TPG CA Series Operation Manual

Variable frequency drive

Advertisement

VARIABLE FREQUENCY
DRIVE
Operation Manual
CA Series
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CA Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for TPG CA Series

  • Page 1 VARIABLE FREQUENCY DRIVE Operation Manual CA Series...
  • Page 2: Safety Precaution

    PREFACE Thank you for using TPG CA series drive. For proper operations and safety purposes, please do read and follow specific instructions contained in this manual before using the product. SAFETY PRECAUTION Please read this manual thoroughly and pay attention to the safety precautions marked with “...
  • Page 3 U/T1,V/T2,W/T3 terminal of drive at first. CAUTION a. The CA series outputs are designed to drive a three-phase induction motor. Do Not use for single-phase motor or using for other purposes. b. The main circuit and control circuit must be wired separately; control circuit must...
  • Page 4: Operation

    Operation DANGER a. Do Not open or remove the cover while power is on or during the drive operation. Do close up the cover before powering on the drive. Do Not remove the cover except for wiring or periodic inspection when power off. b.
  • Page 5 INTRODUCTIONS Features a. Special function key(SPEC): Programmable function key for forward/reverse running, jog speed, selection of primary/secondary frequency command…etc. b. Allow RS-485 communication interface control (Modbus RTU communication protocol). c. 6 sets of fault records: Record 4 types of information under fault condition, respectively. (fault code, output current, DC bus voltage, output frequency) d.
  • Page 6: Chapter 1 Cautions Before Installation

    Chapter 1 Cautions Before Installation 1-1 Product Verification The product has passed the strictest quality test before shipped out from the factory. However, the product might possibly sustain minor damages due to the impact, shaking, vibration, and other factors during the transportation. Please make sure to verify the following items after receiving this product.
  • Page 7 1-3 Common Specifications 1-3-1 The Features of Control and Operation ․Voltage vector sinusoidal PWM control(V/F control); Control method ․Switching frequency: 800Hz~16kHz Range of 0.1~400.00Hz frequency setting Resolution ․Operation panel: 0.01Hz of frequency ․Analog signal: 0.06Hz / 60Hz setting Resolution of output 0.01Hz frequency Overload...
  • Page 8 Command the drive via 3 programmable multi-function input Start method terminals(X1~X3): Forward command / Reverse command, 3-wire start/stop control, 8 sets preset speed control. 4 programmable input terminals: X1~X3 Multi-function Response time (1~255, unit: 1ms) inputs Refer to the chapter of function setting description for F5.19~F5.21.
  • Page 9: Chapter 2 Installation And Confirmation

    Chapter 2 Installation and Confirmation 2-1 Basic Equipment The drive needs the several components for the conjunctive operation. These components are called “basic equipment”, listed in the following: 2-1-1 Power Source: The voltage with three-phase or single-phase of the power source must meet the drive specifications. 2-1-2 MCCB or NFB: MCCB (Molded Case Circuit Breaker) or NFB (No Fuse Breaker) can withstand the inrush current at instant power-on and providing the overload and over-current protection to the drive.
  • Page 10 2-2-3 Specifications of Associated Accessories: The specifications of the accessories must be according to the specifications of the drive. Otherwise, the drive will be damaged and the lifetime of the drive will be shorten. Do Not add any power factor leading capacitor(RC, LC or other capacitance component) between the drive and motor to avoid any accidents.
  • Page 11 2-3 Descriptions of Terminal and Wiring Diagram 2-3-1 Wiring Diagram 2-3-2 Wiring Diagram a. Main Circuit Connection Type Symbol Function Description AC power Power Single-phase; sinusoidal power L1,L2 source input Source source input terminal.(200~240V) terminals The terminals output three phase Drive outputs to Motor U,V,W...
  • Page 12 Common terminal Common terminal for control for analog input power (12V/24V) and analog input control terminal (AI) c. Modbus Port (RJ-45) Type Function Description Communication transmission Differential input of terminal (DX+) RS-485 Modbus *Note 1 (RS-485) Modbus (RS-485) Communication transmission communication only uses terminal (DX-) pin1, 2.
  • Page 13: Chapter 3 The Setting Of Operation Panel & Remote Controller

    Chapter 3 The Setting of Operation Panel & Remote Controller 3-1 The Operation of the Operation Panel and Monitor Mode 3-1-1 The Operation of Operation Panel The operation of the operation panel includes fault messages and three modes. The switching methods are shown as below figure: The operation steps are shown in the below table (by default setting) Operation Steps Display...
  • Page 14 3-1-2 Monitor Mode There are eight monitor modes can be selected in the monitor mode. User can determine one of eight monitor modes as the main display on the operation panel. And the monitor mode can be switched as shown in below figure: Enter monitor mode Display 1...
  • Page 15 3-1-3 The Status of Multi-function Terminals The default setting of “Display 6” is the status of multi-function input terminals and the definition of each segment on the seven-segment display for 4 digits is shown as below figure: The definition of display shown in the below table: Display Terminal Status description...
  • Page 16 c.The selection of function number: Operation Steps Display 1.Press key to switch to the function number setting << mode after the function group is selected. And the function number is flashing. 2.Press ▲ key to increase the function number. 3.Press ▼...
  • Page 17 3-1-6 The Operation in the Monitor Mode Frequency command, motor speed(RPM), machine speed(MPM) are changeable under monitor mode. For example of frequency command change, the setting steps are shown in the following table. The operation steps are shown in the below table: Operation Steps Display 1.In the monitor mode, the display is shown as right.
  • Page 18 3-1-9 Save and Restore the Setting Value. a.The operation steps of saving drive function setting are shown in the below table: Operation Steps Display 1.Press key and enter the function setting mode. PROG 2.Press key and switch to the function number setting <<...
  • Page 19: Chapter 4 Parameter List

    Chapter 4 Parameter List Group List(Factory Setting: F0.18=0) brief version function detail function   (F0.18=0) (F0.18=1) Group Function Group Function  System status  System  Parameter locking  F0  F0  Parameters  Password protection  Power source voltage setting  Start command selection Start command selection  Frequency command  Frequency command selection  selection  Main display selection  F1  Main display selection  F1  SPEC key setting  SPEC key setting  Switching frequency  Switching frequency ...
  • Page 20 F0 System Parameters Range of Factory Func. Name Descriptions Unit Note Setting Setting 0: Software version 1: Drive model number 2: Drive rated current Drive F0.00 ─ ─ ─ Information 3: Drive running hours 4: Drive supply power time 5: Software checksum code 0: Parameters are changeable Parameter F0.01...
  • Page 21 F1 Operation Parameters Range of Factory Func. Name Descriptions Unit Note Setting Setting Start command Rotation direction FWD or REV FWD or REV command command FWD command REV command FWD, REV command Forward Operation panel Reverse Start Reverse 0~11 ─ F1.00 Command command...
  • Page 22 Range of Factory Func. Name Descriptions Unit Note Setting Setting *Note F1.05 Reserved Reserved ─ ─ ─ Frequency 0: In the monitor mode, frequency Command command cannot be changed. *Note Selection F1.06 0, 1 ─ 1: In the monitor mode, frequency (operation command is changeable.
  • Page 23 Range of Factory Func. Name Descriptions Unit Note Setting Setting SPEC Key -28 ~ +28 F1.17 Same function as multi-function input ─ Setting *Note 7 SPEC Key 0: Disable F1.18 Self-Holding 0, 1 ─ 1: Enable Function 0: Ramp to stop + DC braking F1.19 Stop Mode 1: Coast to stop...
  • Page 24 F2 Frequency Parameters Range Factory Func. Name Descriptions Unit Note Setting Setting Multi-speed Multi-speed Multi-speed Primary 50.00 level 3 level 2 level 1 Speed 0.00~ 0.01 *Note 1 F2.00 command command command (Preset 400.00 60.00 Speed 1) *Note 2 Preset 0.00~ 0.01 *Note...
  • Page 25 Range Factory Func. Name Descriptions Unit Note Setting Setting Primary The deceleration time of primary speed, 0.0~ F2.19 Deceleration preset speed 5~16, and jog speed. 3200.0 Time Acceleration Time of 0.0~ *Note F2.20 Acceleration time of preset speed 2 Preset 3200.0 Speed 2 Deceleration...
  • Page 26 Range of Factory Func. Name Descriptions Unit Note Setting Setting 50.0 Maximum *Note 1 F2.32 Output Maximum output frequency of drive 0.1~400.00 0.1Hz 60.0 Frequency *Note 2 Starting Starting frequency of drive’s output *Note F2.33 0.1~10.0 0.1Hz Frequency frequency. 0.1~50.0 *Note 3,4 *Note 3,4 Starting...
  • Page 27 F3 Control Parameters Range of Factory Note Func. Name Descriptions Unit Setting Setting The drive accelerate to the holding Holding frequency and running at constant 0.0~400.00 0.1Hz F3.00 *Note 9 Frequency speed. The drive runs at holding frequency Holding Time by constant speed and running the 0.0~360.0 0.1sec...
  • Page 28 Range of Factory Note Func. Name Descriptions Unit Setting Setting Response Time of Set the response time of automatic 1~255 F3.13 *Note 9 boost voltage range. Automatic Boost Voltage Automatic 0: Disable Voltage 0, 1 ─ F3.18 *Note 9 Regulation 1: Enable (AVR) Response...
  • Page 29 Range of Factory Note Func. Name Descriptions Unit Setting Setting Pulse Setting Set the pulse width of drive baking *Note F3.28 of Braking 10~90 signal. Transistor 0: Drive cannot be restarted 1: Drive can be restarted Operation 2: Ramp to stop (please refer to the Selection at *Note F3.30...
  • Page 30 F4 Protection Parameters Range of Factory Func. Name Descriptions Unit Note Setting Setting 0: Motor overload protection: Disabled Motor 1: Motor overload protection: Overload F4.07 Enabled(OL) ─ *Note 9 Protection 2: Motor overload protection of (OL) independent cooling fans: Enabled(OL) According 10%~150% to the...
  • Page 31 Range of Factory Func. Name Descriptions Unit Note Setting Setting Drive Overheat Set the temperature level of F4.14 1℃ 45~105 *Note 9 Pre-alarm Level warning alarm. Set the temperature dead band of Drive Overheat F4.15 0.1℃ temperature warning and fan 0.1~10.0 *Note 9 Dead Band...
  • Page 32 Range of Factory Func. Name Descriptions Unit Note Setting Setting Current over F4.36  the rated 30%~200% Current Limit current of drive during operation, F4.36 of drive *Note 9 (I-limit) the drive may adjust PWM ouput rated current and limit output current. The gain of the current limitation F4.37 Gain of I-limit 0.00~1.00...
  • Page 33 F5 Multi-function Parameters Range of Factory Func. Name Descriptions Unit Note Setting Setting “Pot knob” 0: Analog input gain Selection 1: Frequency command F5.00 ─ *Note 9 (Analog 2: Current limit Input) 3: Variable voltage of V/F pattern 0: Analog input gain 1: Frequency command AI Selection 2: Current limit...
  • Page 34 Range of Factory Func. Name Descriptions Unit Note Setting Setting 0: Disable ±1: Jog command ±2: Secondary accel/decel command switching Multi-function ±3: Multi-speed level 1 command -28 ~ +28 F5.19 Input ─ ±4: Multi-speed level 2 command *Note 7 Terminal X1 ±5: Multi-speed level 3 command ±6: reserved ±7: Reset command...
  • Page 35 Range of Factory Note Func. Name Descriptions Unit Setting Setting 0: Disable ±1: Running detection ±2: Constant speed detection ±3: Zero speed detection ±4: Frequency detection ±5: Overload detection(OLO) ±6: Stall prevention detection ±7: Low voltage detection(LE) ±8: Braking transistor is active detection(db) ±9: Restart after instantaneous power failure detection...
  • Page 36 Range of Factory Note Func. Name Descriptions Unit Setting Setting 1~5: Terminal adjust the response time. Continuous acceleration or UP/DOWN F5.32 Calibrating deceleration when over the ─ *Note 9 Time setting time 6: Edge trigger UP/DOWN Adjust UP/DOWN frequency on F5.33 0.00~400.00 0.01Hz 0.00...
  • Page 37: Communication Address

    F6 Special Parameters Factory Range of Func. Name Descriptions Unit Note Setting Setting The host uses the address to Communication F6.55 send and receive messages 0~254 ─ *Note 9 Address from the drive (0: Disable) 0: 4800bps F6.56 Baud Rate ─...
  • Page 38: Chapter 5 Parameter Setting Description

