Safety Warning Only professional technicians are allowed for installation and maintenance. Installation in any damp, condensed-phase environment with inflammable and explosive gas is forbidden. When the product is being installed or maintained, the power must be switched off. You are prohibited from touching the conductive part when the product is operating.
NR8-200、NR8-630 Electronic Overload Relay Use Purpose NR8-200, NR8-630 electronic overload relay (hereinafter referred to as relay) is applicable to circuits with frequency of AC 50Hz or 60Hz, rated operating voltage up to 690V and current from 80A to 630A. It is used for overload protection and phase-failure protection of 3-phase AC motor.
NR8-200、NR8-630 Electronic Overload Relay 3.2 Operation and commissioning Table 4 Indicator status Indicator status Circuit working status Green light flashing, red light off Normal Green light flashing, red light on Overload delay Green light on, red light flashing Phase-failure delay...
NR8-200、NR8-630 Electronic Overload Relay Table 5 Analysis and Troubleshooting of Faults Symptoms Cause anaylsis Troubleshooting method and precautions Change to product with bigger size. Size is too small Misoperation of thermal The set current value is smaller than the actual...
Page 8
NR8-200、NR8-630 Electronic Overload Relay QC PASS NR8-200、NR8-630 Electronic Overload Relay IEC/EN 60947-4-1 Check 23 Test date: Please see the packing ZHEJIANG CHINT ELECTRICS CO., LTD.