Global Fire Equipment ORION-BCM LSC Installation Manual

Global Fire Equipment ORION-BCM LSC Installation Manual

Addressable battery charger module with integrated loop sounder circuit

Advertisement

Quick Links

Global Fire Equipment // ​ g lobalfire.pt
ORION-BCM LSC
Addressable Battery Charger Module with Integrated
Loop Sounder Circuit
INSTALLATION MANUAL
OVERVIEW
The ORION-BCM LSC is a self contained EN54-4 Battery Charger Module with an integrated Loop Sounder Circuit
that is controlled and monitored through GFE addressable loop. It also incorporates internal Alarm and Fault relays.
When connected to the analo​ g ue detection loop of any of GFE's analogue addressable panels, the ORION-BCM LSC
occupies two consecutive addresses in the loop. In addition to the PSU output for powering external devices, it also includes
a Conventional Sounder output, which substantially increases its scope of usage. Activation of sounder output can be
achieved either by addressable system cause-effect programming as a normal addressable sounder or directly at the
ORION-BCM (access code required).
An internal monitoring system continuously checks all circuits, ensuring fault detection and notification, listed below. In
addition to local notification, status is also reported to addressable system.
● Sounder Circuit Integrity Fault
● Battery Charger Fault (voltage level and charging behaviour)
● Mains Fault (voltage level) and Earth Fault
● Output Supply ​ V oltage Level
● Communications Fault (On the Addressable Panel)
● General System Fault (by the means of independent watchdog system).
MAIN FEATURES
● Voltage-free inputs to activate built-in Relay for controlling Door Holders and Sounder Circuit
● One supervised Conventional Sounder Circuit
● Dedicated battery charger (Secondary Supply) for Sounder Circuit and Auxiliary Power
● Addressable Loop Interface with fault report feedback (supervision) and sounder activation acknowledgement /control
● Two relays output for Fault (NC) and Fire (SPDT) signal - unmonitored
● Supervised 24V Supply Output with 900mA
● EN54-4 Compliant
ORION-BCM LSC​ has the following local controls:
● Internal Buzzer Silence
● System Reset
● Lamp Test
● Sounders circuit ON/OFF operation
● Disable Auxiliary Outputs
● Disable Sounders
The ORION-BCM LSC Module will reset each time the Addressable Loop is restarted as an integrating part of the whole
Addressable system.
ma_orionbcmlsc_01_010001_en_180711
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ORION-BCM LSC and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Global Fire Equipment ORION-BCM LSC

  • Page 1 ● System Reset ● Lamp Test ● Sounders circuit ON/OFF operation ● Disable Auxiliary Outputs ● Disable Sounders The ORION-BCM LSC Module will reset each time the Addressable Loop is restarted as an integrating part of the whole Addressable system.
  • Page 2: Important Safety Notes

    MOUNTING PANEL The ORION-BCM LSC housing is designed for either surface or semi-recessed mounting. Cable entry points are provided at the top and back of the housing. Do not drill additional holes as cables could then interfere with the PCB or standby battery position.
  • Page 3: Sounder Circuit Wiring

    All sounders must be polarized; non-polarized sounders will indicate a fault on the sounder circuit. The sounder circuit can be activated from the Addressable Panel, by direct activation from ORION-BCM LSC Panel button (access level 2) or by remote input (EV).
  • Page 4: Connecting The Panel

    Global Fire Equipment // ​ g lobalfire.pt ma_orionbcmlsc_01_010001_en_180711 Auxiliary Relay Contact Fault Provides Fault signal to external devices. Relay NC contact 2A @ 30V DC resistive / 0.25A @ 230V AC resistive. Also Active for microprocessor fault. Active until Reset and all faults are cleared. Relay contact will open when any fault is present on the system.
  • Page 5 A – DIL Switch for address assignment (Address to the Analog Loop) B – Analog Loop Connection (Input and Output) C – Connection to the ORION-BCM LSC Main Panel (Data connector) D – LED Status Indicators E – Jumper (Not Used - must be fitted)
  • Page 6: Status Leds

    Global Fire Equipment // ​ g lobalfire.pt ma_orionbcmlsc_01_010001_en_180711 DIL SWITCH ADDRESS ASSIGNMENT OPERATION AND OVERVIEW STATUS LEDs FAULT​ - LED used to indicate any FAULT condition present on panel. DISABLED​ - Used to indicate that the panel has features that have been disabled in Access Level 2.
  • Page 7 DISABLE SOUNDER​ - Use this button to disable or re-enable Conventional sounder circuit (S1). Internal Addressable Interface (ADLI-BCM) ORION-BCM LSC occupies two consecutive addresses on the addressable loop, each one reporting as follow: Address programmed in DIL switch is recognized as a SOUNDER Addressing range must be between 94 and 125.
  • Page 8: Access Levels

    FAULT – Sounder Circuit Fault (open/short circuit, etc.) 4 (see Note) FAULT – Communication with ORION-BCM LSC ​ T his status is only reported by the addressable panel. ORION-BCM LSC doesn’t report fault and fault relay is NOTE:​ not activated.
  • Page 9 On the Fault Relay test, generate a fault (example: remove the sounder circuit EOL or remove Mains Power) and verify the Fault relay operation. NOTE: ​ C ommunication faults between ORION-BCM LSC and the Addressable System will only be signaled at the Addressable panel. Fault relay will not activate if ADLI-BCM is unplugged.
  • Page 10: Standby Battery Calculation

    Global Fire Equipment // ​ g lobalfire.pt ma_orionbcmlsc_01_010001_en_180711 STANDBY BATTERY CALCULATION Battery capacity​ ​ s hould be between 2 x 2.4 Ah 12V DC and 2 x 7 Ah 12V DC. The battery Ah required for a given installation is calculated from the following formula: Standby time Alarm &...
  • Page 11 Global Fire Equipment // ​ g lobalfire.pt ma_orionbcmlsc_01_010001_en_180711 Example of application (External switch Sounder Activation) This implementation, has the ability to, by using two external independent switches on the inputs, overlap (the addressable order) the Sounder Output or the Fire Alarm Relay state.
  • Page 12: Technical Specifications

    Global Fire Equipment // ​ g lobalfire.pt ma_orionbcmlsc_01_010001_en_180711 TECHNICAL SPECIFICATIONS POWER SUPPLY MAINS SUPPLY VOLTAGE 230 +10% -15% V AC Min. 21V DC - Max. 30V DC INTERNAL POWER SUPPLY (28.5V DC nominal) Max. Ripple 1 Vpp TOTAL OUTPUT CURRENT...
  • Page 13 Global Fire Equipment // ​ g lobalfire.pt ma_orionbcmlsc_01_010001_en_180711 GLOBAL FIRE EQUIPMENT S.A. Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL Tel: +351 289 896 560 • Sales: sales@globalfire.pt • Technical Support: techs@globalfire.pt • ​ w ww.globalfire.pt...

Table of Contents