    Chapter 5 Parameter Setting Description F0 System Parameters 【F0.00】 Drive Information a. The function can display the horse power and software version. Check if the capacity of drive corresponding to the drive by this function. b. This manual and software version must be identical. The drive with different software version cannot duplicate drive parameters, or the drive operation panel will display Wr_F.
  • Page 39 【F0.18】 Function 0:brief 1:detail function 【 F0.20】 Default Setting a. Default settings are shown as the below table: Disable Clear fault records Default the factory setting of 60Hz (All SAv setting will be clear) Default the factory setting of 50Hz (All SAv setting will be clear) Store setting Resume setting Read the parameters from drive to digital keypad...
  • Page 40 F1 Operation Parameters 【F1.00】 Start Command Selection a. F1.00 = 0 (I) Motor forward and reverse directions are controlled by multi-function input terminals(X1~X4). (II) Start and motor rotating direction commands are controlled by multi-function input terminals(X1~X4) for forward and reverse command. (III) The motor stops running when the multi-function input terminals are set (closed) or open simultaneously.
  • Page 41 c. F1.00 = 2 (I) Motor rotating direction are controlled by multi-function input terminals (X1~X4). (II) Start command by “RUN” key of the operation panel and the rotation direction by forward or reverse command defined by multi-function input terminals (X1~X4). (III) The motor stops running when the multi-function input terminals (forward/reverse commands) are set closed or open simultaneously.
  • Page 42 h. F1.00 = 8 (I) Start command and the motor rotating direction are controlled by communication. (II) Forward and reverse commands are disabled. i. F1.00 = 9 (I) Multi-function input terminals(X1~X4) define as the reverse command and the motor runs at the reverse direction (counterclockwise). (II) Start command is given by communication control, and the motor rotating direction is defined by reverse command (defined by multi-function input terminals).
  • Page 43 b. F1.01 = 1 The frequency command can be set by function F2.00 using operation panel and ▼ key in the monitor mode as well. c. F1.01 = 3 MPM command is set using the operation panel. d. F1.01 = 4 UP/DOWN command control.
  • Page 44 【F1.06】 Frequency Command Selection (operation panel) The settings are listed as below: 0: The frequency command cannot be changed in the monitor mode to avoid the fault occurred by changing the frequency in the monitor mode. 1: The frequency command can be changed in the monitor mode. 【F1.07】...
  • Page 45 【F1.14】 Digits of Decimal Value (Machine Speed) Set the digits of decimal values (the range from 0~3 digits behind the decimal point) to display the higher resolution of machine speed for observation of machine speed. 【F1.17】 SPEC Key Setting The setting of SPEC key is similar as multi-function input setting; see the function F5.19 ~ F5.22 for SPEC key setting reference.
  • Page 46 【F1.21】 Switching Frequency a. The settings are listed in the below table: Setting Value Switching frequency 800Hz 2.5kHz 5kHz 7.5kHz 10kHz 12.5kHz 16kHz b. De-rate the output current of drive if the switching frequency setting value is over 4. c. The higher switching frequency has less noise. But using higher switching frequency must consider the cable length between drive and motor and must be adjusted according the connection distance between drive and motor (see wiring installation in section 2-3-4)
  • Page 47 【F1.23】 Number of Tolerance to Drive Fault a. Function: Set the number of tolerance to drive fault conditions when faults are occurred for OC, OE, GF during the certain time period. The drive will display fault message on the operation panel and restart again when the numbers of drive faults are over the designated tolerance value.
  • Page 48 F2 Frequency Parameters 【F2.00】 Primary Speed (Preset Speed 1) 【F2.07】 Preset Speed 8 【F2.16】 Jog Speed a. Setting range: 0.00~400.00Hz b. The settings are listed as below: (I) Set the acceleration / deceleration time of multi-speed (F2.18~ F2.28) (II) Set multi-function input terminals(F5.19~ F5.22) c.
  • Page 49 d. Multi-speed and acceleration/deceleration time ※The above illustration is an example of preset speed 1~8. The acceleration / deceleration time of preset speed 5~8 and jog speed are depend on the setting of primary acceleration / deceleration time. ※When the drive stops, and the jog command is ON, the motor is running at the jog speed –...
  • Page 50 c. The secondary acceleration/deceleration time has the higher control priority, and the command is input by the multi-function input terminals. The illustration is shown as below: d. The prohibition of acceleration/deceleration command are ineffective at the STOP command. 【F2.28】 Set S-curve for Accel/Decel Time Setting the S-curve for the acceleration/deceleration time is to slow the acceleration and deceleration time at start and stop.
  • Page 51 Output voltage High voltgae voltage 500V 250V V/F voltage limit pattern Output frequency Base freq./40 Base freq.(F2.35) 【F2.31】 V/F Pattern Selection a. The settings are listed as below: 0: Linear 1: Energy saving mode (Auto-adjust V/F according to the loads) 2: Square curve 3: 1.7 power curve...
  • Page 52 【F2.33】 Starting Frequency Set the starting frequency of the drive, and the setting range is 0.1~10.0Hz 【F2.34】 Starting Voltage Set the output voltage of starting frequency to give more power to overcome the load inertia. 100V/200V series range: 0.1~50.0V 400V series range: 0.1~100.0V 【F2.35】...
  • Page 53 ※The interrelationships are as follows: (I) Base frequency>V/F frequency 2>V/F frequency 1>Start frequency (II) V/F frequency 2<V/F frequency 1, the V/F frequency (voltage) 2 have no effect (III) When V/F frequency 1 and 2<Starting frequency, the V/F frequency (voltage) 1 and 2 have no effect (IV) No limitation between F2.34, F2.36, F2.38, F2.40 【F2.42】...
  • Page 54 【F2.48】 Frequency Lower Limit Set the ratio of the frequency lower limit (1.00=maximum output frequency), and the setting range is 0.00~1.00 × Output frequency lower limit = Frequency lower limit (F2.48) Maximum output frequency (F2.32)
  • Page 55 F3 Control Parameters 【F3.00】 Holding Frequency The drive accelerates to the holding frequency and then operating in constant speed. The setting range is 0.00~400.00Hz 【F3.01】 Holding Time Interval The operation time of drive running at the holding frequency, and the setting range is 0.0~360.0sec.
  • Page 56 a. The function of the stall prevention during the deceleration is to maintain a constant speed when the deceleration is stalling. b. When connecting a dynamic brake unit, F3.07 function can be disabled according to the operation requirement c. If the DC bus voltage of the drive is higher than the dynamic brake voltage level when drive stops, the operation panel or external keypad will display “Hv”.
  • Page 57 c. Setting range: 0: Disable 1: Enable 【F3.19】 Response Time of AVR Set the response time of AVR. The setting range is 0~255. 【F3.21】 DC Braking Level a. Set the current level of DC braking. b. The setting range is 0~150% of drive rated current. 【F3.22】...
  • Page 58 3: When the power is restored during the ramp to stop interval, the drive is restarted and re-accelerated again. b. The drive cannot be started with generator power restart simultaneously at power off. The drive must be started after the generator restarts. c.
  • Page 59 【F3.37】 The Current Level of Speed Tracing a. When the drive current is greater than the current level of speed tracing (F3.37), the output frequency is tracing downwardly to reach the current level of speed tracing. The setting range is 0~200% of drive rated current. b.
  • Page 60 F4 Protection Parameters 【F4.07】 Motor Overload Protection (OL) a. The motor overload protection is listed as below : 0: Motor overload protection: Disabled 1: Motor overload protection: Enabled (OL) 2: Motor overload protection of motor independent cooling fans: Enabled (OL) b.
  • Page 61 increase when the cooling fans is damage or the heat sink is covered by foreign objects. User can maintain the cooling fans of drive in advance. The setting range is 45~105℃ 【F4.15】 Drive Overheat Dead Band When the drive heat sink temperature is over the pre-alarm level, the drive displays “...
  • Page 62 【F4.19】 Minimum Operation Time of Fan Set the minimum operation time of drive cooling fans activation, and then according to the setting of F4.17 to set the operation method of cooling fan. The setting range is 0.1~25 min. 【F4.25】 System Overload Detection(OLO) a.
  • Page 63 【F4.29】 System Overload Detection Time a. The detection of system overload is shown in the below chart: b. The operation panel displays “OLO”, when the system overload time is over the setting value of system overload detection time (F4.29). c. Setting range: 0.1~300.0sec.
  • Page 64 F5 Multi-function Parameters Pot knob” Selection (Analog Input) 【F5.00】 “ The settings are listed as below: 0: Analog input gain 1: Frequency command 2: Current limit 3: Variable voltage of V/F pattern 【F5.01】 Analog Input AI Selection The settings are listed as below: 0: Analog input gain 1: Frequency command 2: Current limit...
  • Page 65 【F5.02】 AI Input Source Selection a.The settings are listed as below: 0: DC 4~20mA(2-10V) 1: DC 0~20mA(0-10V) b. Al-GND analog input terminal (1) Insert JP1 jumper to V position The range of AI is 0~10V or 2~10V; Range is set by function F5.02 (2) Insert JP1 jumper to I position The range of AI is 0~20 mA or 4~20mA;...
  • Page 66 Example: Analog input gain= 1.00 Max. output frequency= 60.0Hz Max. output frequency= 60.0Hz Analog input gain= 0.05 Analog input gain= -0.05 Example: Inverse control application 【F5.07】 Filter Setting of Analog Frequency Pot knob” or AI is set for frequency command control (F1.01=0): signal filtering “...
  • Page 67 for multi-speed setting) ±5: Multi-speed level 3 command(see the function description of F2.00 ~ F2. 07 for multi-speed setting) ±7: Reset command Setting the reset command to reset the drive fault. ±8: External fault command (EF) Drive in operation: accept the external fault command to trip the drive. Drive stop: Disable...
  • Page 68 ±9: Interruption of output command (bb) Interrupt the output voltage of the drive ±10: Coast to stop command(Fr) Interrupt the drive output voltage immediately ±11: Speed search from the maximum frequency...
  • Page 69 ±12: Speed search from the frequency setting ±13: Holding command(refer to the description of multi- acc/dec time) ±14: UP command Frequency setting stepping increase ±15: DOWN command Frequency setting stepping decrease ±16: Clean UP/DOWN frequency command The frequency command is cleaned to 0.00Hz ±17: UP/DOWN command enter key (1) Setting the UP/DOWN command enter key for multi-function input terminals X1~X4.
  • Page 70 ±19: Primary and secondary frequency command option a contact ; The frequency command = Primary frequency command(F1.01) Set to 19 b contact ; The frequency command = Secondary frequency command(F1.02) a contact ; The frequency command = Secondary frequency command(F1.02) Set to -19 b contact ;...
  • Page 71 ±25: DC braking enable (Stop) (1) When the drive stops and DC braking command is ON, DC braking is active to stop the motor. (2) The setting value of output current must be according to the function setting of F3.21, when the DC braking is active. (3) When the start or jog command is active, DC braking command will be clear, and the motor will run to the setting frequency.
  • Page 72 【F5.25】 Digital Input Response Time a. Setting the input response time of multi-function terminals (X1~X3) .(digital debouncing) b. If the signal length of digital inputs is smaller than the digital input response time, drive software will reject the input signal and do no process to input signal. 【F5.26】...
  • Page 73 ±6: Stall prevention detection Output freq. Time Output current Stall Prevention Level at the Constant Speed F3.04 Time Outupt terminal ±7: Low voltage detection(LE) Power source Low voltage detection signal Output terminal ±8: Braking transistor is active detection(db) Detection when the DC bus voltage of drive is higher than the dynamic brake voltage.
  • Page 74 ±9: Restart after instantaneous power failure detection Enable when F3.30 is set to 1. Restart after instantaneous power failure detection Power source Low voltage detection signal Output freq. Delay time for speed searching F3.38 The V/F pattern of speed searching F3.39 Output voltage normal...
  • Page 75 ±11: Fault detection ±12: Start detection of sequential operation control Detection when sequential operation control starts. ±13: One complete operation sector detection of sequential operation control After one complete operation phase of sequential operation control, Ta/Tc terminals will output the detection signal for 0.1 seconds. ±14: One complete operation cycle detection of sequential operation control After one complete operation cycle of sequential operation control, Ta/Tc terminals will output the detection signal for 0.1 seconds.
  • Page 76 Detection when the counting value is equal to the setting value of F5.37 ±18: Reverse detection Detection when the drive runs at reversed direction. ±19: NTC temperature warning detection (OHt) Detection when the drive temperature sensed by thermal detector(NTC) is higher than the temperature warning level (F4.14).
  • Page 77 U=UP (acceleration) status D=DOWN (deceleration) status H=HOLD (constant speed) status U1=UP status bounded at the upper limit of the frequency U2=UP status bounded at the lower limit of the frequency D1=DOWN status bounded at the lower limit of the frequency D2=DOWN status bounded at the upper limit of the frequency 【F5.35】...
  • Page 78 F5.35=0 F5.36=500 F5.37=400 Counting value display Counting trigger signal (X1) 2 0 m s Counter value 2 100ms Counter value 1 Down counting mode: ※The cycle of triggering signal cannot be less than 20ms(<50Hz) ※The detection signal of multi-function output terminal must remain at least for 100ms.
  • Page 79 F6 Special Parameters 【F6.55】 Communication Address a. When using RS-485 communication interface to monitor the drive, each drive must be assigned with its communication address, and the same address number cannot be assigned to other drives once this address is defined already.
  • Page 80 ※Start command is required to restart the drive after the drive is completely stopped. ※The overtime warning display will automatically disappear after the communication is uplinked and functional again. 【F6.60】 Multi-Function Input Selection The settings are listed as below: 0: Multi-function inputs from multi-function terminals 1: Multi-function inputs from communication control...
  • Page 81: Chapter 6 Communication Description

