the audible alarm will beep an abnormal condition code, see the "Troubleshooting Guide" section to identify and
correct the abnormal condition.
Important Information for Calibrating Controllers:
•
All STP-SCI's must all be calibrated prior to operation.
•
All three indicator lights will flash alternately in calibration mode.
•
The STP-SCI will calibrate only when the STP is free of abnormalities (faulty wiring, etc.), and a dispenser
handle is turned on within 10 minutes after calibration is initiated. Calibration must be done at zero flow.
False abnormal conditions will result if calibration is done with flow.
•
If electronic line leak detection is used make sure the STP-SCI is in calibration mode (all three lights flashing
alternately) before the dispenser handle is turned on. If it is not, the STP-SCI will not turn on and the line
leak detector will sense a fault. When the line leak detector senses a fault, it will not provide a dispenser
hook signal to the STP-SCI and the STP-SCI will not calibrate until the line leak detector is reset.
•
With blending dispenser systems calibrate all blended product STP-SCI's simultaneously by selecting the
mid-grade handle at the dispenser.
•
If power is lost to the controller the calibration data is retained.
Reset Button
SW 1
SW 2
L1 and L2
Incoming Power Supply
(50/60 Hz, Single Phase)
M1 and M2
To STP
Incoming Dispenser
Hook Terminals
RS 485
Communication Terminals
Grounding Terminals
Picture 1
4