Troubleshooting Guide - Five Seasons SASD10-2 Owner's Manual

Table of Contents

Advertisement

PROBLEM
Unit does not function
System fan is not on.
correctly. Power light
Wiring improperly connected.
and performance indi-
cator light are OFF.
Defective power switch.
Defective safety interlock.
Unit does not function
Short in cells due to:
correctly. Power light is
1. Broken ionizing wire.
ON and performance
2. Large particles wedged between cell plates.
indicator light is OFF.
3. Cells washed recently and are still wet.
4. Cell end plate insulator is dirty or damaged.
5. Cell plate(s) are bent.
Defective performance indicator light.
Defective power board.
Air Proving Switch (APS) sensor is burnt out.
Air Proving Switch is not getting enough air
across the sensor.
Off board 24V transformer is not working.
Defective power switch.
Power light is OFF and
Defective power switch light.
performance indicator
light is ON.
Cell makes loud hissing
Internal cell contacts are not touching plates.
noise or causes radio
Copper contacts on high voltage tray not making
interference.
good connection on cell.
Cells arcing excessively
Cells wet from washing.
(power light and per-
Particles lodged in cell or broken ionizing wire.
formance indicator light
ON or flashing).
Ducts were not cleaned prior to installation of air
cleaner.
Cell plates are bent.
Dirty cells.
Voltage is too high.
High voltage wires are on wrong copper contact. Reposition high voltage wires on proper contact (see Fig. 5).
Internal contact on cell out of alignment.
Humidifier (if installed) is leaking water on air
cleaner.
Cells arcing excessively
Copper contact on high voltage contact board is
at top of cell near cop-
broken or bent upward.
per contacts (power
light and performance
indicator light ON).
Cells not collecting dirt
Arrow on cells not pointing towards fan blower.
(power light and per-
System fan is on "Automatic" setting (air cleaner
formance indicator light
not on continuously).
ON).
Not enough voltage on collecting cells.
Ozone odor
Cell plates are bent.
Loose or broken ionizing wire.
Dirty cells.
Air Cleaner is on when system fan is not run-
ning. Air cleaner wired incorrectly or air proving
switch is defective.
Incoming voltage is higher than 220V.
Air Cleaner is oversized for house. Not enough
airflow to cover surface area of cells.
Home is extremely dry.
White dust
Clean lint dust too heavy to remain airborne.
Gaps around Air Cleaner.
Table 4 — TROUBLESHOOTING GUIDE
PROBABLE CAUSE
Turn system fan on.
Check wiring or if plug is inserted and receptacle is powered.
Check power switch for continuity with ohmmeter. Replace if defective.
Remove door and press safety interlock with a screwdriver. If lights
come on, bend interlock lever towards front and close door.
1. Remove wire or wire fragments. Replace.
2. Shake large particles out or wash cell.
3. Allow cells to dry completely.
4. Clean or replace end plate insulator.
5. Straighten plates with pliers.
Determine whether high voltage is present by testing power board. If
voltage is present, replace indicator light.
Adjust high voltage potentiometer on power board counter-clockwise. If
high voltage is not present, replace power board.
Remove power box lid and blow lightly for 10 seconds on APS sensor
at bottom of power box. If light does not come on, replace APS.
Check that sensor is located in the plastic bushing at the front of the
power box.
Check that the return duct is installed flush to the top and front edge of
the Air Cleaner duct opening.
Ensure there is a minimum of 360 CFM of air to the air cleaner.
Verify output of transformer. Replace if necessary.
Verify output of switch. Replace if necessary.
Replace power switch.
Test contacts and repair.
With needle-nose pliers, gently pull contacts down or replace contacts.
Allow cells to dry completely.
Wash cell. Shake particle out of cell. Replace wire, if necessary.
Clean ducts.
Remove cells and adjust to original spacing using needle-nose pliers.
Wash cells and clean ionizing wires.
Adjust high voltage potentiometer on power board clockwise.
Realign cell contact.
Repair humidifier. If possible, move humidifier to different location.
If possible, pull down contacts with needle-nose pliers or remove power
box and replace contacts.
Reposition cell handle and place cell in properly.
Use "Fan On" system fan setting for continuous fan operation.
Adjust high voltage potentiometer counter-clockwise on power board.
Straighten with needle-nose pliers.
Replace wires.
Wash cells and clean ionizing wires.
Check operation and wiring of air switch and air cleaner.
Adjust high voltage potentiometer clockwise on power board.
Use correct size of Air Cleaner.
Repair or install central humidifier.
Keep fan running continuously. Ensure that return air grilles are not
obstructed.
Seal or use duct tape around Air Cleaner cabinet.
12
REMEDY