    Chapter 6 Communication Description 6-1 Modbus Port (RJ-45) Type Function Description Communication Differential input of RS-485 transmission terminal *Note 1 (DX+) Modbus (RS-485) Modbus(RS-485) Communication communication only uses pin1, communication transmission terminal (DX-) 3-8 Reserved Reserved Note 1: The terminal resistor(100Ω) selection is set by DSW1(Default setting: ON) Note 2: When using multiple sets of drive, connect all the DX+, DX-...
  • Page 82 6-2 The Setting of Communication Parameter ●F6.55 Communication Address:00~254(00—Disable) ●F6.56 Baud Rate: 0: 4800bps 1: 9600bps 2: 19200bps ●F6.57 Communication Format: 0: 8,N,2 for RTU 1: 8,E,1 for RTU 2: 8,O,1 for RTU ●F6.58 Communication Overtime (Cot): 0.0: No overtime detection 0.1~100.0sec: The setting of overtime detection ●F6.59 Communication Overtime Disposal:...
  • Page 83 6-4 Message Format Address OP Code Data n … Data 1 Data 0 CRC 0 CRC1 (Drive) Drive Operation Data Message Address Transmitting Message (Data length “n”: depending on Checksum (1 Byte) OP Code) ≧10ms (1 Byte) ●Address: Drive address number for host to control 00H: The host broadcasts messages to all receivers (drives).
  • Page 84 ●Operation Code(OP Code) Description: ※03H (Read multi-registers): Example: Read data from registers 2101H and 2102H of the drive 1 Message Code (Host to Drive) Register Starting Register Numbers to CRC Checksum Address Code Readout This example shows the host to read the drive data from 2 registers of the drive. The host identifies drive 1 by calling the drive address (02H) with the “read”...
  • Page 85 ※08H (Drive detection): Only use when testing the communication OP code – 08H is to detect if the drive is correctly receiving the data from the host. The main purpose of using this OP code is to ensure the host data to be correctly sent to the drive.
  • Page 86 Return Code (Drive to Host) Register Starting Register CRC Checksum Address Numbers to Write Code The host writes 2 data (1011H and 1770H) with total data length 4 byte to 2000H and 2001H registers of drive. The drive receives and writes the data to the registers, and then returns the message to the host.
  • Page 87 The following example of using C language to create a sample program for CRC checksum algorithm Example: C language sample program unsigned char *data; // Message pointer unsigned char length; // Message length unsigned int crc_chk(unsigned char *data,unsigned char length) int i;...
  • Page 88: Communication Troubleshooting

    6-6 Processing Time of Communication Transmission The communication waits for 10ms to start the communication transmission after the drive powers on or the communication function of the drive changes. The drive needs 5ms processing time to return the message to the host after the message are received from the host.
  • Page 89 6-8 Drive Registers and Command Code ● Registers – Write Operation Reg. No. Name Description Drive function setting/monitoring; AGnnH Function setting G: function group; nn: function number (see Note4) Example: F1.20=A114H 00: No use 01: Stop b0~b1 10: Start 11: JOG command b2~b3 Reserved 00: No use 01: Forward command...
  • Page 90 ● Registers – Read Operation Reg. No. Name Description No error Drive over current (OC) Over voltage (OE) Drive overheat (OH) Drive overlo ad (OL1)(OL2) Motor overload (OL) External fault (EF) Short protection (SC) A/D converter error (AdEr) Reserved 0AH Reserved 2100H Drive error code 0BH Reserved...
  • Page 91 Reserved 210EH 210FH Reserved Reserved Reserved 1: X1 terminal operation 1: X2 terminal operation 1: X3 terminal operation 1: X4 terminal operation Reserved Reserved 2300H I/O terminal status 1: Y1 terminal detection Reserved Reserved Reserved 1: Primary speed by analog input 1: Primary speed by operation panel 1: Primary speed by UP/DOWN command 1: Primary speed by communication...
  • Page 92 ote: 1. When the function is enabled, multi-fun ction ommand –Mu lti-speed 1, 2, 3, will be inactive. 2. 0: Analog 1: Primary speed 2~16: Multi-speed 2~16 17: Jog speed 18: UP/DOWN command 19: Frequency command of sequential opera ion control 21: Com nication 3.
  • Page 93 6-9 Programming Examples – Register and Command 6-9-1 Access Drive Function Setting – Write Operation Write a single register to access drive function setting: a. Set fu nction F2.00 (primary speed) = 30 Hz b. Speed setti ng is directly input by function setting c.
  • Page 94 4.Primary Acceleration/Deceleration Time Setting: Set the acceleration/deceleration time = 1.5 seconds (resolution: 0.1 seconds) a. Set F2.18 (Primary accel time) = 1.5 secon Convert F2.18 to hexadecimal value for generat ing register number: 18 (decimal) = 12H Convert 1.5 seconds to hex value : 1.5 x 10 (by resolution) = 15 (decimal) = 000FH b.
  • Page 95 2. Drive Frequency Output Readout: xample: If the drive frequency outputs = 40.65Hz, read the data output m the drive and display 40.05Hz in the host. a. The host sends the below codes to access the drive register to read out the frequency output data (read only one register data) -Drive register: 2103H -Number of register to read: 1 ...
  • Page 96 Chapte r 7 Operation Procedures and Fault Protection 7-1 Operat ion Procedures DANGER 1. Do Not remove wires when the internal indicator of the drive remains ON. CAUTION 1. Check if the shield of wire is broken after wiring is completed to avoid electric leakage or short circuit.
  • Page 97 b. Connect the wires o f single-phase power with R/L1,S/L2 terminals. c. Parameter setting: Please reset above parameters. If the parameters are not modified, the motor and drive could be possibly damaged. F4.08 (Motor Rated Current)= 3.1A (the setting must be based on the motor rated current) F4.28 (Overload Detection Level)=80 (the half of the default setting value 160%) F3.04 (Stall Prevention Level at the Constant Speed)=80...
  • Page 98: Motor Overload

    -2 Fault Protection Display and Troubleshooting A: Description: T e drive has well protection functions to protect drive and motor when fa ults occur. When the fault occ urs, the drive trips by the protection functions and d splay the fault message on operation panel. After the fault is trou bleshooted, reset the drive by pressing “...
  • Page 99 Drive error trip message Display Description Cause Troubleshooting Drive overload ●Motor overload. ●Check the load of ●Operation current ●The voltage setting moto r if overload. exceeds 150% of of V/F pattern is too ●Chec k if the drive’s rated high or to o lo acceleration or current and...
  • Page 100 Driv e error tri p messa Display Description Cause Troubleshooting Under voltage ●Phase failure of Increase the powe during operation input power. capacity by The internal DC bus ●Instantaneous selecting higher voltage is bel ow 70 % power off. capacity drive to of power sour ce for ●Voltage...
  • Page 101 Drive error trip message Display escription Cause Troubleshooting ROM error ●EEPR OM dat ● Please reset all write fault. parameters to ●EEPROM default value and component restart the drive defected. ●Return the drive repair, when the fault cannot be eliminated. Internal memory CPU RAM is Please call...
  • Page 102 Power source The voltage of Check if the voltage under voltage power source is of power source is too low mal. Drive overheat ●The surrounding ● Improve the ●The temperatur temperature is ventilation. e of drive’s heat sink too high. ●C lean the dust on reaches the...
  • Page 103 ●Communic atio ●Check the setting of ho communication receiver a setti different. ●The connec ting Check the wire Err 00: Keypad cable trip b efor wire o f the between the connec ting. keypad is keypad and drive. loosen. ●The keypad j Err 01: Keypad of the drive i cable trip d ing...
  • Page 104: Appendix A Outline Dimension Drawings Overall Dimensions Of Drive

