1000Vw+ Wiring Diagram - S&S Northern Merlin 1000VW+ Installation, Operating And Maintenance

Gas proving, electric & water isolation system
Hide thumbs Also See for Merlin 1000VW+:
Table of Contents

Advertisement

Merlin 1000VW+
1
2
L
N
E
Gas Valve
1. Mains Input 230V Single Phase.
2. Gas Solenoid Valve Power Output, 230VAC, Max 3A.
3. Electric Contactor Power Output, 230VAC, Max 3A.
4. Water Valve Power Output, 230VAC, Max 3A.
5. Supply Fan PD Switches terminal, this is disabled on this system.
6. Extract Fan PD Switches terminal, this is disabled on this system.
7. BMS output contacts. Normally Closed, Common and Normally Open. Max.1A @ 230VAC.
8. Gas pressure transducer, Red + positive, Black – negative and Blue IN.
9. Remote EM Stop buttons and Fire Alarm input wired in series (purchased separately). VOLT
FREE INPUT
10. Methane, CO or LPG Detector, power supply and volt free input (purchased separately).
CO2 Monitor (purchased separately). VOLT FREE INPUT
11. Fan Switch output (purchased separately). For wiring instruction, see Fan Switch user manual.
12. Fan PD Switches terminal (purchased separately). VOLT FREE INPUT
13. Permanent 12VDC output when there is power at the panel.
S&S Northern Ltd

1000VW+ Wiring Diagram

4
3
L N E
Water Valve
Please note, Mains wires and low voltage wires should
not be run in the same conduit as per the LOW
VOLTAGE DIRECTIVE
5
6
7
5
6
3
Pressure
Transducer
EM
Stop
Product Data Sheet
8
9
10
11
7
8
9
Gas Detector/
CO2 Monitor
PD Switches or Current Switches
(Volt Free)
F
A
N
P
D
S
W
I
T
C
H
12 13
10 11
8

Advertisement

Table of Contents
loading

Table of Contents