INSTALLATION OF INDOOR, OUTDOOR UNIT
10
Piping length and elevation
Multiple Piping Models
Phase Capacity(kBtu/h)
14/16
18
21
1Ø
24/27
30
40/48
Distributor type Models
Capacity
Phase
(kBtu/h)
40
1Ø
48
56
42
3Ø
48
56
h1
Multiple Piping Type
CAUTION
!
Capacity is based on standard length and maximum allowance length is on the basis of
reliability. If outdoor unit is at higher elevation than the indoor units, after 24 m of vertical
height, 1 oil trap is required.
Total Length
Max Length(A/B)
30
50
50
70
75
85
Total
Max Main Pipe
Length
Length (A/B)
100
50
135
55
145
55
125
55
135
55
145
55
A
h2
B
Max Elevation
(h1)
20
15
25
15
25
15
25
15
25
15
25
15
Total Branch
Max Branch
Pipe Length
Pipe Length
50
15
80
15
90
15
70
15
80
15
90
15
Distributor
A
Distributor
h1
Main Pipe
B
Distributor Type
(Unit: m)
In - In Elevation
(h2)
7.5
7.5
7.5
7.5
7.5
7.5
(Unit: m)
Max Elevation
In - In
(h1)
Elevation (h2)
30
15
30
15
30
15
30
15
30
15
30
15
Branch Pipe
h2