    Appdndix A Outline Dimension Drawings Appendix A Outline Dimension Drawings Overall Dimensions of Drive Unit:mm 1. Removable bracket frame 2. Fixing screws M4 screws...
  • Page 105 交流馬達變頻器 AC MOTOR DRIVE 操 作 手 冊 CA 系列 CA Series...
  • Page 106 序 言 感謝您採用 TPG CA 系列變頻器,在安裝前請詳細閱讀本說明書, 為了能正確的操作與安全使用。 安全注意事項 安裝、配線、運轉保養或故障排除之前,請詳細閱讀本說明書並注意 內容之安全注意事項及「危險」、「注意」二項標示符號或文字。 ※ 專業合格人員:熟悉變頻器之原理、構造、特性、操作程序、安裝, 能遵守安全措施預防危險發生,並詳閱說明書之人員。 表示若不按說明書上之指示去執行工作 , 可能引起 危險 人員傷亡或嚴重的傷害。 表示若不按說明書上之指示去執行工作 , 可能造成 注意 人員的傷害或產品設備的損壞。 ”表示較輕微損傷等級,如果沒有依照注意事項執行工作,也有可能引起嚴 ※雖然“ 重的損壞或傷害。 安裝 注意 1. 需安裝在金屬物體或防火材料上,並避開高溫、潮濕、油氣、棉 絮、金屬粉或腐蝕性氣體之場所。 2. 產品規格如標示為IP00結構保護等級時,安裝後需避免人員碰 觸 , 以免發生觸電危險 ; 另有選配加裝交流電抗器(ACL)也需注意。 3. 變頻器安裝於控制盤內時,需注意盤內溫度不能高於50℃。...
  • Page 107 簡介 特點 1. 多功能特殊鍵(SPEC): 可自行規劃正反轉、寸動、主/副頻…等多機能控制。 2. 支援RS-485通訊控制介面 (Modbus RTU通訊協定)。 3. 共6組異常履歷,可分別記錄異常時4種狀態(異常碼、異常時輸出電 流、異常時DC bus電壓、 異常時輸出頻率)。 4. 可顯示變頻器送電時數與運轉時數。 5. 設定項次群組化分類,方便功能設定及參數管理。 6. 具程序運轉控制及PID控制功能。 7. 可顯示 8 種監看畫面 (其中 3 個另有 12 種監看畫面可選擇)。 8. 具 PTC 馬達過熱保護功能。 9. 輕載時可設定省能源模式。 10. 具自動轉矩提升功能。 11. 具 8 段速度控制。 12.
  • Page 108 1 安裝前注意事項 1 安裝前注意事項 1-1 產品確認 本產品出廠前皆已通過嚴格的品管測試,但考慮產品在運輸過程中可能會因衝 撞、搖晃、震動…等因素,造成產品些微損壞,所以當您收到購買的產品後,請 確認並查驗以下各項,如有查驗後發現任何異常,請立即通知代理商進一步處理。 1-1-1 外觀、銘牌確認 1. 檢查外包裝箱機種型號是否與變頻器機種型號是否相同。 2. 檢視變頻器外觀是否有烤漆脫落、汙損、變形等情形。 3. 查看變頻器上的銘牌內容,是否與您所訂購的產品規格相符。 1-2 標準規格 CA-201A CA-202A 型號 最大適用馬達(W) 額定輸出容量(VA) 額定輸出電流(A) 三相 200~240V 額定輸出電壓(V) 0.1~400Hz 輸出頻率範圍(Hz) 單相, 200~240V , 50 / 60Hz 電源(Ø,V,Hz) 輸入電流(A) 176V~264V 50/60Hz /±5% 容許電壓/頻率變動率...
  • Page 109 1 安裝前注意事項 1-2 共同規格 1-2-1 控制特性及運轉特性 正弦 PWM 方式(V/F 控制),載波頻率:800~15kHz 控制方式 0.1-400.0Hz 頻率控制範圍 操作面板:0.01Hz(0.01~99.99Hz/100.0~400.0Hz) 頻率設定解析度 類比信號:0.06Hz/60Hz 0.01Hz 輸出頻率解析度 變頻器額定輸出電流的 150%、跳脫時間 1 分鐘 過負載容量 啟動/停止制動時間 0~60.0 秒 停止制動頻率 0.1~60Hz 直流制動 控 制動能力 0~150%的額定電流 制 特 約 20% 制動轉矩 性 V/F 曲線(2 個轉折點) V/F 曲線...
  • Page 110 2 安裝與確認 2 安裝與確認 2-1 基本配備 變頻器之運作,需由一些元件組合而成才能產生效用,這些元件稱為基本配備。 其包含如下: 2-1-1 電源:依照變頻器規格選定三相或是單相電源。 2-1-2 無熔絲開關:當電源開啟時,無熔絲開關可忍受突波電流,並且提供變頻 器過負載和過電流保護。 2-1-3 變頻器:馬達的控制主體;不同馬達極數或不同額定電壓之馬達,額定電 流値會有差異,因此選用變頻器時,應以馬達額定電壓及額定電流為依據, 勿只以馬達之馬力數為參考條件(請參考變頻器標準規格)。 2-1-4 馬達:按照實際的需求決定馬達;請注意馬達的額定電流不可大於變頻器 電流。 註:CA變頻器為三相感應馬達專用,無法控制單相馬達。 2-2 環境條件 為了讓變頻器能安全的運作,必須注意安裝環境的情況。 條件如下: 2-2-1 電源﹕依照變頻器規格選定三相或單相電源。(請參考CA標準規格) 2-2-2 位置﹕變頻器運轉時基於散熱考量,機器周圍必須有足夠的通風散熱距 離,所以變頻器周圍最小距離,如下圖所示﹕ 10cm以上 10cm 以 CA-202A 上 TPG Corp. http://www.tpg-tw.com 10cm以上...
  • Page 111 2 安裝與確認 2-2-3 相關配備規格﹕相關配備的選用,必須配合所使用的變頻器規格,過與不 及都可能造成變頻器的損毀或壽命降低。 請勿在變頻器和馬達之間加裝進相電容(RC、LC或其它電容元件),避免任何 工安意外。 2-2-4 環境整潔﹕變頻器安裝的環境需考量通風、清潔、溫溼度。 2-2-5 操作人員﹕需技術有認證過人員才可進行操作和問題排除。...
  • Page 112 2 安裝與確認 2-3 接線圖和端子敘述 2-3-1 接線圖 2-3-2 端子說明 1. 主迴路端子配置 端子種類 端子記號 端子名稱 說明 交流電源 主 電源 L1,L2 單相正弦波 AC200~240V 電源輸入。 輸入端子 回 輸出至 路 馬達 U,V,W 三相輸出接至三相感應馬達。 馬達端子 端 子 接地 接地用端子 第三種接地 100Ω以下 2. 控制迴路端子控制 端子種類 端子記號 端子名稱 說明...
  • Page 113 2 安裝與確認 3. Modbus連接座(RJ-45) 端子種類 端子腳位 端子名稱 說明 Modbus 通訊傳輸端子(DX+) Modbus(RS-485)通訊使用 (RS-485) 1,2 腳位 通訊傳輸端子(DX-) 保留 保留...
  • Page 114 3 操作面板及遠端操作器設定 3-1 操作面板狀態與監看模式 3-1-1 操作面板的操作狀態 操作面板的操作狀態包含異常訊息與三種模式,切換方法如下圖所示: 操作步驟如下表(以出廠設定為例): 操作步驟 顯示 1.開機進入主畫面。 2.按 鍵,進入設定項次選擇模式。 PROG 3.按 FUNC 鍵,進入參數設定模式。 DATA 4.按 FUNC 鍵返回設定項次選擇模式。 DATA 5.按 鍵返回監看模式。 PROG 異常信號顯示: 操作步驟 顯示 變頻器運轉中跳出異常信號。 1.異常排除後,按 鍵清除異常並返回監看模式。...
  • Page 115 3 操作面板及遠端操作器設定 3-1-2 監看模式 在監看模式下共有八個監看畫面可切換,包含一個主畫面與七個輔助畫面, 如下表所示: 監看畫面說明如下表(以出廠設定為例): 畫面 說明 顯示 畫面1 輸出頻率(Hz、CRG:亮) 畫面2 頻率命令(Hz、CRG:亮) 畫面3 輸出電壓(V、CRG:亮) DC bus電壓(V、CRG:亮) 畫面4 畫面5 輸出電流(A、CRG:亮) 畫面6 端子狀態(Hz、V、CRG、RUN:亮) 畫面7 變頻器溫度(V、A、CRG:亮) 畫面8 馬達轉速(Hz、A、CRG:亮) 1. 八個監看畫面的任何一個可設定為主畫面,其他為輔助畫面,在監看模式下按 鍵切換畫面1~畫面8;設定方式由設定項次F1.08選擇。 2. 可選擇比較重要的輔助畫面作主畫面,系統會在操作於輔助畫面下閒置約3分鐘 後,自動切換回主畫面。 3. 畫面6~8由設定項次F1.09~F1.11決定。...
  • Page 116 3 操作面板及遠端操作器設定 3-1-3 多機能端子狀態 畫面6於出廠狀態為多機能端子狀態顯示,七段顯示器上各位置所代表的端子 代號如下圖: 顯示畫面所代表意義如下表: 顯示畫面 端子 狀態說明 多機能輸入端子X1功能動作。 多機能輸入端子X2功能動作。 多機能輸入端子X3功能動作。 多機能輸出Y1端子動作 3-3-4 設定項次選擇模式功能說明 a. 群組編號選擇: 操作步驟 顯示 1.監看模式下按 鍵進入設定項次選擇模式;群組編號閃 爍。 2.按 鍵增加設定群組編號。 ▼ 3.按 鍵減少設定群組編號。 群組編號範圍請參閱「4. 設定項次一覽表」 b. 群組編號/項次編號切換 操作步驟 顯示 1.群組編號閃爍時,按 鍵切換到項次編號。 << 2.項次編號閃爍時,按 鍵切換到群組編號。 <<...
  • Page 117 3 操作面板及遠端操作器設定 c. 項次編號選擇: 操作步驟 顯示 1.選定群組編號後,按 鍵切換到項次編號;項次編號 閃爍。 ▲ 2.按 鍵,項次編號增加。 ▼ 3.按 鍵,項次編號減少 項次編號範圍請參閱「4. 設定項次一覽表」。 備註:淺色字代表閃爍 3-1-5 參數設定模式 設定範圍由該設定項次決定,操作步驟如下表: 操作步驟 顯示 1.設定項次選擇模式;以F2.17 (輸出頻率)為例。 2.於設定項次選擇模式按 鍵,進入參數設定模式。 FUNC DATA 3.按 鍵,移動小數位數;以小數點後一位為例。 << ▲ 4.按 鍵輸出頻率加0.1。 ▼ 5.按 鍵輸出頻率減0.1。 6.按 FUNC 鍵回到設定項次選擇模式。...
  • Page 118 3 操作面板及遠端操作器設定 3-1-6 監看模式下的操作 在監看模式下可更改頻率命令、馬達轉速(RPM)、線速度(MPM)。以更改頻 率命令為範例,說明如下圖所示: 操作步驟如下表: 操作步驟 顯示 1.監看模式;以頻率命令為例。 2.按 鍵,移動頻率命令位數。 << 3.按 鍵,移動頻率命令位數;以改變個位數為例。 << ▲ 4.按 鍵頻率命令加1。 ▼ 5.按 鍵頻率命令減1。 6.設定需要頻率後,五秒內按 FUNC 鍵儲存。 DATA 註:淺色代表閃爍。 ▲ ▼ a. 在監看模式下以 、 鍵來控制頻率的高、低。 b. 設定需求頻率後,於5秒內(即LED數值閃爍狀態下)按下 鍵便可完成儲存動 作;若未儲存,則五秒後回到監看模式,將於3分鐘後自動儲存;若未超過3分鐘 即斷電將自動回復原來設定(請參考設定項次F1.07)。 3-1-7 變頻器啟動、停止 按...
  • Page 119 3 操作面板及遠端操作器設定 3-1-9 儲存、恢復設定值 a. 儲存變頻器設定項次資料: 操作步驟 顯示 1.按 鍵進入設定項次選擇模式。 PROG 2.按 鍵切換至項次編號。 << ▼ 3.按 鍵移動設定項次至F0.20。 4.按 FUNC 鍵進入參數設定模式。 DATA ▲ 5.按 鍵切換設定資料至 “SAv”。 6.按 鍵儲存,約二秒儲存完畢後顯示 “End”。 FUNC DATA 7.顯示 “End” 約一秒後,回到設定項次選擇模式。 8.按 鍵回到監看模式(頻率命令)。 PROG b. 恢復變頻器設定項次資料: 操作步驟 顯示 1.按...
  • Page 120 5 參數設定說明 4 設定項次一覽表 簡易參數群組表(F0.18=0) 完整參數群組表(F0.18=1) 群組 功能 群組 功能 系統參數 系統參數(簡易) 參數密碼 異常履歷 控制設定(簡易) 控制設定 畫面設定(簡易) 畫面設定 SPEC鍵設定 SPEC鍵設定 停止方法 停止方法 載波設定(簡易) 載波設定 變頻器主速度與多段速度 變頻器的主速度與寸動 主速度與多段加減速時間 頻率 主速度加減速時間 頻率參 V/F曲線設定(含轉折點) 參數 V/F曲線設定 數 跳躍頻率 輸出頻率上下限 輸出頻率上下限 緩行頻率與時間 失速防止設定 馬達滑差補償 保護...
  • Page 121 5 參數設定說明 F0 系統參數 設定 名稱 說明 設定範圍 單位 出廠值 備註 項次 0:軟體版本 1:變頻器型號 2:變頻器額定輸出電流 F0.00 變頻器資訊 ─ ─ ─ 3:變頻器運轉時數 4:變頻器送電時數 5:程式檢查碼 0:參數可更改 F0.01 0, 1 ─ 參數鎖定 1:參數不可更改 註 9 F0.02 保留 保留 ─ ─ ─ 註 9 F0.03 保留...
  • Page 122 5 參數設定說明 F1 操作參數 設定 名稱 說明 設定範圍 單位 出廠值 備註 項次 啟動命令 運轉方向 正、反轉指令控制 正、反轉指令控制 正轉指令控制 反轉指令控制 正、反轉指令控制 正轉方向 操作面板設定 啟動控制 反轉方向 F1.00 0~11 ─ 選擇 反轉指令控制 保留 保留 通訊控制 通訊控制 通訊控制 反轉指令控制 正轉指令控制 通訊控制 操作面板設定 通訊控制 0:頻率命令由(F1.03)類比輸入源選擇 1:頻率命令由操作面板設定 2:保留...
  • Page 123 5 參數設定說明 設定 名稱 說明 設定範圍 單位 出廠值 備註 項次 操作面板有 8 種顯示狀態,選擇其中之一作 為主畫面顯示狀態 1:輸出頻率 2:頻率命令 主畫面 3:輸出電壓 F1.08 ─ 顯示選擇 4:DC bus 電壓 5:輸出電流 6:端子狀態 7:散熱片溫度 8:畫面顯示 8 0:端子狀態 1:變頻器溫度 註 9 F1.09 ─ ─ ─ 保留 2:馬達轉速(RPM) 3:線速度(MPM) 4:程序運轉階段...
