OPERATION
The H808 is a current-sensitive switching device that monitors current (amperage)
in the conductor passing through it. A change in amperage in the monitored
conducter that crosses the switch threshold plus the hysteresis value will cause the
resistance of the status output to change state, similar to the action of a mechanical
switch. The setpoint is adjustable through the action of a 20-turn potentiometer
(see CALIBRATION section). The status output is suitable for connection to building
controllers or other appropriate data acquisition equipment operating at up to 30
volts. The H808 requires no external power supply to generate its output.
NOTES
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) Current Transformer (CT) as shown. This technique can be
combined with wrapping (see below) to add range for a low current load on a high
current source.
2.5A
DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.
Terminate the CT secondary before applying current.
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product's maximum current for the number of turns
through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating
and permanent equipment damage.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor
body to produce multiple turns. This increases the current measured by the
transducer.
Z201763-0E
PAGE 2
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
H808
> 50 A (Sensor max.)
150A
5A
300A:
H68xx-5A CT
< 0.75 A (Sensor Min.)
4x
0.5A
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
INSTALLATION GUIDE
CALIBRATION
Before beginning calibration, establish normal load conditions.
OK!
A
Then choose either A or B below.
A. To monitor under-current (belt loss, coupling shear, status)
!
OK!
A
1. Turn setpoint screw
clockwise until Status
Open LED turns ON.
2. Slowly turn the screw counter-clockwise until the Status Closed LED just
turns ON.
Status
Setpoint
Closed
STOP
B. To monitor over-current (mechanical problems, seized impeller)
!
OK!
A
1. Turn setpoint screw
Setpoint
counter-clockwise until
Status Closed LED turns ON.
2. Slowly turn the setpoint screw clockwise until the Status Open LED just
turns ON.
Status
Open
Setpoint
STOP
TROUBLESHOOTING
Problem
No Reading at
• Check sensor calibration (see above)
Controller
• Check for control power at sensor (<30VDC)
• Check for amperage in monitored conductor (>0.75A)
• Verify correct polarity
Setpoint screw has
• The setpoint screw has a slip-clutch at both ends of its travel to
no stops
avoid damage. Twenty turns CCW will reset the sensor to be most
sensitive. Repeat calibration above.
Both LEDs are lit
Unit is out of calibration. Turn screw 20 turns CCW and recalibrate.
STATUS
OK!
Status
Open
Setpoint
STOP
3. Turn the screw an
Setpoint
+
additional 1/4 turn
counter-clockwise for
1/4
operational margin.
STATUS
OK!
Status
Closed
STOP
+
3. Turn the setpoint
Setpoint
screw an additional
1/4 turn clockwise for
1/4
operational margin.