Silent Call Communications CO5-MCUS Installation And Operation Manual

Carbon monoxide detector with built in wireless transmitter

Advertisement

Quick Links

C
M
D
ARBON
ONOXIDE
ETECTOR
W
B
W
T
ITH
UILT IN
IRELESS
RANSMITTER
Installation and Operation Manual
Document #
Model # CO5-MC(US)
3126052
108136
418 MH
T
Z
RANSMITTER

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CO5-MCUS and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Silent Call Communications CO5-MCUS

  • Page 1 ARBON ONOXIDE ETECTOR UILT IN IRELESS RANSMITTER Installation and Operation Manual Document # Model # CO5-MC(US) 3126052 108136 418 MH RANSMITTER...
  • Page 2: General Information

    GENERAL INFORMATION: Before installing detectors, please thoroughly read these installation instructions. For detailed information on detector spacing, placement, zoning, wiring, and special applications refer to current edition of the NFPA 72 National Fire Alarm and Signaling Code. NOTICE: These instructions should be left with the owner/user of this equipment.
  • Page 3 WHAT TO DO IF THE CARBON MONOXIDE DETECTOR GOES INTO ALARM: WARNING: Activation of your CO alarm indicates the presence of Car- bon Monoxide (CO) which can KILL YOU. If Alarm sounds: 1. Operate reset/silence button; 2. Call your emergency services (_____________________) (fi re department or 911);...
  • Page 4 and consult the manufacturers’ instructions, or contact the manufacturers directly, for more information about CO safety and this equipment. Make sure that motor vehicles are not, and have not been, operating in an at- tached garage or adjacent to the residence. IMPORTANT INFORMATION FOR THE USER: CAUTION: This alarm will indicate the presence of carbon mon oxide gas at the sensor.
  • Page 5 Carbon Monoxide Gas and its Detection This carbon monoxide detector is designed for indoor use only. Do not expose to rain or moisture. Do not knock or drop the detector. Do not open or tamper with the detector as this could cause malfunction. The detector will not protect against the risk of carbon monoxide poisoning if not properly installed.
  • Page 6 SYMPTOMS OF CO POISIONING: Carbon Monoxide (CO) is an insidious poison. Carbon monoxide bonds to the hemoglobin in the blood and reduces the amount of oxygen being circulated in the body. It is a cumulative poison. Even low levels of CO have been shown to cause brain and other vital organ damage in unborn infants with no effect on the mother.
  • Page 7 SOURCES OF CARBON MONOXIDE: Home appliances used for cooking and heating are the most common household Carbon Monoxide sources. Vehicles running in an attached garage can also produce dangerous levels of CO. Burning any fossil fuel including gasoline, propane, natural gas, oil, and wood can produce Carbon Monoxide.
  • Page 8: General Description

    Extended operation of unvented fuel burning devices (range, oven, fi replace, etc.). Temperature inversions which can trap exhaust gases near the ground. Car idling in an open or closed attached garage, or near a home. GENERAL DESCRIPTION: The CO5-MC(US) is a 3V battery powered Carbon Monoxide (CO) detec- tor with a built in wireless transmitter intended for use with Silent Call 418MHz Medallion Series Silent Buddy Receiver.
  • Page 9 IMPORTANT: The range and proper operation of any wireless device will vary depending on its surroundings. It is very important that each CO5-MC(US) detector is tested with each receiver intended for alarm. Detector Description • LIsted to UL Standard 2034 •...
  • Page 10: Testing The Detector

    During initial power-up, the red and green LEDs will blink together once every 10 seconds four times. It takes about 30 seconds for the detector’s CO sensor to stabilize (see Table 1). After power-up has completed and the detector is functioning normally, the green LED blinks once every 10 seconds.
  • Page 11 Hush feature: If required, the audible alarm can be silenced for fi ve minutes by pushing the Test button. The red alarm light will continue to fl ash in temp-4 pattern. If carbon monoxide is still present after the 5-minute hush period, the audible alarm will sound. The hush feature will not operate at levels above 350 ppm (parts per million) carbon mon- oxide.
  • Page 12: Battery Installation And Replacement