  • Page 124 5 參數設定說明 設定 名稱 說明 設定範圍 單位 出廠值 備註 項次 0:可反轉 0,1 註 9 F1.20 禁止反轉 ─ 1:不可反轉 F1.21 ─ 載波頻率 設定值越大,運轉噪音越小 (註8) 0:載波不隨負載電流大小調整 過負載降波 0,1 F1.22 ─ 註9 1:載波隨負載電流大小調整 模式 異常保護 1次 F1.23 自動復歸 異常狀況發生時,自動復歸次數 0~16 註9 次數選擇 底色為 設定項次:代表運轉中可設定。...
  • Page 125 5 參數設定說明 F2 頻率參數 設定 名稱 說明 設定範圍 單位 出廠值 備註 項次 50.00 多段指令 多段指令 多段指令 3 (註1) 主速度 F2.00 0.00~400.00 0.01Hz (第一段速) 60.00 (註2) 註 9 F2.01 0.00~400.00 0.01Hz 10.00 第二段速 註 9 F2.02 0.00~400.00 0.01Hz 20.00 第三段速 註 9 F2.03 0.00~400.00 0.01Hz 30.00 第四段速...
  • Page 126 5 參數設定說明 設定 名稱 說明 設定範圍 單位 出廠值 備註 項次 50.0 (註1) 最大輸出 F2.32 0.1~400.0 0.1Hz 變頻器可操作之最大頻率 60.0 頻率 (註2) F2.33 0.1~10.0 0.1Hz 起動頻率 變頻器的起動頻率 註9 0.1~50.0 (註3,4) (註3,4) F2.34 0.1V 起動電壓 對應起動頻率之輸出電壓 0.1~100.0 12.0 (註5) (註5) 50.0 (註1) 基底頻率 V/F曲線最大電壓之對應頻率 F2.35 0.1~400.0 0.1Hz...
  • Page 127 5 參數設定說明 F3 控制參數 設定 名稱 說明 設定範圍 單位 出廠值 備註 項次 註 9 F3.00 0.0~400.0 0.1Hz 緩行頻率 變頻器加速至緩行頻率下作等速運轉 註 9 F3.01 0.0~360.0 0.1sec 緩行時間 變頻器在緩行頻率下等速運轉的時間 30%~200% 加速中 加速狀態下,失速防止處理方式為 之變頻器 註 9 F3.03 等速運轉 (200%:關閉) 失速防止準位 額定電流 30%~200% 等速中 等速狀態下,失速防止處理方式為 之變頻器...
  • Page 128 5 參數設定說明 設定 名稱 說明 設定範圍 單位 出廠值 備註 項次 0~150% 直流制動 註 9 F3.21 之變頻器 直流制動時的電流準位 能力設定 額定電流 直流制動 註 9 F3.22 1~255 依直流制動情形增減反應時間 反應時間 啟動時直流 註 9 加速啟動時,直流制動時間 F3.23 0.0~60.0 0.1sec 制動時間 停止時直流 註 9 F3.24 降速停止時,直流制動時間 0.0~60.0 0.1sec 制動時間...
  • Page 129 5 參數設定說明 設定 名稱 說明 設定範圍 單位 出廠值 備註 項次 斷電降速之 註 9 兩段減速時間切換之頻率設定值 F3.35 0.0~400.0 0.1Hz 切換頻率 0~200% 速度追蹤 當電流大於速度追蹤電流時,輸出 註 9 之變頻器 F3.37 電流準位 頻率開始向下搜尋 額定電流 速度追蹤前之 註 9 F3.38 速度追蹤前之遮斷輸出時間 0.1~60.0 0.1sec 遮斷時間 速度追蹤的 速度追蹤動作中以所設定的V/F 註 9 F3.39 0~100% 百分比電壓輸出...
  • Page 130 5 參數設定說明 F4 保護參數 設定 名稱 說明 設定範圍 單位 出廠值 備註 項次 0:馬達過載保護無效 1:馬達過載保護有效(OL) 馬達 F4.07 ─ 註9 過載保護選擇 2:獨立散熱風扇馬達過載保護有效 (OL) 依各馬 10%~150% 力數之 之變頻器 F4.08 馬達額定電流依馬達實際額定電流設定 0.1A 馬達額定 額定電流 電流 1/3之馬達 0~馬達額定 註 9 F4.09 馬達無載電流依馬達無載下的輸出電流設定 0.1A 額定 電流值 電流值...
  • Page 131 5 參數設定說明 設定 名稱 說明 設定範圍 單位 出廠值 備註 項次 註 9 ─ ─ ─ 保留 保留 F4.19 註 9 ─ ─ ─ 保留 保留 F4.21 註 9 ─ ─ ─ 保留 保留 F4.22 註 9 ─ ─ ─ 保留 保留...
  • Page 132 5 參數設定說明 F5 多機能參數 設定 名稱 說明 設定範圍 單位 出廠值 備註 項次 0:類比輸入增益 1:頻率命令 類比輸入 註 9 F5.00 ─ Pot選擇 2:電流限制 3:V/F獨立調整之V 0:類比輸入增益 1:頻率命令 2:電流限制 類比輸入 註 9 F5.01 ─ AI選擇 3:V/F獨立調整之V 4:PTC溫度 5:PID回授 0:4~20mA (2~10V) AI選擇 0,1 註 9 F5.02 ─...
  • Page 133 5 參數設定說明 設定 名稱 說明 設定範圍 單位 出廠值 備註 項次 0:無作用 ±1:寸動指令 端子X1 ±2:副加,減速指令切換 -28 ~ +28 F5.19 ─ 多機能 ±3:多段指令1 (註7) 輸入設定 ±4:多段指令2 ±5:多段指令3 ±6:- ±7:重置指令 ±8:外部異常指令(EF) 端子X2 -28 ~ +28 ±9:遮斷輸出指令(bb) F5.20 ─ 多機能 (註7) ±10:自由運轉停止指令(Fr) 輸入設定 ±11:由最大頻率作速度尋找 ±12:由頻率命令作速度尋找...
  • Page 134 5 參數設定說明 設定 名稱 說明 設定範圍 單位 出廠值 備註 項次 0:無作用 ±1:運轉中檢出 ±2:等速檢出 ±3:零速中檢出 ±4:頻率偵測 ±5:系統過負載檢出(OLO) ±6:失速防止檢出 ±7:低電壓檢出(LE) ±8:煞車晶體動作檢出(db) ±9:瞬停復電再起動動作中檢出 端子 ±10:異常再起動動作中檢出 Y1(TA/TC) -21~+21 F5.26 ─ ±11:異常信號檢出 (註7) 多機能 ±12:程序運轉檢出 輸出設定 ±13:程序運轉一階段運轉完成檢出 ±14:程序運轉一週期運轉完成檢出 ±15:程序運轉暫停檢出 ±16:計數值到達檢出1 ±17:計數值到達檢出2 ±18:反轉檢出 ±19:變頻器過熱警示檢出(OHt) ±20:風扇運轉檢出 ±21:外接PTC過熱警示檢出(OH1) 0:斷電清除記憶...
  • Page 135 5 參數設定說明 設定 名稱 說明 設定範圍 單位 出廠值 備註 項次 0:上數模式 註 9 0、1 F5.35 計數值模式 ─ 1:下數模式 計數值 註 9 計數值到達設定 1 F5.36 0~9999 到達設定 1 計數值 註 9 計數值到達設定 2 F5.37 0~9999 到達設定 2 註 9 F5.39 等速檢出範圍 等速檢出的頻寬範圍 0.0~10.0 0.1Hz 註...
  • Page 136 5 參數設定說明 F6 特殊參數 設定 名稱 說明 設定範圍 單位 出廠值 備註 項次 副機以此位址來接受及回傳訊息 註 9 F6.55 0~254 ─ 通訊位址 (0,無作用) 0:4800bps 通訊 註 9 F6.56 1:9600bps ─ 傳輸速率 2:19200bps 0:8,N,2 註 9 F6.57 ─ 1:8,E,1 通訊格式 2:8,O,1 副機接受訊息的間隔時間,大於設定 通訊逾時 註 9 F6.58 時間則作通訊逾時檢出...
  • Page 137 5 參數設定說明 5 參數設定說明 F0 系統參數 【F0.00】 變頻器資訊 a. 可顯示變頻器馬力數與軟體版本訊息。 使用者監看此參數是否與驅動器容量相符合。 b. 此說明書必須與軟體編號相同。 不同軟體編號的變頻器,不可以交互做複製的動作,操作面板會顯示Wr_F。 c. 操作面板的LED燈來分別指示各項顯示內容,LED燈顯示各項內容如下: ○ ○ ○ 軟體版本 ● ○ ○ 變頻器型號 ○ ● ○ 變頻器額定輸出電流 ● ● ○ 變頻器運轉時數(小時) ○ ○ ● 變頻器送電時數(小時) ● ○ ● 程式檢查碼 d.
  • Page 138 5 參數設定說明 【F0.18】 設定模式 0:簡易模式時隱藏部份功能 1:完整模式時可設定所有功能項 【F0.20】 變頻器公用參數 a. 設定內容如下: 無效 清除異常履歷 將變頻器恢復成60Hz出廠値 將變頻器恢復成50Hz出廠値 儲存設定值 恢復設定值 參數讀出 (變頻器操作器) 參數寫入 (操作器變頻器) b. 參數設定後請務必以SAv定此項儲存,方便未來參數之還原。...
  • Page 139 5 參數設定說明 F1 操作參數 【F1.00】 啟動控制選擇 a. F1.00 = 0 (1) 多機能輸入端子(X1~X4)選擇正轉指令端子及反轉指令端子。 (2) 啟動命令及運轉方向皆由正轉指令端子或反轉指令端子控制。 (3) 正轉指令端子、反轉指令端子同時短路或開路時,停止運轉。 例:設定值:F5.19=22、F5.20=23 b. F1.00 = 1 (1) 多機能輸入端子(X1~X4)選擇正轉指令端子及反轉指令端子。 (2) 啟動命令由正轉指令端子控制;運轉方向由反轉指令端子控制。 例:設定值:F5.19=22、F5.20=23 c. F1.00 = 2 (1) 多機能輸入端子(X1~X4)選擇正轉指令端子及反轉指令端子。 (2) 啟動命令由操作面板控制;運轉方向由正轉指令端子及反轉指令端子控制。 (3) 正轉指令、反轉指令端子同時短路或開路時,停止運轉。 例:設定值:F5.19=22、F5.20=23...
  • Page 140 5 參數設定說明 d. F1.00 = 3 (1) 啟動命令由操作面板控制;運轉方向固定正轉。 (2) 正轉指令、反轉指令端子無作用。 e. F1.00 = 4 (1) 啟動命令由操作面板控制;運轉方向固定反轉。 (2) 正轉指令、反轉指令端子無作用。 f. F1.00 = 5 (1) 多機能輸入端子(X1~X4)選擇反轉指令端子。 (2) 啟動命令由操作面板控制;運轉方向由反轉指令端子控制。 例:設定值:F5.19=23 g. F1.00 = 6~7 保留 h. F1.00 = 8 (1) 啟動命令及運轉方向皆由通訊控制。 (2) 正轉指令、反轉指令端子無作用。 i.
  • Page 141 5 參數設定說明 ※ 當F1.00 = 0或2時 若正轉指令端子和反轉指令端子同時開路時,監看模式的頻率畫面會顯示‘----’與 監看畫面值交替閃爍。 若正轉指令端子和反轉指令端子同時短路時,監看模式的頻率畫面會顯示‘ dtF’閃 爍。 ※ 運轉方向為反轉時,輸出頻率顯示 “-”,反轉指示燈亮起。 【F1.01】 主頻率命令選擇 a. F1.01 = 0 頻率由類比輸入端子控制(由F1.03選擇Pot、AI類比輸入源)。 (1) Pot: 頻率範圍的增益比及偏壓比可參照F5.03、F5.04的設定。 (2) AI-GND: 頻率範圍的增益比及偏壓比可參照F5.05、F5.06的設定。 由JP1選擇輸入模式 JP1I模式: 輸入電流源範圍4~20mA或0~20mA (由F5.02選擇)。 JP1V模式: 輸入電壓源範圍2~10V或0~10V (由F5.02選擇)。 b. F1.01 = 1 由操作面板設定頻率命令,在操作面板上,由項次F2.00設定頻率,亦可在監看模 ▲ ▼ 式以...
  • Page 142 5 參數設定說明 【F1.02】 副頻率命令選擇 可由F5.19~F5.22設定為±19,利用多機能輸入端子切換主/副頻率命令。 設定內容如下:(參考第F1.01設定說明) 0:類比輸入設定 1:操作面板設定 2:UP/DOWN設定 【F1.03】 類比輸入源選擇 設定內容如下:(參考第F5.00~F5.01設定說明) 0:Pot+AI 1:Pot-AI 2:AI-Pot 3:Pot 或 AI(由多機能輸入端子切換) 4:Pot 5:AI ※ Pot為操作面板旋鈕、AI為類比輸入端子。 【F1.04】 Pot 輸入源選擇 設定內容如下: 0:變頻器操作面板 Pot 設定旋鈕 1:外部遠端操作器(KP-601) Pot 設定旋鈕 b. STOP鍵使用方法 (1) STOP鍵當緊急停止使用: 當變頻器啟動與運轉方向由輸入端子控制時(F1.00=0、1或10),在變頻器運轉期 間按下STOP鍵,則輸出頻率降至0.00Hz,操作面板顯示 ;重新再 起動的方法是將啟動命令解除,再重新起動。 (2) STOP鍵為一般停止使用:...
  • Page 143 5 參數設定說明 【F1.08】 主畫面顯示選擇 a. 設定內容如下: 1:輸出頻率 2:頻率命令 3:輸出電壓 4:DC bus電壓 5:輸出電流 6:端子狀態 7:變頻器溫度 8:畫面顯示8 (F1.11) b. 可設定以上任何一個為主畫面,其他為輔助畫面。 c. 當在輔助畫面下,不做任何操作時,經過約3分鐘後會自動跳回主畫面。 【F1.11】 輔助畫面 8 設定內容如下: 0:端子狀態 1:變頻器溫度 2:馬達轉速(RPM) 3:線速度(MPM) 4:程序運轉階段 5:程序運轉週期 6:計數值 7:電流限制準位 8:主頻率命令 9:副頻率命令 10:PID 命令 11:PID回授 【F1.13】 線速度設定值 監看模式之線速度顯示 線速度=速度設定值(F1.13) ×...
  • Page 144 5 參數設定說明 【F1.18】 SPEC 鍵自保持功能選擇 SPEC鍵自保持功能選擇: 0:無自保持 1:有自保持 範例:將SPEC鍵作為反轉功能。 ●F1.00 啟動控制設為5 (由操作面板啟動), ●F1.17 設為23(反轉), ●F1.18 設為1 有自保持,則運轉中按下SPEC鍵時,馬達將會反轉。 【F1.19】 停止方法 a. 設定內容如下: 0:減速停止+直流制動(請參考設定項次F3.21~F3.35) 1:自由運轉停止(慣性停止) 2:自由運轉停止+直流制動 b. 當F1.19=2,其停止動作如下圖所示: c. 直流制動時變頻器輸出電流有異常時,請適當調整F3.38時間,使馬達轉子剩磁消 失,再進行直流制動。 【F1.20】 禁止反轉 設定內容如下: 0:可反轉 1:不可反轉...
