Summary of Contents for SANJIANG JTY-GD-01K

  • Page 1 Multi-Area Agent Releasing Control System...
  • Page 2: Table Of Contents

    Contents I. Overview................................1 II. Features................................1 III. Technical Parameters..........................1 IV. System Installation and Connection......................2 V. Description of the Control Panel.........................6 VI. Description of the Keyboard Operation....................8 VII. Power Management for the Control Panel..................... 8 VIII. System Adjustment........................... 9 IX. System Maintenance..........................10 X.
  • Page 3: Overview

    Version:170720 SANJIANG ELECTRONICS I. Overview Multi-area Agent Releasing Control System includes JB-QB-QM200/n(n=2-4) Agent Releasing Control Panel (hereinafter briefed as JB-QB-QM200/4 or the control panel, with JB-QB-QM200/4 agent releasing control panel as the main) and agent releasing device, HFC-227ea heptafluoropropane (hereinafter briefed as HFC-227ea) agent , smoke detector (JTY -...
  • Page 4: System Installation And Connection

    Version:170720 SANJIANG ELECTRONICS 3. Main Technical Parameters for Alarm bell Input Voltage DC24V Max operating current 18mA Power Temperature:-10℃~50℃ Operating Environment Humidity:≤95%(noncondensing) Dimensions φ150×58mm 4. Main Technical Parameters for Extinguishing Agent Device Action Startup Figuration Size Deposit Maximal Load Pressure...
  • Page 5 Version:170720 SANJIANG ELECTRONICS Figure 3 Installation of Agent Releasing Device Structure of the agent releasing device and the main parts is shown in Figure 4. Figure 4 l First ensure the outlet elbow of the electromagnetic valve is firmly placed and the outlet of the elbow is vertically upward, and then carefully move the storage device into the cabinet.
  • Page 6 Version:170720 SANJIANG ELECTRONICS JTY-GD-01K JTY-GD-01K JB-QB-QM200/n JTW-ZD-01K JTW-ZD-01K Alarm Bell AC220V/50Hz Electromagnetic valve Figure 5 Signal Terminal load Common Figure 6 Terminal load Terminal load Alarm Bell Eelectromagnetic valve JTW-ZD-01K JTY-GD-01K 10 11 16 17 20 21 28 29 31 32...
  • Page 7 Version:170720 SANJIANG ELECTRONICS Note: l In area n (n=1-4), zone 1 connects with conventional smoke detector JTY - GD - 01K; While the connection is in open circuit, the system will alarm that zone 1 of area n has trouble; while the detector alarms or the connecting wire is in short circuit, the system will alarm that zone 1 of area n has a fire alarm.
  • Page 8: Description Of The Control Panel

    Version:170720 SANJIANG ELECTRONICS of one battery and the black wire with “-” pole of another battery, then use one wire to connect the batteries in series. Note: Installation sequence of the storage batteries: first fix the batteries in the box, then connect the wires as is shown in figure 9, otherwise it may cause short circuit easily.
  • Page 9 Version:170720 SANJIANG ELECTRONICS (Reserve indicator light) ◎ RELEASE TROUBLE When the system detects open circuit in the terminal of electromagnetic valve, this light will be on. ◎ INPUT TROUBLE (Reserve indicator light) ◎ OUTPUT TROUBLE (Reserve indicator light) AC TROUBLE...
  • Page 10: Description Of The Keyboard Operation

    Version:170720 SANJIANG ELECTRONICS light will blink. If system pause occurred in release delay status (pause on the main panel is pressed), it will exit release delay status and the light is out. Note: The reason that can’t enter release startup status after release delay includes: Other area is starting electromagnetic valve, wait till other area finished the act, and then enter release startup status.
  • Page 11: System Adjustment

    Version:170720 SANJIANG ELECTRONICS system will keep the discharging depth of the battery at over 19V to ensure the performance and longevity of the battery. When the system has a trouble in the power module, it will alarm for AC TROUBLE. If the power supply trouble affects the precision of detection zone, the system will give the alarm for power supply trouble and, at the same time, stop the partially affected monitoring function to prevent erroneous actions.
  • Page 12: System Maintenance

    Version:170720 SANJIANG ELECTRONICS Note: 1. After testing, first remove power supply (include AC power and DC power) and reinstall the electromagnet (As shown in figure 4), apply power again to ensure normal operation of the device. The spur guard on electromagnetic valve is used for locking cam deflector rod, which can be pulled down only after drawing out spur guard when starting the container valve manually.
  • Page 13 Version:170720 SANJIANG ELECTRONICS Symptom: With AC input, the system alarms AC trouble When the voltage of AC input is beyond AC187V-AC242V, the power supply module of the system will enter protected status, please confirm the voltage of AC input. Symptom: System alarm is delayed too long The system is probably in the environment with strong interference;...