    BATTERY INSTALLATION AND REPLACEMENT: You can purchase a new 3 volt Panasonic CR123A or Duracell DL123A at many different local retail stores or directly from Silent Call Communi- cations by calling 1-800-572-5227, or online at www.silentcall.com. To replace the battery: 1.
  • Page 13 TEST BUTTON GREEN LED RED LED 5800CO-001-V0 Figure 1: CO5-MC(US) Wireless Carbon Monoxide Detector PROGRAMMING: The CO5-MC(US) CO Detector is preprogrammed with a unique address at the Factory. You will need to follow the MINI MR1214-MC program- ming instructions in order to program your CO detector with your receiver.
  • Page 14: Mounting The Detector

    MOUNTING THE DETECTOR: First, determine the best location for the detector, one that provides proper carbon monoxide detection (see Figure 4 for suggested detec- tion locations) and a strong wireless transmission path. Proper Carbon Monoxide Detection Location: On a wall location, the detector should be at least as high as a light switch, and at least six inches from the ceiling.
  • Page 15 • Where dirt or dust could collect and block the sensor • Where it could be knocked, damaged, or inadvertently removed Good Transmission Path: A good transmission path must be established from the proposed mounting location before permanently installing the detector. To check, perform the test described in the testing signal strength section.
  • Page 16 (INSTALLED) FEATURE) NOTE MOUNTING SLOT'S ELBOW. CLOCKWISE TO LOCK 5800CO-006-V0 Figure 2. Mounting the Detector 5800CO-003-V0 Figure 3. Mount Detector Across Ceiling Panel Support...
  • Page 17 DO NOT attach the detector to removable ceiling panels. Attach the detector across panel support as shown in Figure 3. CAUTION: Airborne dust particles can enter the detector. Manufacturer recom- mends the removal of detectors before beginning construction or any other dust producing activity.
  • Page 18 Tamper Protection: The CO5-MC(US) detector includes a tamper-resistant feature that prevents removal from the mounting base without the use of a tool. To engage the tamper-resistant feature, cut the small plastic tab located on the mounting base (Figure 2), and then install the detector. To remove the detector from the base once it has been made tamper resistant, use a small screwdriver to depress the square tamper release tab, located on the skirt of the mounting base, and turn the detector counterclock-...
  • Page 19 REFERENCE TABLE 1 for LED indication Mode defi nitions. Using a 1/8 diameter tool press and release the Test /Hush button. If the Detector is operating properly you will hear 4 quick beeps followed by 5 seconds of silence, followed by 4 more quick beeps. Red Led Blinks once a second between Temporal patterns.
  • Page 20 rotating the detector or moving the detector to another location that provides proper reception. Also be sure that the detector has been programmed and tested to the receiver in use. FUNCTIONAL GAS TEST The CO5-MC(US) has a functional gas test mode which can be used to verify the detector’s ability to sense carbon monoxide gas.
  • Page 21: Maintenance