  • Page 145 5 參數設定說明 【F1.21】 載波頻率 a. 設定內容如下: 設定值 載波頻率 800Hz 2.5kHz 5kHz 7.5kHz 10kHz 12.5kHz 16kHz b. 載波頻率設定值超過4時,應降額使用。 c. 載波頻率設定值越高,噪音越小,但是必須考量變頻器與馬達之間的連線距離做適 當調整。(可參考章節2-3-4配線注意事項之關係表) d. 隨著負載變化,載波頻率將自行調變。(如下圖所示) e. 載波頻率設定值愈低,雜訊干擾愈低。 載波頻率 負載電流 變頻器負載電流 載波頻率 16kHz 100% 12.5kHz 10kHz 7.5kHz 時間 1min 1min 1min 1min 1min 1min 【F1.22】...
  • Page 146 5 參數設定說明 過負載降載 0  1  波模式 (F1.22) OL1 曲線 跳脫時間 (min) 1min 3sec 輸出電流 100 150 180 (150%額定 1min) (150%額定 1min) (180%額定 30sec) (180%額定 3sec) 載波限制 無 曲線 1 *輸出載波頻率依減額曲線表自動調降 載波限制 曲線 2   【F1.23】 異常保護自動復歸次數選擇 a. 功用:針對OC、OE、GF異常重置及再次啟動。 b. 異常再啟動次數設定0時,異常發生後不執行異常再啟動功能。...
  • Page 147 5 參數設定說明 F2 頻率參數 【F2.00】 主速度(第一段速) 【F2.07】 第八段速度 【F2.16】 寸動速度 a. 設定範圍:0.00~400.00Hz b. 相關設定項次 (1)多段加/減速時間(F2.18~ F2.28) (2)多機能輸入設定(F5.19~ F5.22) c. 多段速度的產生 寸動指令 多段指令3 多段指令2 多段指令1 名稱 × × × 寸動速度 主速度 (第一段速) 第二段速 第三段速 第四段速 第五段速 第六段速 第七段速 第八段速 ※ ’× ’:代表無意義(Don’t care)。 ※...
  • Page 148 5 參數設定說明 d. 多段速度與加/減速時間 ※ 上圖以 8 段速度為範例,第五段速以後的多段速度和寸動速度的加/減速時間,是 依照主加/減速時間動作。 ※ 在運轉停止時,若寸動指令 ON,則以寸動速度運轉,無需運轉指令。 ※ 在多段速度下(主速度除外),類比輸入端子(Pot、AI)無作用。 ※ 加/減速時間請參照設定項次(F2.18~ F2.21)。 【F2.17】 加、減速基準頻率 加/減速時間所對應之頻率,設定範圍:0.01~400.00Hz。 【F2.18/F2.19】 主加速時間/主減速時間 【F2.20~F2.25】 二~四段加速時間/二~四段減速時間 【F2.26/F2.27】 副加速時間/副減速時間 a. 多段加/減速時間就是從0到達加/減速基準頻率(F2.17)所需的時間,多段指令可同 時控制多段速度與多段加/減速時間,設定範圍:0.0~3200.0秒。 b. 主速度、第五段速~第十六段速和寸動速度同樣以主加/減速時間為其加/減速時間。 c. 副加/減速時間有優先權,副加/減速指令由多機能輸出端子選擇。...
  • Page 149 5 參數設定說明 說明如下: d. 停止指令作用下,加/減速禁止指令無效。 【F2.28】 S字加/減速時間 S字加/減速選擇的主要功能是緩和加/減速時的衝擊。例如:防止輸送線上的物品掉落 或緩和電梯升降衝擊。...
  • Page 150 5 參數設定說明 【F2.31】 V/F曲線選擇 a. 設定內容如下: 0:直線 1:省能源裝置,依負載輕重自動作V/F調整 2:2次方曲線 3:1.7次方曲線 4:1.5次方曲線 b. F2.31=1時,當負載電流小時,自動調整變頻器輸出電壓,可以達到節能的效果。 c. F2.31=2~4時,使用於風扇、幫浦達成省電目的。 【F2.32】 最大輸出頻率 變頻器可操作之最大頻率,設定範圍:0.1~400.0Hz。 【F2.33】 起動頻率 變頻器的起動頻率,設定範圍:0.1~10.0Hz。 【F2.34】 起動電壓 起動頻率之輸出電壓 100V/200V級規格範圍:0.1~50.0V 400V級規格範圍:0.1~100.0V 【F2.35】 基底頻率 馬達基底頻率;依馬達銘牌上標示的頻率設定,設定範圍:0.1~400.0Hz。 【F2.36】 基底電壓 馬達基底電壓;依馬達銘牌上標示的電壓設定。 100V/200V級規格範圍:0.1~255.0V 400V級規格範圍:0.1~510.0V 【F2.37】 第一轉折點頻率 V/F曲線第一轉折點頻率,設定範圍:0.0~399.9Hz。...
  • Page 151 5 參數設定說明 【F2.38】 第一轉折點電壓 V/F曲線第一轉折點電壓。 100V/200V級規格範圍:0.0~255.0V 400V級規格範圍:0.0~510.0V 【F2.39】 第二轉折點頻率 第二轉折點頻率(參考第F2.37設定說明) 【F2.40】 第二轉折點電壓 第二轉折點電壓(參考第F2.38設定說明) ※ 相對關係如下: (1) 基底頻率>第二轉折點頻率>第一轉折點頻率>起動頻率。 (2) 第二轉折點頻率<第一轉折點頻率時,第二轉折點無作用。 (3) 第一、二轉折點頻率<起動頻率時,第一、二轉折點無作用。 (4) F2.34、F2.36、F2.38、F2.40互不限制。 【F2.42】 跳躍頻率1 【F2.44】 跳躍頻率3 為了防止機械共振產生 , 可利用跳躍頻率方法避開共振頻率 , 設定範圍 : 0.0~400.0Hz 。...
  • Page 152 5 參數設定說明 【F2.45】 跳躍頻率區間 共有三組跳躍頻率、一種跳躍頻率區間,設定範圍:0.0~25.5Hz。 【F2.47】 頻率上限值 輸出頻率的上限值(1.00=最大輸出頻率),設定範圍:0.00~1.00。 頻率輸出上限= 頻率上限值(F2.47) ×最大輸出頻率(F2.32) 【F2.48】 頻率下限值 輸出頻率的下限值(1.00=最大輸出頻率),設定範圍:0.00~1.00。 頻率輸出下限= 頻率下限值(F2.48) ×最大輸出頻率(F2.32)
  • Page 153 5 參數設定說明 F3 控制參數 【F3.00】 緩行頻率 變頻器加速至緩行頻率下作等速運轉,設定範圍:0.0~400.0Hz。 【F3.01】 緩行時間 變頻器在緩行頻率下等速運轉的時間,設定範圍:0.0~360. 0秒。 設定緩行頻率及緩行時間的主要目的是防止馬達滑差現象。馬達滑差發生原因:加速 時馬達轉速跟不上而失速及過電流情況。 【F3.03】 加速中失速防止準位 加速狀態下,失速防止處理方式為等速運轉 (200%:關閉),設定範圍:30%~200% 之變頻器額定電流。 【F3.04】 等速中失速防止準位 等速狀態下,失速防止處理方式為降速運轉 (200%:關閉),設定範圍:30%~200% 之變頻器額定電流。 【F3.05】 等速中失速防止加速時間設定 等速失速防止時,輸出頻率的加速時間,設定範圍:0.1~3200.0秒。 【F3.06】 等速中失速防止減速時間設定 等速失速防止時,輸出頻率的減速時間,設定範圍:0.1~3200.0秒。 【F3.07】 減速中失速防止選擇 0:減速中失速防止機能無作用。 1:減速中失速防止機能有作用。...
  • Page 154 5 參數設定說明 等速中失速防止 加速中失速防止 失速防止減速時間 輸出頻率 輸出頻率 失速防止加速時間 時間 時間 加速中失速防止 等速中失速防止 準位 準位 電流 電流 失速防止檢出 失速防止檢出 時間 時間 a. 選擇有減速中失速防止功能,則減速中失速時,以等速運轉。 b. 連接動態煞車裝置時,可視實際需要關閉減速中失速防止功能(F3.07)。 c. 若變頻器停機時,主迴路DC bus電壓高於動態煞車電壓準位時,操作面板(或遠端 操作器)顯示“ Hv ”。此時按RUN鍵無法啟動變頻器,若DC bus電壓低於動態煞車 電壓準位,則自動恢復正常,回到主畫面。 【F3.09】 馬達滑差補償 a. 因馬達會隨負載大小而產生不同的滑差,因此當負載電流大於滑差補償動作準位 時,變頻器即補償輸出頻率,以達到恆定轉速,設定範圍:-59.9~60.0Hz。 b. 補償頻率 = ...
  • Page 155 5 參數設定說明 【F3.21】 直流制動能力設定 a. 直流制動能力:直流制動時的電流準位。 b. 設定範圍:0~150%之變頻器額定電流。 【F3.22】 直流制動反應時間 依直流制動情形增減反應時間,設定範圍:0~255ms。 【F3.23】 啟動時直流制動時間 啟動時直流制動是防止馬達轉向不明之自由運轉,設定範圍:0.0~60.0秒。 【F3.24】 停止時直流制動時間 a. 停止時直流制動是防止馬達惰走現象。 b. 降速停止時,直流制動時間。設定範圍:0.0~60.0秒。 【F3.25】 停止直流制動頻率 a. 直流制動動作頻率點,設定範圍:0.1~60.0Hz。 b. 在運轉中,如果改變頻率命令至F2.33 (起動頻率)以下時,當輸出頻率降速至啟動 頻率以下,則做直流制動,此時F3.25(停止時直流制動頻率)沒有作用。 輸出頻率 停止時直流制動頻率 F3.25 時間 啟動時直流 停止時直流制動時間 制動時間 F3.24 F3.23 運轉指令 時間 【F3.30】 瞬停復電後再運轉選擇 a.
  • Page 156 5 參數設定說明 100V級規格範圍75.0~96.0V 200V級規格範圍150.0~192.0V 400V級規格範圍300.0~384.0V 【F3.32】 斷電降速之減算頻率 a. 斷電降速時,頻率=輸出頻率-減算頻率。 b. 設定範圍:0.0~20.0Hz。 【F3.33】 斷電降速之減速時間1 輸出頻率大於切換頻率 (F3.35) 的減速時間,設定範圍:0.0~3200.0秒。 【F3.34】 斷電降速之減速時間2 輸出頻率小於切換頻率 (F3.35) 的減速時間,設定範圍:0.0~3200.0秒。 【F3.35】 斷電降速之切換頻率 兩段減速時間 (F3.33和F3.34) 切換之頻率設定值,設定範圍:0.0~400.0Hz。 【F3.37】 速度追蹤電流準位 a. 當電流大於速度追蹤電流時,輸出頻率開始向下搜尋,設定範圍:0~200%之變頻 器額定電流。 b. 速度追蹤的功能,主要是應用在瞬間停電復電後再運轉的速度尋找、異常再啟動 的速度尋找,或由輸入端子下達速度尋找指令時的動作。 c. 可參考多機能輸入端子設定F5.19~F5.22的速度尋找功能。 【F3.38】 速度追蹤前之遮斷時間 速度追蹤前之遮斷輸出時間,設定範圍:0.1~60.0秒。應用範例請參考第88頁之多機 能輸入端子X1~X4設定,±11:由最大頻率作速度尋找及±12:由頻率命令作速度尋 找之圖示說明。...
  • Page 157 5 參數設定說明 F4 保護參數 【F4.07】 馬達過載保護選擇 a. 過載保護選擇的設定內容如下: 0:馬達過載保護無效, 1:馬達過載保護有效(考慮馬達運轉頻率作OL保護)。 2:獨立散熱風扇馬達過載保護有效(不考慮馬達運轉頻率作OL保護)。 b. 防止馬達長期操作於過載狀態而產生損壞,若關閉馬達過載保護,可能使馬達損 壞。 【F4.08】 馬達額定電流 馬達額定電流:依馬達銘牌上標示設定,設定範圍:10~150%變頻器額定電流;設定 單位:安培。 【F4.09】 馬達無載電流 馬達無載電流:約為馬達額定電流之三分之一,可設定範圍:0~馬達額定電流值;設 定單位:安培。 【F4.10】 馬達過載跳脫時間 a. 運轉電流超過馬達額定電流F4.08時,進入反限時曲線OL保護計時階段。 b. 當輸出電流達F4.08馬達額定電流150% 連續運轉F4.10之設定時間,跳OL保護。 c. 馬達過載保護(OL)保護的動作時間,設定範圍:0.5~10.0分鐘。 【F4.12】 變頻器過熱跳脫保護準位 變頻器溫度達跳脫準位,則跳OH保護,設定範圍:85~115℃。 【F4.13】 變頻器過熱警示選擇 a. 設定內容如下: 0:無,關閉過熱警示偵測。 1:過熱警示(OHt),變頻器持續運轉(relay 檢出)。 2:過熱警示(OHt),變頻器將降低載波運轉,每...
  • Page 158 5 參數設定說明 【F4.17】 風扇控制選擇 a. 功能:延長風扇壽命、節省能源消耗、延長散熱片清潔週期。 b .設定內容如下: 0:強制風冷 變頻器送電後,風扇持續運轉不停止。 1:運轉風冷: 當變頻器啟動時風扇才運轉;當變頻器停止時,需等待(F4.19)最小動作時間 後,風扇才停止。 2:溫控風冷: 當變頻器溫度高於(F4.18)風扇動作溫度時,風扇才運轉;當變頻器溫度降至 (F4.15)溫度遲滯區間以下,並再等(F4.19)最小動作時間後,風扇才停止。 【F4.18】 風扇動作溫度 風扇起動的溫度準位,設定範圍:25~60℃。 【F4.19】 風扇最小動作時間 設定風扇強迫運轉最小動作時間後,再依(F4.17)風扇控制選擇設定風扇運轉控制方 式;設定範圍:0.1~25min。...
  • Page 159 5 參數設定說明 【F4.25】 系統過負載檢出設定(OLO) a. 設定內容如下: 0:無過負載檢出。 1:有過負載檢出。 b. 過負載檢出的目的是防止系統受到損壞,所以檢出準位 (F4.28 ) 與檢出時間 (F4.29) 可依照使用者需求設定。 【F4.26】 系統過負載檢出狀態 設定內容如下: 0:頻率等速才檢出。 1:運轉中檢出:變頻器啟動後運轉中檢出。 【F4.27】 系統過負載後輸出設定 設定內容如下: 0:檢出過負載後可繼續運轉。 1:檢出過負載後異常跳脫。 【F4.28】 系統過負載檢出準位 過負載檢出功能之電流準位,設定範圍:30~200%變頻器額定電流。 【F4.29】 系統過負載檢出時間 a. 過負載檢出如下圖 b. 過負載持續發生須超過過負載檢出時間才會檢出,並且操作面板顯示” OLO”。 c. 設定範圍:0.1~300.0秒。...
