Refrigerant Gas Sensor For Occupied Spaces OVERVIEW The AquiTron AT-G-ALERT detects refrigerant leaks in occupied spaces. The detector is for indoor applications. It is housed in an ABS enclosure that fits into most 47mm depth 2-gang UK electrical back boxes (not included).
Page 3
Figure 3. AT-G-ALERT Proper vs. Improper Placement. Mount the AT-G-ALERT according to the above considerations, product dimensions, and maximum wiring lengths. SAFETY INSTRUCTIONS CODE COMPLIANCE: Comply with all local and national laws, rules, Failure to install and operate the unit in accordance with these wiring codes, and regulations associated with this equipment.
Page 4
CONFIGURATION PIN 1 - RESTART PIN 6 - ALARM LATCHING Off: Normal Operation (Default) Off: Alarms automatically reset (Default) On: Restart AT-G-ALERT On: Alarms latch and require manual reset PIN 2,3 - ALARM ON DELAY PIN 7 - BUZZER DISABLE Off,Off: No Delay (Default) Off,On: 5 miniute Delay Off: Buzzer enabled (Default)
Page 5
Example of a custom faceplate Example of a UK back box Mounting tabs Direction arrows (x2) for proper mounting. Brushed Aluminium Effect Sensor type / calibration and ID/ serial number labels Test point access holes (x2) Replaceable sensor module Sensor alignment ribs (x3) Figure 9.
Page 6
GENERAL CALIBRATION PROCEDURE 1. Verify that the detector is NOT in alarm and does not have a fault condition (i.e., it must not have a continuous orange LED). 2. Verify that the calibration gas is in a balance of air, not Nitrogen (N2). 1.