    MAINTENANCE: It is recommended to Test and visually inspect the CO alarm Once a week. Replace CR123A Battery at least once a year to ensure proper op- eration of all the CO5-MC(US) functions. Make Note of the Replace CO detector by Date. CO detector has a life span of six years max. Occasionally clean the outside casing with a clean dry cloth.
  • Page 22 CO Technology Limitations: The CO5-MC(US) utilizes an electrochemical CO sensing element, and therefore has certain performance limitations. The CO sensing element has a typical life of 6 years from the date of manufacture, and while the product has a timer to create a trouble condition after 6 years of operating, the date code of the product, rather than the timer, should determine when the product is replaced.
  • Page 23 FCC INFORMATION NOTICE: Unauthorized changes or modifi cations could void the user’s authority to operate the equipment. This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device maynot cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation of the device.
  • Page 24 40° to 100°F (4.4° to 37.8°C) Operating Humidity Range: 15% to 95% Relative Humidity, non-condensing Agency Listings: Conforms to ANSI/UL STD 2034 For Warranty Claims/Repairs Please Contact the Manufacturer: Silent Call Communications 5095 Williams Lake Road Waterford, MI 48329 800-572-5227 Please Visit www.Silentcall.com...
  • Page 25 ARBON ONOXIDE ETECTOR UILT IN IRELESS RANSMITTER Installation and Operation Manual Document # Model # CO5-MC 3126052 108123 418 MH RANSMITTER...
  • Page 26 GENERAL INFORMATION: Before installing detectors, please thoroughly read these installation instructions. For detailed information on detector spacing, placement, zoning, wiring, and special applications refer to local building and fi re codes. NOTICE: These instructions should be left with the owner/user of this equipment.
  • Page 27 WHAT TO DO IF THE CARBON MONOXIDE DETECTOR GOES INTO ALARM: WARNING: Activation of your CO alarm indicates the presence of Car- bon Monoxide (CO) which can KILL YOU. If Alarm sounds: 1. Operate reset/silence button; 2. Call your emergency services (_____________________) (fi re department or 911);...
  • Page 28 and consult the manufacturers’ instructions, or contact the manufacturers directly, for more information about CO safety and this equipment. Make sure that motor vehicles are not, and have not been, operating in an at- tached garage or adjacent to the residence. IMPORTANT INFORMATION FOR THE USER: CAUTION: This alarm will indicate the presence of carbon mon oxide gas at the sensor.
  • Page 29 Carbon Monoxide Gas and its Detection This carbon monoxide detector is designed for indoor use only. Do not expose to rain or moisture. Do not knock or drop the detector. Do not open or tamper with the detector as this could cause malfunction. The detector will not protect against the risk of carbon monoxide poisoning if not properly installed.
  • Page 30 SYMPTOMS OF CO POISIONING: Carbon Monoxide (CO) is an insidious poison. Carbon monoxide bonds to the hemoglobin in the blood and reduces the amount of oxygen being circulated in the body. It is a cumulative poison. Even low levels of CO have been shown to cause brain and other vital organ damage in unborn infants with no effect on the mother.
  • Page 31 SOURCES OF CARBON MONOXIDE: Home appliances used for cooking and heating are the most common household Carbon Monoxide sources. Vehicles running in an attached garage can also produce dangerous levels of CO. Burning any fossil fuel including gasoline, propane, natural gas, oil, and wood can produce Carbon Monoxide.
  • Page 32 Extended operation of unvented fuel burning devices (range, oven, fi replace, etc.). Temperature inversions which can trap exhaust gases near the ground. Car idling in an open or closed attached garage, or near a home. GENERAL DESCRIPTION: The CO5-MC is a 3V battery powered Carbon Monoxide (CO) detector with a built in wireless transmitter intended for use with Silent Call 418MHz Medallion Series Silent Buddy Receiver.
  • Page 33 IMPORTANT: The range and proper operation of any wireless device will vary depending on its surroundings. It is very important that each CO5- MC detector is tested with each receiver intended for alarm. Detector Description • Local sounder • Dual LED’s •...
  • Page 34: Testing The Detector

    CO sensor to stabilize (see Table 1). After power-up has completed and the detector is functioning normally, the green LED blinks once every 10 seconds. The LED indication must not be used in place of the tests specifi ed under TESTING THE DETECTOR.
  • Page 35 Table 1: Detector LED Modes Green LED Red LED Sounder Normal Blinks every 10 seconds Off Off (Standby) Alarm/Test Blinks every 1 second Temporal 4 Pa ern† Off Chirp every 45 sec be- Blinks every 45 seconds ginning Low Ba ery Off...
  • Page 36 Hush feature: If required, the audible alarm can be silenced for fi ve minutes by pushing the Test button. The red alarm light will continue to fl ash in temp-4 pattern. If carbon monoxide is still present after the 5-minute hush period, the audible alarm will sound. The hush feature will not operate at levels above 350 ppm (parts per million) carbon mon- oxide.
  • Page 37 BATTERY INSTALLATION AND REPLACEMENT: You can purchase a new 3 volt Panasonic CR123A or Duracell DL123A at many different local retail stores or directly from Silent Call Communi- cations by calling 1-800-572-5227, or online at www.silentcall.com. To replace the battery: 1.
  • Page 38 TEST BUTTON GREEN LED RED LED 5800CO-001-V0 Figure 1: CO5-MC Wireless Carbon Monoxide Detector PROGRAMMING: The CO5-MC CO Detector is preprogrammed with a unique address at the Factory. You will need to follow the Silent Buddy MR1110-MC pro- gramming instructions in order to program your CO detector with your receiver.
  • Page 39 MOUNTING THE DETECTOR: First, determine the best location for the detector, one that provides proper carbon monoxide detection (see Figure 4 for suggested detec- tion locations) and a strong wireless transmission path. Proper Carbon Monoxide Detection Location: On a wall location, the detector should be at least as high as a light switch, and at least six inches from the ceiling.
  • Page 40 • Where dirt or dust could collect and block the sensor • Where it could be knocked, damaged, or inadvertently removed Good Transmission Path: A good transmission path must be established from the proposed mounting location before permanently installing the detector. To check, perform the test described in the testing signal strength section.
  • Page 41 (INSTALLED) FEATURE) NOTE MOUNTING SLOT'S ELBOW. CLOCKWISE TO LOCK 5800CO-006-V0 Figure 2. Mounting the Detector 5800CO-003-V0 Figure 3. Mount Detector Across Ceiling Panel Support...
  • Page 42 DO NOT attach the detector to removable ceiling panels. Attach the detector across panel support as shown in Figure 3 CAUTION: Airborne dust particles can enter the detector. Manufacturer recom- mends the removal of detectors before beginning construction or any other dust producing activity.
  • Page 43 Tamper Protection: The CO5-MC detector includes a tamper-resistant feature that prevents removal from the mounting base without the use of a tool. To engage the tamper-resistant feature, cut the small plastic tab located on the mounting base (Figure 2), and then install the detector. To remove the detector from the base once it has been made tamper resistant, use a small screwdriver to depress the square tamper release tab, located on the skirt of the mounting base, and turn the detector counterclockwise.
  • Page 44 REFERENCE TABLE 1 for LED indication Mode defi nitions. Using a 1/8 diameter tool press and release the Test /Hush button. If the Detector is operating properly you will hear 4 quick beeps followed by 5 seconds of silence, followed by 4 more quick beeps. Red Led Blinks once a second between Temporal patterns.
  • Page 45 rotating the detector or moving the detector to another location that provides proper reception. Also be sure that the detector has been programmed and tested to the receiver in use. FUNCTIONAL GAS TEST The CO5-MC has a functional gas test mode which can be used to verify the detector’s ability to sense carbon monoxide gas.
  • Page 46: Maintenance