  • Page 160 5 參數設定說明 F5 多機能參數 【F5.00】 類比輸入Pot選擇 設定內容如下: 0:類比輸入增益 1:頻率命令 2:電流限制 3:V/F獨立調整之V 【F5.01】 類比輸入AI選擇 設定內容如下: 0:類比輸入增益 1:頻率命令 2:電流限制 3:V/F獨立調整之V 4:PTC溫度 5:PID回授 ※ 當F1.01 = 0,頻率命令由類比信號輸入,則F5.00與F5.01至少有一個必須設定為 1,否則頻率命令為0.0Hz。 ※ F5.00與F5.01設定相同(1~3)時,F1.03設定0~2才有作用。 ※ F5.00(F5.01)設為0時,須與F5.00(F5.01)設定為1~3搭配使用,作為增益調整。...
  • Page 161 5 參數設定說明 【F5.03】 類比輸入Pot增益比 類比輸入Pot增益比調整,設定範圍:0.00~2.00。 【F5.04】 類比輸入Pot偏壓比 類比輸入Pot偏壓比調整,設定範圍:-1.00~1.00。 【F5.05】 類比輸入AI增益比 類比輸入AI增益比調整,設定範圍:0.00~2.00。 【F5.06】 類比輸入AI偏壓比 類比輸入AI偏壓比調整,設定範圍:-1.00~1.00。 a. 類比輸入為 Pot (面板設定旋鈕) AI (類比輸入端子):4~20mA(2~10V)或0~20mA(0~10V) b. 最大頻率命令值=最大輸出頻率(F2.32) × 類比輸入增益比(F5.03或F5.05) c. 偏壓比對應的頻率(C.V)= 最大輸出頻率(F2.32) × 類比輸入偏壓比(F5.04或F5.06) d. 頻率命令: C.V) 最大頻率命令    頻率命令 類比命令 20mA) 或 ...
  • Page 162 5 參數設定說明 例如:假設類比輸入增益比=1.00 最大輸出頻率60.0Hz 最大輸出頻率60.0Hz 類比輸入偏壓比=0.05 類比輸入偏壓比=-0.05 例如:逆向控制應用範例 最大輸出頻率 頻率 60.0Hz 命令 類比輸入增益比 =0.00 60.0Hz 類比輸入偏壓比 =1.00 類比指令 0V(4mA) 10V(20mA) 【F5.07】 類比頻率濾波設定 a. 當Pot或AI設定為頻率命令控制時(F1.01=0),作信號濾波。 b. 設定值越大,反應越慢,當設定值為0時則無濾波,設定範圍:0~255。...
  • Page 163 5 參數設定說明 【F5.19】 端子X1多機能輸入設定 【F5.21】 端子X3多機能輸入設定 a. ' + '代表a接點(常開接點) ' - '代表b接點(常閉接點) b. 多機能端子X1 ~X3可設定為以下功能之任一種: ±1:寸動指令(參考多段速度 F2.16 說明) ±2:副加,減速指令切換(參考多段加/減速時間 F2.26 和 F2.27 說明) ±3:多段指令1(參考多段速度 F2.00 ~ F2.07 說明) ±4:多段指令2(參考多段速度 F2.00 ~ F2. 07 說明) ±5:多段指令3(參考多段速度 F2.00 ~ F2. 07 說明) ±7:重置指令...
  • Page 164 5 參數設定說明 ±11:由最大頻率作速度尋找 外部運轉指令 速度尋找指令 >0.1Sec 減速時間為2sec 最大輸出頻率 正常加速時間 輸出頻率 速度追蹤時間F3.38 恢復正常的V/F 輸出電壓 速度追蹤的V/F F3.39 追蹤電流準位 速度追蹤電流準位F3.37 輸出電流 ±12:由頻率命令作速度尋找 ±13:加/減速禁止指令(參考多段加/減速時間) ±14:UP指令 頻率命令遞增 ±15:DOWN指令 頻率命令遞減 ±16:UP/DOWN頻率命令清除 頻率命令被清除為0.00Hz ±17:UP/DOWN 頻率命令確認 (1) 若多機能輸入端子 X1~X4 選擇此功能時,則 UP/DOWN 頻率命令經確認 後,才會生效。 多機能端子開路:UP/DOWN 指令調整頻率命令值,輸出頻率不隨頻率 命令改變。 多機能端子短路:輸出頻率開始加/減速至頻率命令值。 (2) 若多機能輸入端子 X1~X4 不選擇此功能,則只要 UP/DOWN 指令動作, UP/DOWN 頻率命令立即生效。...
  • Page 165 5 參數設定說明 ±18:選擇類比輸入源(Pot/AI) 項次 F1.03 類比輸入源選擇=3( Pot 或 AI) 時 a接點時,選擇類比輸入源為Pot端子輸入。 設定18時 b接點時,選擇類比輸入源為AI端子輸入。 a接點時,選擇類比輸入源為AI端子輸入。 設定-18時 b接點時,選擇類比輸入源為Pot端子輸入。 ±19:主副頻率命令選擇 a接點時,頻率命令為主頻率命令。(F1.01) 設定19時 b接點時,頻率命令為副頻率命令。(F1.02) a接點時,頻率命令為副頻率命令。(F1.02) 設定-19時 b接點時,頻率命令為主頻率命令。(F1.01) ±20:程序運轉起動指令輸入 當 F6.00 項次設定值不為零(使用程序運轉),程序運轉起動指令 ON 時,變 頻器的輸出頻率依程序運轉項次的設定自動運轉 。 若程序運轉起動指令 OFF 時,則程序運轉終止。 ±21:程序運轉暫停指令輸入 運轉中可利用程序運轉暫停指令暫時中斷運轉的程序,待暫停指令取消後, 接續運轉程序繼續運轉。 ±22:正轉 使用方式,請參考 F1.00 項次說明。 ±23:反轉...
  • Page 166 5 參數設定說明 ±25:直流制動允許(停止時) (1) 變頻器靜止時,當直流制動允許命令 ON 時,直流制動形成。 (2) 直流制動動作時,輸出電流依照 F3.21 設定值。 (3) 假設運轉命令或者寸動命令成立時,直流制動會被清除,馬達開始運轉 至頻率命令。 (4) 若運轉命令或者寸動命令消失,輸出頻率降至停止時直流制動頻率點 (F3.25),則直流制動形成。 ±26:計數輸入 (1) 多機能輸入端子,可利用外部觸發信號使變頻器計數。 (2) 選用 4V 以上,13V 以下的輸入界面信號。 (3) 觸發信號:如近接開關、光電檢知器的信號。 ±27:計數清除 清除計數器的值 ±28:電流限制允許 (1) 多機能11輸入動作且F5.00、F5.01其中一項設為2。 a. 電流限制允許。 b. 監看模式下監看(範圍為1~150)。 (2) 多機能輸入未動作 a. 電流限制允許無作用。 b.
  • Page 167 5 參數設定說明 c. Y1輸出端子可設定為以下功能之任一種: ±1:運轉中檢出 變頻器運轉命令下即檢出。 ±2:等速檢出 等速運轉時即檢出。 ±3:零速中檢出 變頻器無輸出時檢出,DC 制動時不檢出。 ±4:頻率偵測 ±5:系統過負載檢出(OLO)
  • Page 168 5 參數設定說明 ±6:失速防止檢出 ±7:低電壓檢出(LE) ±8:煞車晶體動作檢出(db) 變頻器DC bus電壓大於動態煞車電壓準位時檢出。...
  • Page 169 5 參數設定說明 ±9:瞬停復電再起動動作中檢出 F3.30設定為1時,才有動作。 瞬停復電再啟動動作中檢出功能 電源電壓 低電壓檢測信號 輸出頻率 速度追蹤 時間F3.38 速度追蹤的 V/F F3.39 輸出電壓 正常的 速度追蹤電流準位 F3.37 輸出電流 Y1輸出端子 ±10:異常再啟動動作中檢出 異常再啟動動作中檢出功能 異常狀態 速度追蹤時間 F3.38 輸出頻率 速度追蹤的V/F F3.39 輸出電壓 正常的 速度追蹤電流 準位F3.37 輸出電流 Y1輸出端子...
  • Page 170 5 參數設定說明 ±11:異常信號檢出 ±12:程序運轉檢出 執行程序運轉時檢出。 ±13:程序運轉一階段運轉完成檢出 程序運轉,每完成一個運轉程序,Y1(TA/TC)輸出端子檢出,輸出信號維持0.1 秒。 ±14:程序運轉一週期運轉完成檢出 程序運轉,所有運轉程序皆完成,Y1(TA/TC)輸出端子檢出,輸出信號維持0.1 秒。 ±15:程序運轉暫停檢出 程序運轉中,程序運轉暫停指令動作時檢出。 ±16:計數值到達檢出1 計數值等於F5.36設定時檢出1 ±17:計數值到達檢出2 計數值等於F5.37設定時檢出2 ±18:反轉檢出 變頻器運轉為反轉時,則Y1(TA/TC)輸出端子檢出。 ±19:變頻器過熱警示檢出(OHt) 當溫度檢知器(NTC)檢知變頻器溫度高於(F4.14)警示準位時,則Y1(TA/TC) 輸出端子檢出。 ±20:風扇運轉檢出 ±21:外接PTC溫度警示檢出(OH1) 當外接PTC檢知器檢知溫度高於(F4.21)警示準位時,則Y1(TA/TC)輸出端子 檢出。 【F5.30】 UP/DOWN控制記憶選擇 0:斷電清除記憶:斷電會將頻率命令清除為 0.00Hz。 1:斷電記憶:復電後頻率命令為斷電前所記憶的值,記憶在 F5.30。...
  • Page 171 5 參數設定說明 【F5.31】 UP/DOWN微調頻率 UP/DOWN 指令每次動作,頻率命令改變值之間距 設定值 單位 頻率命令改變值之間距 0: 0.01Hz 0.01Hz 1~8: ×0.05Hz 設定8表示頻率命令改變值(8×0.05Hz=0.4Hz) 9: 0.5Hz 0.5Hz 10~250: ×0.1Hz 設定250表示頻率命令改變值(250×0.1Hz=25Hz) 【F5.32】 UP/DOWN微調時間 1~5:端子微調反應時間(超過設定值即連續加/減速 單位:秒): 端子UP/DOWN設定ON/OFF超過設定時間時,連續加(減)速到最大(零速 度)輸出頻率-ON代表加速設定和OFF代表減速設定。 6:邊緣觸發: 不受微調反應時間控制,以輸入信號做邊緣觸發動作,信號反應時間為30ms。 【F5.33】 UP/DOWN頻率命令調整 直接以KEYPAD調整頻率,為頻率命令設定值;UP/DOWN指令改變頻率命令值, 數值改變後5秒回存至F5.33項次。 UP/DOWN指令時序圖: U=UP (加速)狀態 D=DOWN (減速)狀態 H=HOLD (等速)狀態 U1=UP狀態,被限制在頻率上限值...
  • Page 172 5 參數設定說明 【F5.35】 計數值模式 設定內容如下: 0:上數模式 1:下數模式 【F5.36】 計數值到達設定 1 計數值到達設定 1:0~9999 次。(計數值到達檢出 1 請參考 F5.26) 【F5.37】 計數值到達設定 2 計數值到達設定 2:0~9999 次。(計數值到達檢出 2 請參考 F5.26) 上數模式: 下數模式: F5.35=1 F5.36=1000 F5.37=2000 計數器顯示值 9999 2001 2000 1999 1001 1000 9999 計數觸發信號 (X1) 2 0 m s 計數值到達檢出2 100ms...
  • Page 173 5 參數設定說明 F6 特殊參數 【F6.55】 通訊位址 a. 使用RS-485介面來監控變頻器時,每一台變頻器必須設定通訊位址;且通訊位址 不可重複;設定範圍:0~254,最多可串聯31部。 b. 00—無作用,不作通訊溝通。 【F6.56】 通訊傳輸速率 設定通訊的傳輸速率(bps:位元/秒);請選擇與上層機器相同的速率。 0:4800bps 1:9600bps 2:19200bps 【F6.57】 通訊格式 a. 串列通訊為非同步串列傳輸,1 frame = 11 位元;格式共分三種:[8,N,2 for RTU]: 1 start 位元,8 data 位元,2 stop 位元。 [8,E,1 for RTU]:1 start 位元,8 data 位元,1 偶同位,1 stop 位元。 [8,O,1 for RTU]:1 start 位元,8 data 位元,1 奇同位,1 stop 位元。...
  • Page 174 6 通訊說明 6 通訊說明 6-1 Modbus通訊埠 (RJ-45)接線說明 端子 端子種類 端子名稱 說明 腳位 RS-485 差動輸入 通訊傳輸端子(DX+) (註 1) Modbus(RS-485) Modbus(RS-485)通訊僅使用 通訊 通訊傳輸端子(DX-) 1,2 腳位 3-8 保留 保留 註 1:終端電阻 100Ω 選擇由 DSW1 切換 (出廠值:ON) 註 2:當多台使用時必須將各台 DX+、DX-相同端子併接起來,並將隔離網覆線接至 FG。 註 3:終端電阻開關之功用為終止電氣信號,以免產生反射信號而干擾正常信號傳遞,多台使用時 需將第一台和最後一台 DSW1 (終端電阻開關) 必須切至上方(ON),其餘各台 DSW1 皆切至 下方,出廠設定為...
  • Page 175 6 通訊說明 6-2 通訊參數設定 ●F6.55 通訊位址:00~254 (00—通訊功能關閉) ●F6.56 通訊傳輸速率: 0:4800bps 1:9600bps 2:19200bps ●F6.57 通訊格式: 0:8,N,2 for RTU 1:8,E,1 for RTU 2:8,O,1 for RTU ●F6.58 通訊逾時設定: 0.0:無逾時檢出 0.1~100.0sec:逾時檢出時間設定 ●F6.59 通訊逾時處理: 0:警告並繼續運轉 1:警告並減速停止 2:警告並自由運轉停止 ●F6.60 多機能輸入控制選擇: 0:多機能輸入由多機能端子控制 1:多機能輸入由通訊控制 6-3 通訊格式 串列通訊為非同步串列傳輸,1 frame = 11 位元;格式分為以下三種型式: ●8,N,2:1 start 位元,8 data 位元,2 stop 位元...
