AIR HEATER WD-A, WD-U
05
Assembly

05.07 Lamellae Adjustment, manual

1. First bend lamella  manually into the requested position.
2. Adjust remaining lamellae manually.
In case of corrections of the adjustment angle, the lamellae can be bent several times without problems.
Attention!
Blow-out louver 503-W is installed behind the blow-out louvers 500-W, 501-D.
Firstly adjust lamellae 500-W, 501-D, then proceed with 503-W as described above.

05.08 Lamellae Adjustment, automatic

Energy-saving louver 505-W/506-D-S, with switching device 678, prevents drifting of the primary air stream by high
temperature difference between primary air and room air.
By using the energy-saving louver, the drifting (thermal lift) of the primary air stream, especially during the heating-up
period, can be opposed. In choke position, there are single air jets, so that secondary air (room air) is mixed to the pri-
mary air stream. Thus, the air inlet - primary air stream is increased and cooled in the core.
By the control device (order No. 678), the temperature difference between nominal and real value of the room tempe-
rature is permanently determined.
Acc. to the determined difference as well as the adjustment at the control device (steepness of the control curve), the
servo-motor for the choke louver is activated.
> high temperature difference = choke position
< low or no temperature difference (heating-up finished) = unchoked position.
Blow-out louver
basic version Nr. 500 WD
W
1
Blow-out louver
rotated 90° No. 503 W
usable with 500 WD
1
1
9
9
Secondary air
No. 504
D
Blow-out louver
ceiling 4-directions No. 502 D
1
1
1
1
1
1