    MAINTENANCE: It is recommended to Test and visually inspect the CO alarm Once a week. Replace CR123A Battery at least once a year to ensure proper operation of all the CO5-MC functions. Make Note of the Replace CO detector by Date. CO detector has a life span of six years max. Occasionally clean the outside casing with a clean dry cloth.
  • Page 47 CO Technology Limitations: The CO5-MC utilizes an electrochemical CO sensing element, and there- fore has certain performance limitations. The CO sensing element has a typical life of 6 years from the date of manufacture, and while the prod- uct has a timer to create a trouble condition after 6 years of operating, the date code of the product, rather than the timer, should determine when the product is replaced.
  • Page 48 IC INFORMATION NOTICE: Unauthorized changes or modifi cations could void the user’s authority to operate the equipment. This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation of the device.
  • Page 49 40° to 100°F (4.4° to 37.8°C) Operating Humidity Range: 15% to 95% Relative Humidity, non-condensing Agency Listings: Certifi ed to CSA STD6.19-01 For Warranty Claims/Repairs Please Contact the Manufacturer: Silent Call Communications 5095 Williams Lake Road Waterford, MI 48329 800-572-5227 Please Visit www.Silentcall.com...
  • Page 50 ÉTECTEUR DE MONOXYDE DE CARBONE AVEC TRANSMETTEUR SANS FIL INCORPORÉ Instructions d’installation et d’emploi Document # CO5-MC ODÈLE 3126052 108123 418 MH RANSMETTEUR DE...
  • Page 51: Informations Générales

