX7322 Addressable Sounder Base has 16 kinds of different alarm tone and a kind of warning tone. The Tones of it can be change according to the project requirement by a programming tool. The detailed parameters of different tone are shown in Table 1.
Page 9
TX7322 Addressable Sounder Base Installation & Operation Manual 84.1 970Hz 1s off / 1s on 82.3 970Hz, 0.5s / 630Hz, 0.5s 86.2 500Hz - 1200Hz×3, 3.5s on / 0.5s off 87.4 2850Hz, 0.5s on / 0.5s off×3 / 1.5s off 87.4...
TX7322 Addressable Sounder Base Installation & Operation Manual Fig.14 Tone setting Fig.15 Success to setting Fig.16 Fail to setting 3.5 Read Configuration Under the main menu, as described in Section 3.2, the configuration parameters of the Addressable Sounder Base can be viewed by clicking the button 1“Read” or “1”, as shown in Figure 9.
TX7322 Addressable Sounder Base Installation & Operation Manual 2. Tone 16 – Volume dB(A) Table 3 Sound pressure level of tone 16 at different bus voltage with 3 meters away Horizontal Plane Vertical Plane Angle (3m) Max 28V Min 17.5V Max 28V Min 17.5V...
Page 12
TX7322 Addressable Sounder Base Installation & Operation Manual every half-year according to national codes or laws. Any fire alarm devices or any other components of the system must be repaired and/or replaced immediately as they fail. This product is not approved to EN54-23 (Beacon Functionality) and must not be used as a visual alarm device or to provide a primary warning notification of fire.