Alarm tone and voice annunciation sounder

Advertisement

Quick Links

1)
Introduction
The Appello tone and speech annunciation
sounder has three different styles in AC and DC.
A105NAPPX
Sounder
AL105NAPP Sounder-Beacon Combination
Sounder-Beacon
Combination
available as either a high output LED or
Xenon strobe.
These Sounder units share a common set of
functions:-
4 stages, each stage can record up to 30
seconds of CD quality audio.
Facility to record via an on board microphone
or a line in input.
The recorded message can be played back
proceeded either with or without the choice
of one of forty five tones.
The Beacon functions are either:-
Xenon Strobe - 1Hz flash rate
LED - Either Steady or 2Hz blink rate
2)
Operating and Marking
All
units
have
the
requirements and limitations.
Unit Type No.
Voltage
Range
Sounder only outputs
A105NAPPX DC 24Vdc
10-30Vdc
Max Current 256mA @ 30Vdc
A105NAPPX AC 115Vac 90-260Vac 112mA
230Vac 90-260Vac 124mA
Max Current 127mA @ 260Vac
AL105NAPPX combined unit - Add selected
sounder & beacon currents to calculate total
current required.
Beacon only outputs
LED Beacon DC 24Vdc
10-30Vdc
Max Current 166mA @ 30Vdc
LED Beacon AC 115Vac 90-260Vac 60mA
230Vac 90-260Vac 35mA
Max Current 60mA @ 90Vac
Xenon Beacon DC 12Vdc 10-14Vdc
24Vdc 20-28Vdc
Xenon Beacon AC 115Vac +/-10%Vac 100mA
230Vac +/-10%Vac
Operating Temp: -20 to +55°C
IP Rating:
Type 4 / 4X / 3R / 13 , IP66
ae&t - 4 impasse Joliot Curie - 64110 Jurançon - tél 05 59 06 06 00 - info@aet.fr - aet.fr
units
are
following
operating
Current
256mA
157mA
500mA
250mA
50mA
INSTRUCTION MANUAL
A105NAPPX & AL105NAPPX APPELLO
Alarm Tone and Voice Annunciation Sounder
Marking:
3)
Installation & Wiring Requirements
A105NAPPX
AL105NAPPX

Advertisement

loading
Need help?

Need help?

Do you have a question about the A105NAPPX and is the answer not in the manual?

Questions and answers

Summary of Contents for AE&T A105NAPPX

  • Page 1 Sounder only outputs A105NAPPX DC 24Vdc 10-30Vdc 256mA Max Current 256mA @ 30Vdc A105NAPPX AC 115Vac 90-260Vac 112mA 230Vac 90-260Vac 124mA Max Current 127mA @ 260Vac AL105NAPPX combined unit - Add selected sounder & beacon currents to calculate total current required.
  • Page 2 Always de-energize unit before removing cover. Unit Set-up and Recording The installation of the units must be in The unit will need to be configured to suit the end accordance with any local codes that may apply user. and should only be carried out by a competent If recording either via the onboard microphone or trained electrical engineer.
  • Page 3 DC Units Second, Third and Fourth Stage AC Units Second, Third and Fourth Stage Selection Selection The Appello unit uses –ve switching to change The Appello unit uses Live switching to change the tone to the second, third and fourth stages. the tone to the second, third and fourth stages.
  • Page 4 S2 - Set-up S4 - Tones Power & Alarm Stage Terminal Function L.E.D 's Peak level L.E.D On board microphone Audio Line-in Jumper Alarm Tone & (Voice) Recorded Content Volume Controls 7) Appello Setup Guide The following guide is designed to get the user quickly interfacing with the Appello unit. •...
  • Page 5 Quick ref - Switch ‘S2’ Dip Switch Function Settings Switch OFF Position ON Position Function Function Record Mode Playback Mode Switch 2 On & Switch 3 On = Alarm Stage 1 Stage selection switch Switch 2 Off & Switch 3 On = Alarm Stage 2 Switch 2 On &...
  • Page 6 Quick Ref - Recording Mode (Stage 1 illustrated) For Stage 1: Set Switch ‘S2’ positions 2,3 & 4 to 'ON' Alternatively for : For Stage 2: Set Switch ‘S2’ positions 3 & 4 to 'ON' For Stage 3: Set Switch ‘S2’ positions 2 &...
  • Page 7 Quick Ref - Erase Single stage Mode (Stage 1 illustrated) For Stage 1: Set Switch ‘S2’ positions 2,3 & 7 to 'ON' Alternatively for : For Stage 2: Set Switch ‘S2’ positions 3 & 7 to 'ON' For Stage 3: Set Switch ‘S2’...
  • Page 8 Quick Ref - Mass Erase Mode (Erases All Stages) Set Switch ‘S2’ position 7 to 'ON' Set jumper J4 ‘ME’ to ON position (centre and right pin connected) Switch on power or Press reset button Press action button: Erase will begin - - - - erase complete Reset Jumper J4 ‘ME’...
  • Page 9 Quick Ref - Synchronising Two Sounders (All stages) Connect Synch cable to Master and Slave PCB Set 1 off Units as Master and 1 off Unit as Slave Set jumper J6 to Sync on Set jumper J5 S/M on Master unit to master position (on) Set jumper J5 S/M on Slave unit to slave...
  • Page 10 Table 1: Tone selection table Table 1: Tone selection table Table 1: Tone selection table Table 1: Tone selection table Table 1: Tone selection table Table 1: Tone selection table Switch Switch Stage 2 Stage 2 Stage 3 Stage 4 Stage 1 Stage 1 Frequency Description...

This manual is also suitable for:

Al105nappxAl105napp