    INFORMATIONS GÉNÉRALES : Avant l’installation de détecteurs, veuillez lire attentivement ces instructions d’installation. Pour des informations détaillées sur l’espacement des détec- teurs, leur position, leur câblage et leurs applications spéciales, veuillez vous reporter aux codes du bâtiment et de lutte contre l’incendie locaux. REMARQUE: Ce manuel doit demeurer en la possession du propriétaire / de l’utilisateur de l’équipement.
  • Page 52 QUE FAIRE SI L’ALARME DU DÉTECTEUR DE MONOXYDE DE CARBONE EST DÉCLENCHÉE : ADVERTISSEMENT: L’activation de votre alarme de CO indique la présence de monoxyde de carbone qui peut VOUS TUER. Si l’alarme se déclenche: 1. 1) Appuyez sur le bouton de réinitialisation/ silencieux; 2.
  • Page 53 médiat de l’équipement. Prenez note de tout matériel à combustion non inspecté par le technicien, et consultez les instructions du fabricant, ou contactez le fabricant directement, pour en savoir plus sur la sécurité du CO et de cet équipement. Vérifi ez qu’aucun véhicule motorisé n’est ou n’a été...
  • Page 54 Le gaz monoxyde de carbone et sa détection Ce détecteur de monoxyde de carbone est conçu pour une utilisation à l’in- térieur uniquement. Ne l’exposez pas à la pluie ou l’humidité. Ne faites pas tomber et ne heurtez pas le détecteur. N’ouvrez pas le détecteur et ne l’altérez pas car il risquerait de ne pas bien fonctionner.
  • Page 55 SYMPTÔMES D’EMPOISONNEMENT AU CO: Le monoxyde de carbone (CO) est un poison insidieux. Le monoxyde de carbone s’agglomère à l’hémoglobine dans le sang et réduit la quantité d’ox- ygène circulant dans le corps. Il s’agit d’un poison à effet cumulatif. Il a été montré...
  • Page 56 SOURCES DE MONOXYDE DE CARBONE: Les appareils domestiques utilisés pour la cuisson et le chauffage sont les sources les plus courantes de monoxyde de carbone domestique. Les véhicules en marche dans un garage attenant peuvent également produire des niveaux de CO dangereux. La combustion de tout combustible fossile comme l’essence, le propane, le gaz naturel, le pétrole et le bois peut produire du monoxyde de carbone.
  • Page 57: Description Générale

    2. Le fonctionnement prolongé d’appareils à combustion non ventilés (cui- sinière, four, cheminée, etc.). 3. Des inversions de température susceptibles de piéger les gaz d’échappe- ment près du sol. 4. La marche au ralenti d’un moteur de voiture dans un garage attenant ou- vert ou fermé, ou à...
  • Page 58 IMPORTANT: La portée et le bon fonctionnement de tout appareil sans fi l dépendent de son environnement. Il est très important que chaque détecteur CO5-MC soit testé avec chaque récepteur devant servir d’alarme. Description du détecteur • Alarme sonore locale •...
  • Page 59 Lorsqu’il est allumé et que le détecteur fonctionne normalement, le voyant vert DEL clignote une fois toutes les 10 secondes. L’indicateur DEL ne doit pas être utilisé au lieu des tests mentionnés dans la rubrique relative au TEST DU DÉTECTEUR.
  • Page 60 Tableau 1 : Modes du détecteur DEL Voyant DEL vert Voyant DEL rouge Aver sseur sonore Clignote toutes les 10 Normal (a ente) Éteint Éteint secondes Clignote toutes les Alarme/Test Séquence T4 † Éteint secondes Émet un pe t bruit toutes Clignote toutes les 45 les 45 sec à...
  • Page 61 Mode silencieux: Si nécessaire, l’alarme audible peut être mise en mode silen- cieux pendant cinq minutes en appuyant sur le bouton Test. Le voyant rouge d’alarme continuera à clignoter en suivant une séquence T4. S’il reste encore du monoxyde de carbone après le délai de silence de 5 minutes, l’alarme audible retentit.
  • Page 62: Installation Et Remplacement De La Pile

