7.4 Filter Arrangement

CAUTION: FIRE HAZARD
Never install a filter on the supply air side. Filters should
always be installed on return air side of system.
WARNING: CARBON MONOXIDE AND POISONING HAZARD
Never operate a furnace without a filter or with filter
access door removed.
Filter size
Ecoer
96% AFUE Gas Furnace MGH96 series does not include a fi lter from
The
the manufacturer. The fi lter and filer rack must be fi eld supplied and fi eld
installed. A high velocity fi lter is recommended, see recommended fi lter size and
type in Table 2. One of the most common causes of furnace malfunctions is a
blocked or dirty fi lter. The fi lter must be inspected monthly for dirt
accumulation and replaced if necessary.
Filter type
Air velocity through disposable fi lters may not exceed 300 feet per minute (FPM).
All velocities over this require the use of high velocity fi lters. If a normal speed
disposable fi lter is used and air speed exceeds 300 feet per minute (FPM), two
side returns or one side return and the bottom return may be needed. For airfl ow,
refer to Tables 3 & 4.
NOTICE:
If disposable fi lters are used, air passage through fi lters
should be increased to twice the size of original air
opening by using a transition duct or using two fi lters in V
shape (see Fig. 19) in normal duct size.
Figure 19
Furnace cabinet width
17-1/2
21
24.5
Table 2
Manufacturer recommended high velocity fi lter sizes - Inch
Data subject to change
Side return
Locate the 4 knockout locations. These indicate the size of the cut-out to be made
in the furnace side panel. Refer to Fig 20, "Side Return Knockout Markings".
Figure 20
Install the side fi lter rack (fi eld supplied) following the instructions provided with
that accessory. If a fi lter(s) is provided at another location in the return air system,
the duct work may be directly attached to the furnace side panel.
Bottom Return fi lters
Filter(s) may be located in the duct system outside the furnace using an external
duct fi lter box attached to the furnace plenum or at the end of the duct in a return
fi lter grille(s). The use of straps and/or supports is required to support the weight
of the external fi lter box.
Filter size
Side return
16X25
16X25
16X25
Installation, Operation & Maintenance
Side return knockout markings
Dimensions of return air "cut out" must match those shown in Figure 1.
DO NOT cut outside of the "knockout" markings.
Bottom return
16X25
20X25
24X25
07-2021 | Ecoer Inc.
Front of
Furnace
Cut out for
side return
Filter type
High Velocity (600 FPM)
High Velocity (600 FPM)
High Velocity (600 FPM)