Honeywell Modutrol IV M9175D 1014 Manual page 9

Table of Contents

Advertisement

The motors in the application need to be all symmetrical or all
asymmetrical. The M62 motor needs to be a "-S" slaving
model, as listed in Table 8. In order to get the correct response
the Series 62 needs the appropriate shunt resistor from Table
8. The motors' potentiometer settings are given in the
configuration table (Table 9) below. When slaving more than
one Series 90 motor use the appropriate resistor table as
indicated by the configuration table and install two resistors to
ONE of the motors (Tables 10 and 11). If the motor is the M62
master connect one resistor from terminals T to G and one
from T to Y. If the motor is one of the M90 slaves connect one
resistor from terminals R to B and one from R to W.
NOTE: More than 6 slaves is not recommended.
OS Number
M6284D1000-S, M6284D1026-S, M6284D4004-S,
M6285A1005-S, M6285A1054-S, M6285A4009-S
M6274F1009-F, M6284F1070-F, M6284F1078-F,
M6285F1001-F, M6294F1009-F, M6294F1017-F,
M6284D1032-F
M6284A1071-S, M6284A1089-S, M6284C1028-S
M6284A1030-S, M6284A1055-S, M6284A1097-S,
M6284B1004-S, M6284C1010-S, M6284C1044-S,
M6284F1013-S, M6284F1039-S, M6285A1039-S,
M6285A1047-S, M6285C1001-S, M6294B1036-S,
M6294D1008-S
M6284F1062-S
"-S" Slaving Series 90 Mod IV Motor
"-F" 0-10K Feedback
Symmetrical or
Asymmetrical
Symmetrical
Symmetrical
Symmetrical
Symmetrical
Asymmetrical
Asymmetrical
Asymmetrical
Asymmetrical
Table 10. Resistor Table 1
Number of Motors in Parallel
1
2
3
4
5
6
Table 8. Series 60 and Series 90 in Slaving Application
600 Ohms
10 K Ohms
196/346 Ohms
119/224 Ohms
1800 Ohms
Table 9. Configuration Table
Master
Slave
Stroke
Stroke
Stroke Pot
160
160
CW
90
90
CCW
160
90
CCW
90
160
Configuration not recommended
160
160
CW
90
90
CCW
160
90
Configuration not recommended
90
160
Configuration not recommended
Resistor Value
NONE
3500 Ohms
2000 Ohms
1300 Ohms
1000 Ohms
800 Ohms
Feedback
Sensitivity
Resistance
Adjustment
No
No
Yes
Yes
No
Master
Master
Sensitivity Pot
CW
CCW
CW
CW
CW
Number of Motors in Parallel
1
2
3
4
5
6
9
SERIES 90 MODUTROL IV
Internal
Linear
Series 90 Slaving
Shunted
Feedback
Yes
No
187 Ohm
No
Yes
Not Available
Yes
No
274 Ohm
Yes
No
Not Necessary
Yes
No
Not Available
Slave
Slave
Stroke Pot
Sensitivity Pot
CW
CW
CCW
CCW
CCW
CCW
CW
CW
CW
CW
Table 11. Resistor Table 2
NONE
5000 Ohms
2400 Ohms
1700 Ohms
1400 Ohms
1200 Ohms
MOTORS
Shunt Resistor
Resistor
Table
1
2
1
1
1
Resistor Value
63-2631—07

Advertisement

Table of Contents
loading

This manual is also suitable for:

Modutrol iv 90 seriesModutrol iv m9175d 1014 (u)

Table of Contents