    INSTALLATION ET REMPLACEMENT DE LA PILE: Les piles 3 volts Panasonic CR123A ou DL123A peuvent être achetées dans différents magasins de détail locaux ou directement auprès de Silent Call Communications en appelant le 1-800-572-5227, ou en ligne à www.silentcall. com. Pour remplacer la pile : Retirez le détecteur de son support de montage en le faisant tourner dans le sens contraire des aiguilles d’une montre.
  • Page 63 BOUTON DE TEST VOYANT DEL VERT VOYANT DEL ROUGE 5800CO-001-V0 Figure 1: Détecteur de monoxyde de carbone sans fi l CO5-MC PROGRAMMATION: Le détecteur de CO CO5-MC est préprogrammé à l’aide d’une adresse unique en usine. Vous devrez suivre les instructions de programmation du Silent Buddy MR1110-MC pour programmer votre détecteur de CO en fonction de votre récepteur.
  • Page 64 MONTAGE DU DÉTECTEUR: Tout d’abord, déterminez le meilleur emplacement pour le détecteur, il doit permettre de bien détecter le monoxyde de carbone (voir la Figure 4 pour en savoir plus sur les emplacements suggérés pour la détection) et une bonne transmission du signal sans fi...
  • Page 65 • Dans ou sous un placard • Dans un endroit où la circulation de l’air serait obstruée par des rideaux ou des meubles • Dans un endroit où la poussière ou la saleté peuvent s’accumuler et ob- struer le détecteur •...
  • Page 66 VIS DE MONTAGE (INSTALLÉ) ONGLET ANTI-ALTÉRATION (COUPEZ LE PETIT ONGLET POUR ACTIVER LA FONCTIONNALITÉ ANTI-ALTÉRATION) REMARQUE SERVEZ-VOUS DE L’EMPLACEMENT DES VIS A OU B EN FONCTION DES BESOINS, PUIS FAITES TOURNER LA BASE ET SERREZ LES VIS AU NIVEAU DU COUDE DE CHAQUE FENTE DE MONTAGE ENGAGEZ L’ENCOCHE AVEC L’ONGLET ANTI-ALTÉRATION SUR LE SUPPORT ET TOURNEZ...
  • Page 67 N’ATTACHEZ PAS le détecteur à des panneaux amovibles du plafond. Attachez le détecteur sur le panneau comme le montre la Figure 3 ATTENTION: Les particules de poussière en suspension dans l’atmosphère peuvent entrer dans le détecteur. Le fabricant recommande de retirer les détecteurs avant de commencer des travaux de construction ou toute autre activité...
  • Page 68: Test Du Détecteur

    Protection contre l’altération: Le détecteur CO5-MC est équipé d’une fonctionnalité résistant à l’altération qui empêche son retrait du support d’installation sans l’utilisation d’un outil. Pour installer la fonctionnalité anti-altération, coupez la languette de plastique située sur le support d’installation (Figure 2), et installez le détecteur. Pour retirer le détecteur du support une fois qu’il a été...
  • Page 69 TABLEAU DE RÉFÉRENCE 1 pour les défi nitions des modes d’indication DEL. À l’aide d’un outil de 1/8 de diamètre, appuyez et relâchez le bouton Test /Si- lencieux. Si le détecteur fonctionne correctement, vous entendez 4 bips rapid- es suivis par 5 secondes de silence, suivies par 4 bips plus rapides. Le voyant rouge clignote une fois par seconde entre les séquences.
  • Page 70 meilleure. Vérifi ez également que le détecteur a bien été programmé et testé en fonction du récepteur que l’on utilise. TEST DE GAZ FONCTIONNEL Le CO5-MC est équipé d’un mode de test de gaz fonctionnel qui peut per- mettre de vérifi er la capacité du détecteur à déceler la présence de gaz mon- oxyde de carbone.
  • Page 71 MAINTENANCE: On recommande de tester et d’inspecter visuellement le système d’alarme au CO une fois par semaine. Remplacez la pile CR123A au moins une fois par an pour garantir le bon fonctionnement de toutes les fonctions du CO5-MC. Prenez note de la date de remplacement du détecteur de CO. Sa durée de vie maximale est de six ans.
  • Page 72 Limitations de la technologie CO: Le CO5-MC utilise un élément de détection électrochimique CO, et a donc certaines limites de performance. L’élément de détection de CO a une durée de vie type de 6 ans à compter de la date de fabrication. Il est programmé pour indiquer une alerte après six ans de fonctionnement, mais c’est le code de date du produit, plutôt que ce programme, qui doit déterminer le moment du remplacement du produit.
  • Page 73 AVIS D’INFORMATION IC: Toute modifi cation non autorisée pourrait annuler autorisation votre d’utiliser l’équipement. Cet appareil est conforme avec Industrie Canada exemptes de licence RSS ou les normes. Son fonctionnement est sujet aux deux conditions suivantes: (1) cet ap- pareil ne doit pas émettre de brouillage nuisible, et (2) cet appareil doit accepter toute interférence reçue, y compris les interférences pouvant entraîner un fonctionnement indésirable du dispositif.
  • Page 74 15 % à 95 % d’humidité relative, sans condensation Homologation: Certifi é conforme à la norme CSA 6.19-01 Pour les demandes d’indemnisation/réparations dans le cadre de la garantie, veuillez contacter le fabricant : Silent Call Communications 5095 Williams Lake Road Waterford, MI 48329 800-572-5227 Veuillez consulter www.SilentCall.com...