  • Page 176 6 通訊說明 6-4 訊息格式 資料 n 資料 1 資料 0 CRC 0 CRC1 … 位址 功能碼 訊息資料 無傳輸時間 通訊位址 訊息指令 CRC 檢查碼 (資料長度 “n”:視功能碼而定) (1 byte) (1 Byte) ≧10ms ●位址: 00H—主機對所有副機作廣播,副機接受指令後並不作回傳。 01H~FEH—主機對所指定的副機下指令。 ●功能碼: 03H—讀取多個暫存器。 06H—寫入單一暫存器。 08H—副機偵測。 10H—寫入多個暫存器。 ●資料:包含啟始暫存器,暫存器個數,資料長度(最大 8 筆),資料內容(最大 16 位元 組)。註:資料長度—1 byte,其他—1 word (2 bytes)。...
  • Page 177 6 通訊說明 ●功能碼說明: ※03H (讀取多個暫存器): 命令訊息 CRC 檢查碼 通訊 啟始暫存器 暫存器個數 功能碼 位址 高位元 低位元 高位元 低位元 低位元 高位元 此範例是主機讀取 02 副機的 2 個暫存器資料:從(2101H-啟始暫存器)起至(2102H-暫 存器個數)為止共 2 個暫存器。 回傳訊息 2101H 資料 2102H 資料 CRC 檢查碼 資料 通訊 功能 個數 高位 低位 高位...
  • Page 178 6 通訊說明 ※08H (副機偵測): 僅可以在通訊測試時使用 命令訊息 資料 1 資料 2 CRC 檢查碼 通訊 功能碼 位址 高位元 低位元 高位元 低位元 低位元 高位元 此範例是主機用 08H 功能碼診斷偵測 02 副機資料:0000H 和 AA55H。 回傳訊息 資料 1 資料 2 CRC 檢查碼 通訊 功能碼 位址 高位元 低位元 高位元...
  • Page 179 6 通訊說明 6-5 CRC 檢查碼運算方法 下列為產生 CRC 檢查碼的運算流程圖: 以下例子是說明如何產生 CRC 檢查碼。 範例:透過通訊位址 02H 和功能碼 03H,用 CRC-16 運算法產生 CRC 檢查碼 D140。 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 First Code 02H 0 0 0 0 0 0 1 0 1 1 1 1 1 1 1 1 1 1 1 1...
  • Page 180 6 通訊說明 以下為使用 C 語言所寫的 CRC 檢查碼範例程式: unsigned char *data; //通訊訊息指標 unsigned char length; //通訊訊息長度 unsigned int crc_chk(unsigned char *data,unsigned char length) int i; unsigned int reg_crc=0xffff; while(length--) reg_crc^=*data++; for(i=0;i<8;i++) if(reg_crc&0x01) reg_crc=(reg_crc>>1)^0xa001; else reg_crc=reg_crc>>1; 6-6傳輸處理時間 當變頻器開機,或改變相關通訊設定項次後,經過 10ms 主機方可開始通訊傳輸;將 命令訊息傳送出去後,副機需 5ms 的處理時間才會把回傳訊息傳送回主機。如果是廣 播則不回傳,主機可在...
  • Page 181 6 通訊說明 6-7異常通訊處理 1. 當在通訊網路發生錯誤時,變頻器提供了自我檢測功能,辨認發生錯誤的地方。 請檢查通訊功能設定,解決通訊錯誤。(請參照 6-2:通訊參數設定) 2. 當主機接收到變頻器回傳的錯誤訊息時,代表命令訊息為不合法的。以下為錯誤 訊息的通訊格式 錯誤訊息 CRC 檢查碼 通訊位址 功能碼 錯誤碼 1xxxxxxxB 其中功能碼是將原本命令訊息的功能碼最高位元(bit7)設為 1,錯誤碼則依不同錯誤給 予不同數值;以下為錯誤碼敘述: 錯誤碼 名稱 說明 串列通訊同位元錯誤 串列通訊格式錯誤 串列通訊資料框錯誤 串列通訊位元溢位 Modbus 功能碼錯誤 功能碼不在 03H,06H,08H,10H 其中 Modbus CRC 錯誤 CRC 檢查碼錯誤 1.傳送資料列長度與協定不符 Modbus 資料錯誤 2.寫入暫存器資料超出範圍...
  • Page 182 6 通訊說明 6-8 暫存器和指令說明 ●寫入暫存器 暫存器編號 名稱 說明 設定、監看變頻器設定項次; AGnnH G 表示群組,nn 表示項次 設定項次 【註 4 】 例如:F1.20 由 A114H 表示 00:無作用 01:停止 b0~b1 10:啟動 11:寸動指令 b2~b3 保留 00:無作用 01:正轉指令 b4~b5 10:反轉指令 11:改變轉向指令 00:主加/減速時間 01:一段加/減速時間 b6~b7 10:二段加/減速時間 11:三段加/減速時間 運轉操作命令 1 2000H 000:主速度(通訊) 001:多段速度...
  • Page 183 6 通訊說明 ● 謮出暫存器 暫存器編號 名稱 說明 00H 無異常 01H 過電流 (OC) 02H 過電壓 (OE) 03H 變頻器過熱 (OH) 04H 變頻器過負載 (OL1)(OL2) 05H 馬達過負載 (OL) 06H 外部異常 (EF) 07H 短路保護 (SC) 08H A/D 轉換器故障 (AdEr) 09H 保留 0AH 保留 2100H 變頻器異常碼 0BH 保留...
  • Page 184 6 通訊說明 暫存器編號 名稱 說明 210AH 保留 210BH 保留 210CH 保留 210DH 保留 210EH 保留 210FH 保留 保留 保留 1:X1 動作 1:X2 動作 1:X3 動作 1:X4 動作 保留 保留 2300H 控制端子狀態 1:Y1(TA/TC)檢出 保留 保留 保留 1:主速由類比輸入 1:主速由操作面板設定 1:主速由 UP/DOWN 設定 1:主速由通訊輸入...
  • Page 185 6 通訊說明 註: 1.當有效時,多機能指令—多段指令 1、多段指令 2、多段指令 3,將無動作。 2.頻率命令段速對照表 0:類比 1:主速度 2~16:多段速 2~16 17:寸動速度 18:UP/DOWN 命令 19:程序運轉頻率命令 21:通訊 3.異常履歷對照表 異常編號 變頻器顯示值 內容說明 A/D 轉換器故障 (AdEr) IGBT 模組異常 (Fot) (EEr1) 變頻器內部記憶體故障 (OC) 變頻器過電流保護 (OE) 過電壓保護 (LE1) 運轉中電源電壓過低保護 (GF) 接地漏電保護 (OH) 變頻器過熱保護 (OL) 馬達過負載保護...
  • Page 186 6 通訊說明 6-9 程式範例–暫存器和指令 6-9-1 存取變頻器設定項次–寫入操作 a. 設定設定項次 F2.00 (主速度) = 30 Hz b. 速度 = 30Hz  30.00Hz(最小單位:0.01Hz)  30.00 / 0.01 = 3000 (十進制)=0BB8H(十六進制) 主機寫入副機命令訊息(不含 CRC 檢查碼) 通訊 暫存器位址 暫存器資料 功能碼 位址 高位元 低位元 高位元 低位元 6-9-2 主機控制變頻器–寫入操作 主機利用...
  • Page 187 6 通訊說明 3.速度設定(頻率命令): 設定速度 30.05Hz (最小單位:0.01Hz) a. 變頻器寫入速度設定(頻率命令)位址:2001H b. 轉換 30.05Hz 成十六進制數值: 30.05 / 0.01 (最小單位) = 3005 (十進制) = 0BBDH (十六進制) 通訊 暫存器位址 暫存器資料 功能碼 位址 高位元 低位元 高位元 低位元 4.主加速度/主減速度時間設定: 設定主加速/主減速時間=1.5 秒 (最小單位:0.1 秒) a. 設定 F2.18 (主加速時間) =1.5 秒 轉換...
  • Page 188 6 通訊說明 命令訊息 (主機到變頻器) 通訊 暫存器位址 讀出暫存器個數 功能碼 位址 高位元 低位元 高位元 低位元 b. 當”GF”發生時,變頻器回傳異常訊息到主機: -GF 異常碼: 0EH 回傳訊息 (變頻器到主機) 2100H(暫存器)資料 通訊 功能碼 位元資料 位址 高位元 低位元 2. 讀出變頻器輸出頻率: 範例:假如變頻器輸出頻率=40.65Hz,從主機上讀出變頻器輸出資料 40.65Hz。 a. 主機從暫存器 2103H 位址(輸出頻率)讀出 1 個變頻器暫存器 資料。 -暫存器位址:2103H -讀出暫存器個數:1  0001H 命令訊息...
  • Page 189 7 操作程序與異常保護 7 操作程序與異常保護 7-1 操作程序 危險 1. 變頻器電源指示燈(CRG)未熄滅前,請勿進行拆線工作。 注意 1. 配線完成後應檢查配線是否破損,以免漏電或短路。 2. 端子上之螺絲是否鎖緊。 A. 確定電源、電壓、馬達、變頻器是否匹配。 B. 將電源連接到變頻器R/L1, S/L2, T/L3(三相電源)或是R/L1, S/L2 (單相電源)端子。 C. 送電後設定好所需的參數和功能,並且在U/T1, V/T2, W/T3端子量測變頻器的輸出 電壓,並確認輸出電壓和需求値,完成後按 “ ” 鍵。 D. 關掉電源並且等到變頻器的電源指示燈熄滅 ,然後連接變頻器U/T1, V/T2, W/T3 端 子到馬達。 E. 電源開啟後利用變頻器慢速驅動馬達,確認馬達旋轉方向是否正確後,再慢慢增加 馬達轉速。 F.
  • Page 190 7 操作程序與異常保護  b. 連接單相電源線到R/L1, S/L2端子。 c. 參數設定: 請重新設定以下設定項次。如果沒修改參數設定,馬達和變頻器可能會 損壞。 F4.08:馬達額定電流 =3.1A (依照馬達實際額定電流設定) F4.28:過負載檢出準位=80 (原本出廠值160%應減半) F3.04:等速中失速防止=80 (原本出廠值160%應減半)
  • Page 191 7 操作程序與異常保護 7-2異常保護顯示與處理對策 a 說明: 變頻器有完善的保護功能,在異常發生時保護變頻器和馬達;當異常發生時,變 頻器會跳脫保護並在操作器上顯示異常訊息。異常排除後,可按壓操作器上 “ ” 鍵,或是透過多機能輸入端子從外部下達重置命令。 b 保護內容及處理對策一覽表: 變頻器異常跳脫訊息 顯示 說明 原因 處理對策 IGBT模組異常 ●變頻器驅動電源 當多機能輸入端子 系統異常。 重置指令或按 ●變頻器輸出異常 都無效時,請送廠維 過電流。 修。 ●IGBT模組溫度過 高。 ●檢查馬達是否有絕 接地漏電保護 變頻器輸出端短路 ●變頻器輸出端接地且 或接地。 緣劣化。 ●檢查馬達線是否有 接地電流超過接地漏 電檢知準位以上。 破損。 ●接地漏電檢知準位: F4.01 ●變頻器輸出端短...
  • Page 192 7 操作程序與異常保護 變頻器異常跳脫訊息 顯示 說明 原因 處理對策 ●馬達負載過大。 ●檢查馬達負載是否 變頻器過負載保護 ●運轉電流達變頻器額 ●V/F曲線設定的電 過大。 定電流 150% 1 分鐘。 ●檢查加/減速時間 壓過高或過低。 ●變頻器容量太小。 是否過短。 ●檢查V/F設定是否 適當。 ●加大變頻器容量。 ●負載過重。 ●檢查馬達與變頻器 變頻器電流限制 ●加速時間太短。 運轉電流超過變頻器額 是否匹配。 定電流 200%跳脫條 ●自然停止時再啟 ●檢查馬達是否有超 件。 動。 額運轉。 煞車晶體過載 煞車動作頻率過 增加“減速時間”設 高,造成煞車晶體...
  • Page 193 7 操作程序與異常保護 變頻器異常跳脫訊息 顯示 說明 原因 處理對策 ●環境溫度過高。 ●改善通風系統。 變頻器過熱保護 ●變頻器的散熱片溫度 ●散熱片有異物。 ●清除散熱片積塵。 ●變頻器的冷卻風 ●更換冷卻風扇。 達跳脫準位。 ●跳脫準位:F4.12 扇異常。 ●檢查馬達負載是否 馬達過熱 馬達過熱。 ●馬達內部溫度過高, 過大。 ●檢查加/減速時間 超過跳脫準位 ●跳脫準位:F4.23 是否過短。 ●檢查 V/F 設定是否 適當。 PID 回授信號異常 回授斷線。 檢查回授信號線路 是否正常。 A/D 轉換器故障 --- 請送廠維修。 外部異常...
  • Page 194 7 操作程序與異常保護 變頻器警告訊息 *當變頻器顯示以下訊息,變頻器會停止輸出;異常狀態移除後,變頻器會自動恢復到 正常狀態。 顯示 說明 原因 處理對策 系統過負載保護 --- 確認機械設備的使用。 ●馬達負載系統過 大,運轉電流達動 作條件。 ●動作準位:F4.28 ●動作時間:F4.29 電源電壓過高 電源電壓過高。 檢查輸入電源,是否在 ●停止中變頻器內 變頻器額定輸入範圍 部 DC bus 電壓超 內。 過保護準位。 ●增加“減速時間”設 煞車晶體動作 馬達減速時間過短, ●變頻器內部 DC 造成回升電壓太高。 定。 bus 電壓超過設定 ●使用高轉矩制動方 準位。 式。 ●設定準位:F3.27 ●加裝動態煞車器,降...
  • Page 195 7 操作程序與異常保護 正/反轉運轉指令同 多機能輸入端子操作 檢查正反轉控制端子 時動作 不當。 接線。 變頻器警告訊息 顯示 說明 原因 處理對策 無正/反轉運轉指令 --- 檢查正/反轉控 制端子接線。 與頻率命令 交替顯示 不同程式版本的變頻器執 變頻器版本不同。 檢查變頻器軟 行交互做複製 體版本是否相 同。 Modbus 通訊逾時 ●通訊線鬆脫或接 ●檢查通訊線接 線錯誤。 線是否正確。 ●主/副機通訊設定 ●檢查通訊設定 不同。 是否適當。...
  • Page 196 附錄 I 外型尺寸圖 附錄 A 外型尺寸圖 (1) 變頻器尺寸圖 (2)安裝尺寸開孔圖: 固定方式 1:免螺絲固定器(標準固定) 2:螺絲固定(振動環境使用) ※外型尺寸若有變更,依實物為準。 附錄 I...
  • Page 197 Note Note...
  • Page 198 Note Note...
  • Page 199 Note Note...
  • Page 200 Note Note...