Introduction
An EVCS is a fixed, secure, bi-directional, full duplex
voice communication system to assist fire fighters in an
emergency in high rise buildings or large sites where radio
communication may not work, and covers the operation
of fire telephones, disabled refuge systems and the
Disabled Toilet Alarm.
The VoCALL Compact Emergency Voice Communications
System (EVCS) is designed to fully comply with
BS5839-Part 9:2011 (abb. Pt9) for use as a fire telephone
system, disabled refuge call system or as a combined
system when both fire telephones and disabled refuge
points are required.
Suitability
Fire telephone systems are recommended for all
public buildings and multi story buildings over four
floors by BS9999.
Disabled refuge systems are required by Building
Regulations Approved Document B for all non-domestic
dwellings. Building Regulations Approved Document B
also requires all buildings where the public or disabled staff
gain access to any floor other than the ground floor using
lifts or stairs are required to exit.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VoCALL CFVCCM9 compact master and is the answer not in the manual?

Questions and answers

Summary of Contents for Eaton VoCALL CFVCCM9 compact master

  • Page 1 Technical Data PR211-183-505-01 VoCALL CFVCCM9 compact master & VoCALL CFVCCS10 compact master installation, commissioning and maintenance manual Introduction Suitability An EVCS is a fixed, secure, bi-directional, full duplex Fire telephone systems are recommended for all voice communication system to assist fire fighters in an...
  • Page 2: Product Overview

    Remove the VoCALL Compact unit from its packing, and check the contents against the following list: 1. VoCALL CFVCCM9 Compact Master unit. 2. Installation & maintenance manual (this document). 3. User guide & logbook. 4. Accessory pack with the following contents: a.
  • Page 3: Connecting Vocall Compact Unit

    Technical Data PR211-183-505-01 VoCALL CFVCCM9 compact master Unpacking the VoCALL CFVCCS10 Before mounting the unit on the wall it is advisable to remove the cable knockouts. Decide how the wiring will be brought into compact slave unit the panel and remove the required knockouts for cable entry. If a knockout is removed, fill the hole with a good quality cable gland.
  • Page 4 Technical Data PR211-183-505-01 VoCALL CFVCCM9 compact master Mains connection >0.75mm <2.5mm Main UNITY VoCALL Distribution Compact Board M9 or S10 > 3m m Type A outstations Each compact requires a 3A spur, returning to a breaker clearly marked “EVCS DO NOT TURN OFF” . If the units are distributed...
  • Page 5: Disabled Toilet Alarm

    Technical Data PR211-183-505-01 VoCALL CFVCCM9 compact master Handsets (Type A): Connections inside Connections inside exchange unit telephone unit Line - Connector on Network / Compact unit to black phone lead Line + Connector on Network / Compact unit to Yellow phone lead...
  • Page 6: Auxiliary Connections

    Technical Data PR211-183-505-01 VoCALL CFVCCM9 compact master Auxiliary connections Menu structure There are 3 levels of accessibility: User, Manager, and Engineer. The VoCALL Compact unit has three auxiliary connections as shown below: User level is accessible to all. • Manager level is accessible to those who log in as Manager •...
  • Page 7 Technical Data PR211-183-505-01 VoCALL CFVCCM9 compact master Navigating menus View fault log This menu is an information only menu. It displays the last 99 Cooper fire faults that have occurred, recording the type of fault and the date and time the fault occurred.
  • Page 8 Technical Data PR211-183-505-01 VoCALL CFVCCM9 compact master Set time+date Change engineer PIN Scroll through the root menu using the navigation keys until The default Engineer PIN to access the configuration menus is Set time+date is selected. Press TICK to show the Set 0000, but this can be changed.
  • Page 9 Technical Data PR211-183-505-01 VoCALL CFVCCM9 compact master Panel settings Relay Settings The In use relay has multiple settings: None, In use, Connected, Depending upon location of install, the buzzer can operate in or Ignored. different modes, and the access level used to operate the panel can be set.
  • Page 10 Technical Data PR211-183-505-01 VoCALL CFVCCM9 compact master This shows a sub menu for each outstation Battery Test This menu option performs a battery test when requested. The ø M9-outstation 1 menu shows the current state of the PSU and the battery. Both...
  • Page 11: Operation

    Technical Data PR211-183-505-01 VoCALL CFVCCM9 compact master Pressing TICK again will show the settings menu, with the The operator can then lift the master handset and connect to network option currently selected. If this is no, the CFVCCM9 unit the calling outstation by pressing the TICK key. If more than one will not communicate with the S10, and will be effectively isolated.
  • Page 12: Technical Specification

    Technical Data PR211-183-505-01 VoCALL CFVCCM9 compact master Technical specification Technical specification Product description VoCALL Compact 9 Line Master Unit VoCall 10 Line Slave Exchange Unit Power supply Volatge 230V ac +/- 10% 50/60Hz Internal power supply 14V dc Supply and battery...
  • Page 13 Eaton EMEA Headquarters Route de la Longeraie 7 1110 Morges, Switzerland Eaton.eu © 2018 Eaton All Rights Reserved Eaton is a registered trademark. Publication No. PR211-183-505-01 / CSSC-930 All other trademarks are property February 2018 of their respective owners.

This manual is also suitable for:

Vocall cfvccs10 compact master

Table of Contents