BACnet Router Start-up Guide
BAS Router (BACnet Multi-Network Router)
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after January 2015
Kernel Version:
6.17
Application Version:
0.3.0
Document Revision:
3

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BACnet and is the answer not in the manual?

Questions and answers

Summary of Contents for FieldServer BACnet

  • Page 1 BACnet Router Start-up Guide BAS Router (BACnet Multi-Network Router) APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after January 2015 Kernel Version: 6.17 Application Version: 0.3.0 Document Revision:...
  • Page 2: Table Of Contents

    Appendix A Useful Features ..............................12 Appendix A.1. Tooltips ................................12 Appendix B Limited 2 year Warranty ........................... 14 FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com...
  • Page 3: Bacnet Router Description

    The BACnet Router provides stand-alone routing between BACnet networks such as BACnet/IP, BACnet Ethernet, and BACnet MS/TP — thereby allowing the system integrator to mix BACnet network technologies within a single BACnet internetwork. There are three physical communication ports on the BAS Router. One is a 10/100 Mbps Ethernet port and the other two are RS-485 MS/TP ports.
  • Page 4: Installing The Bacnet Router

    Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his expense. Modifications not expressly approved by FieldServer could void the user's authority to operate the equipment under FCC rules”...
  • Page 5: 10/100 Ethernet Connection Port

    The Ethernet Port is used both for BACnet Ethernet and BACnet/IP communications. It is also used for configuring the Router from a Web page. Follow the steps below to connect the Router to a BACnet network and optionally to a PC for configuration purposes: ...
  • Page 6: Connecting To The Bacnet Router

    CONNECTING TO THE BACNET ROUTER The FieldServer Toolbox Application can be used to discover and connect to the BACnet Router on a local area network. To connect to the BACnet Router over the Internet using Toolbox, add the Internet exposed IP address of...
  • Page 7: Using A Web Browser Directly

    BACnet Router is 192.168.2.101, Subnet Mask is 255.255.255.0  If the PC and the BACnet Router are on different IP Networks, assign a Static IP Address to the PC on the 192.168.2.X network. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com...
  • Page 8: Configuring The Bacnet Router

    6.1.3 All connections  Network Number - set up the BACnet network number for the connection. Legal values are 1-65534. Each network number must be unique across the entire BACnet internetwork.  Enable - enable or disable the connection; note that BACnet/IP Primary is always enabled.
  • Page 9: Bacnet Ip Secondary

    NAT Router. If no NAT Router is being used, these fields can be left blank.  IP Port - this MUST be different to the IP Port used on the BACnet IP Primary connection. Default is 47809 (0xBAC1). 6.1.6 BACnet MSTP ...
  • Page 10: Diagnostics

    Router Port by which each device can be reached. Device Discovery is limited to 300 devices. There may be more devices on a large BACnet network, and the Who-Is request can be limited to devices of interest by configuring discovery parameters.
  • Page 11: Export Button

    Device Discovery is performed by the device object configured on the Router. Since this device is bound locally to the BACnet IP Primary segment, all devices present on this BACnet segment will appear as local devices with network number 0. Also, to discover only the devices present on this BACnet segment, set the Network parameter to 0.
  • Page 12: Appendix A Useful Features

    Note that the DHCP Server becomes inactive if another DHCP Server is detected on DHCP Server the network. Network Number Enter a value between 1 and 65534 that is unique across the entire BACnet network. The IP Port number to be used for this BACnet/IP connection. Common values: 47808, IP Port 47809.
  • Page 13 Token Usage Timeout (ms) Set a larger value to improve network reliability with slow devices. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com...
  • Page 14: Appendix B Limited 2 Year Warranty

    In all cases FieldServer Technology’s responsibility and liability under this warranty shall be limited to the cost of the equipment. The purchaser must obtain shipping instructions for the prepaid return of any item under this warranty provision and compliance with such instruction shall be a condition of this warranty.