The Series 2800 Current to Pressure Transducer converts a current
input to a linearly proportional pneumatic output pressure. This unit
utilizes a closed loop pressure feedback system that closely controls
output and compensates for vibration, mounting angle, temperature, and
supply pressure variations. These characteristics make this unit ideal for
field mounting on a valve. The control mechanism is a piezoceramic
actuator encapsulated in a protective skin, which provides a constant
defense against humidity and contaminants. These features make this
unit ideal for use in demanding applications. The 2800 also comes in a
NEMA 4X enclosure and is field reversible. It is FM and CSA approved
intrinsically safe, as well. For ease of installation, this model has input
and output ports on both the front and back and can be easily panel
mounted.
Model
Input
Output
2813-WP
4-20 mA
3-15 psig (0.2-1.0 bar)
4-20 mA
2816-WP
6-30 psig (0.4-2.1 bar)
W.E. ANDERSON DIV., DWYER INSTRUMENTS, INC.
P.O. BOX 358 • MICHIGAN CITY, INDIANA 46361 U.S.A.
Series 2800 Current to Pressure Transducer
Specifications - Installation and Operating Instructions
1
[25.4]
Ø1/8
[Ø3.17]
1-1/2
[38.1]
MOUNTING HOLES
#10-32 UNF-2B X 3/8 DP
2 PLCS
2-15/16
[74.7]
1-51/64
[45.7]
3-11/16
[93.7]
1-19/64
2-3/16
[33.0]
[55.4]
SPECIFICATIONS
Service: Oil free, clean dry air filtered to 40 microns.
Input Signal: 4-20 mA.
Air Supply: Minimum: 5 psig (0.3 bar) above maximum output;
Maximum: 100 psig (6.9 bar).
Output: 3 to 15 psig (0.2 to 1.0 bar), 6 to 30 psig (0.4 to 2.1 bar).
Accuracy: ±0.1% of span.
Hysteresis: ±0.1% of span.
Repeatability: ±0.1% of span.
Deadband: 0.02% of span.
Power Requirement: Loop powered.
Temperature Limits: Operating: -40 to 160°F (-40 to 71°C); Storage: -
40 to 200°F (-40 to 93°C).
Pressure Connections: 1/4˝ female NPT.
Electrical Connection: 1/2˝ female NPT.
Air Consumption: 0.025 scfm (0.01 l/s) at midrange typical.
Output Capacity: 4.5 scfm (2.1 l/s) at 25 psig (1.7 bar) supply; 12.0
scfm (5.7 l/s) at 100 psig (6.9 bar) supply.
Enclosure: Chromate-treated aluminum with epoxy paint.
Enclosure Rating: NEMA 4X (IP65) and Intrinsically safe.
Weight: 0.8 lb (0.37 kg).
Agency Approvals: CSA, CE, FM.
Phone: 219/879-8000
Fax: 219/872-9057
Bulletin V-4
22 GA. WIRE LEADS
APPROX. 18˝ LONG
POS, NEG, GRD
1/2 NPT
Ø1-1/8
[Ø28.7]
3-1/8
IN & OUT PORTS
[79.2]
1/4-18 NPT
4 PLCS
25/64
[9.72] 49/64
33/64
[19.4]
[13.1]
www.dwyer-inst.com
e-mail: info@dwyer-inst.com

Advertisement

loading

Summary of Contents for W.E. Anderson 2800 Series

  • Page 1 Enclosure Rating: NEMA 4X (IP65) and Intrinsically safe. Weight: 0.8 lb (0.37 kg). Agency Approvals: CSA, CE, FM. Phone: 219/879-8000 www.dwyer-inst.com W.E. ANDERSON DIV., DWYER INSTRUMENTS, INC. Fax: 219/872-9057 e-mail: info@dwyer-inst.com P.O. BOX 358 • MICHIGAN CITY, INDIANA 46361 U.S.A.
  • Page 2 INSTALLATION Equipment Ratings: The Series 2800 transducer is a force balance device in which the piezo Intrinsically safe for Class I, II, and III, Division 1, Groups C, D, E, F, and actuator is positioned in relation to a nozzle as the input signal is varied. G hazardous (classified) locations and intrinsically safe for Class I, Zone The application of an electrical signal causes axial movement of the 0, Group IIB hazardous (classified) locations and suitable for Class I, II,...
  • Page 3 Reverse Acting Calibration MAINTENANCE When calibrated to operate in the reverse acting mode the minimum NOTICE Under normal circumstances, no maintenance should be input signal produces the maximum output pressure and increasing the required. input signal results in decreasing the output pressure. Setting the unit to operate in the reverse acting mode is accomplished by positioning Cleaning internal electrical switches.
  • Page 4 Contact customer service to receive a return goods authorization number before shipping. ©Copyright 2011 Dwyer Instruments, Inc. Printed in U.S.A. 10/11 FR# R2-443362-00 Rev. 1 Phone: 219/879-8000 www.dwyer-inst.com W.E. ANDERSON DIV., DWYER INSTRUMENTS, INC. Fax: 219/872-9057 e-mail: info@dwyer-inst.com P.O. BOX 358 • MICHIGAN CITY, INDIANA 46361 U.S.A.