Incite Fire Taktis Vision Installation And Operation Manual

Incite Fire Taktis Vision Installation And Operation Manual

Fire alarm annunciator panel

Advertisement

Quick Links

Fire Alarm Annunciator Panel
Taktis Vision
Installation and Operation Manual
Man-1161IN Rev. A
*Man-1161IN*
Taktis Vision Installation & Operation Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Taktis Vision and is the answer not in the manual?

Questions and answers

Summary of Contents for Incite Fire Taktis Vision

  • Page 1 Fire Alarm Annunciator Panel Taktis Vision Installation and Operation Manual Man-1161IN Rev. A *Man-1161IN* Taktis Vision Installation & Operation Manual...
  • Page 2 Safety Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work act 1974 to ensure as reasonably as is practical that the article will be safe and without risk to health when properly used. An article is not regarded as properly used if it is used ‘without regard to any relevant information or advice’...
  • Page 3: Table Of Contents

    Contents i Section 1 Introduction ........................1 Taktis Vision Annunciator Features ......................1 Related Documentation..........................1 Section 2 Overview .......................... 2 Fascia Layout..............................2 Internal Features ............................3 Section 3 Installation ........................4 Before You Begin ............................4 General Installation Checklist........................4 Mounting the Surface Enclosure ........................
  • Page 4: Introduction

    Installation Manual http://www.tba.pdf Operation Manual http://www.tba.pdf Using your Smart-phone, tablet or device install a third party QR Code Reader and scan the code to view the doc- uments. Installation Manual Operation Manual Man-1161IN Rev.A Taktis Vision Installation & Operation Manual...
  • Page 5: Overview

    235.0 Description Description Enclosure lid fixing screw Display ambient light sensor Enclosure lid Enclosure hinge Touch panel display Enclosure knock-out (for cable entry) Enable keyswitch (Enables Access Level 2) Enclosure back box Man-1161IN Rev.A Taktis Vision Installation & Operation Manual...
  • Page 6: Internal Features

    Reboot button (panel firmware dependent) No function Write Enable switch No function No function Network terminals (Net in, Net out) No function Not used Processor reset button USB to PC communications port Buzzer Man-1161IN Rev.A Taktis Vision Installation & Operation Manual...
  • Page 7: Installation

    1/ Open the enclosure by removing the screw located at the top-centre. The enclosure lid hinges downwards. Re- move hinge pins by pulling inwards. Disconnect earth wire and put enclosure lid safely to one side. Figure 3-1 Opening the Enclosure Man-1161IN Rev.A Taktis Vision Installation & Operation Manual...
  • Page 8 Fix the enclosure back box using suitable fixings, through all fixing points. Figure 3-2 Surface Enclosure Back Box Dimensions 230.6 190.6 Ø5.0 Ø5.0 ALL DIMENSIONS IN MM NOT TO SCALE Man-1161IN Rev.A Taktis Vision Installation & Operation Manual...
  • Page 9: Trim Ring (Where Specified)

    NOT TO SCALE Note: 175mm X 240mm are the advised wall cut-out dimensions. The diagram below shows side view of the enclosure within the trim ring. Figure 3-4 Trim Ring with Enclosure in Place Man-1161IN Rev.A Taktis Vision Installation & Operation Manual...
  • Page 10: Installing The Trim Ring

    Installation 3 Installing the Trim Ring The diagram below illustrates trim ring fitting options. Figure 3-5 Trim Ring Fixing Centres Figure 3-6 Trim Ring Fold Tabs Man-1161IN Rev.A Taktis Vision Installation & Operation Manual...
  • Page 11: Fixing The Enclosure Back Box To Trim Ring

    Use four, M4 x 8mm machine screws in conjunction with M4 plain washers to fix enclosure back box to the trim ring. Figure 3-7 Fixing the Enclosure Back Box to the Trim Ring Man-1161IN Rev.A Taktis Vision Installation & Operation Manual...
  • Page 12: Mounting The Flush Enclosure

    Figure 3-9 Flush Enclosure Back Box Dimensions 240.0 50.0 234.0 190.6 Ø4.5 Ø4.5 ALL DIMENSIONS IN MM NOT TO SCALE Note: 175mm X 240mm are the advised wall cut-out dimensions. Man-1161IN Rev.A Taktis Vision Installation & Operation Manual...
  • Page 13: Cabling

    “fire alarm - do not switch off”. The mains supply must include an earth conductor connected to the fixed installation earthing system of the building. Man-1161IN Rev.A Taktis Vision Installation & Operation Manual...
  • Page 14: Connecting To The Annunciator

    The current consumption of the Annunciator with the PF input activated is 232mA (buzzer silenced, touch panel back-light on). The effect on the battery capacity of the power supply which is powering the Annunciator should be considered when connecting Annunciators to a system. Man-1161IN Rev.A Taktis Vision Installation & Operation Manual...
  • Page 15: Wiring Scheme

    This fault scenario could clearly be extended to more network points and this would add 1200 metres of cable length in each case. A sensible fault tolerance limit has therefore to be suggested to enable the performance of the system to be predict- Man-1161IN Rev.A Taktis Vision Installation & Operation Manual...
  • Page 16: Cable Type

    360-degree ring. Simply stripping back the insulation of the cable and connecting “pigtails” to earth is not recommended. Shield cable is connected at one end only. When using this method it is also important to ensure that the gland body is electrically bonded to the panel enclo- sure. Man-1161IN Rev.A Taktis Vision Installation & Operation Manual...
  • Page 17: Configuration

    Access Level 3 is required to set the Annunciator address. The default code for Access Level 3 is ‘333333’. Press ‘User Controls’. Press ‘Engineer Options’. Press ‘Configuration’. Press ‘Learn Panel’. Exit out of menu. 3-10 Switch the ‘Write Enable’ switch to position 1. Man-1161IN Rev.A Taktis Vision Installation & Operation Manual...
  • Page 18: Download A Configuration

    Using the number buttons key in your login code and press ‘Submit’ button to accept. Access Level 3 is required to set the Annunciator address. The default code for Access Level 3 is ‘333333’. Press ‘Engineer Options’. Press ‘Configuration’. Press ‘Export Configuration’. Man-1161IN Rev.A Taktis Vision Installation & Operation Manual...
  • Page 19: Section A

    3 x 20 mm and 2 x 28 mm knockouts in back Finish Epoxy powder coated Colour Lid & Box, BS 00 A 05 fine texture Weight 2 Kg maximum IP Rating IP30 Man-1161IN Rev.A Taktis Vision Installation & Operation Manual...