Page 1
Industrial Ethernet extender, for point-to-point, line and ring structures with in-house copper cables User Manual...
Page 2
Industrial Ethernet extender, for point-to-point, line and ring structures with in-house copper cables 2014-12-18 Designation: UM EN PSI MODEM-SHDSL/ETH, TC ETH EXTENDER Revision: This user manual is valid for: Designation Order No. PSI-MODEM-SHDSL/ETH 2313643 TC ETH EXTENDER S19 2702077 PHOENIX CONTACT 104273_en_01...
Page 3
How to contact us Internet Up-to-date information on Phoenix Contact products and our Terms and Conditions can be found on the Internet at: phoenixcontact.com Make sure you always use the latest documentation.
Page 4
The receipt of technical documentation (in particular user documentation) does not consti- tute any further duty on the part of Phoenix Contact to furnish information on modifications to products and/or technical documentation. You are responsible to verify the suitability and intended use of the products in your specific application, in particular with regard to observ- ing the applicable standards and regulations.
In addition, it can be used to enable Ethernet communication via a slip ring. On Page 30, we show an example of rotating applications where communication is built up redundantly by means of fiber optic and copper lines. 104273_en_01 PHOENIX CONTACT...
Page 8
Additional features – Two digital outputs for status transmission – Configuration software for extended functionality – Online diagnostics – Log book function including event description and suggested solution – Saving and printing of project and device configurations PHOENIX CONTACT 104273_en_01...
Page 9
Type Order No. Pcs. / Pkt. Industrial Ethernet extender, for point-to-point connections, line and ring PSI-MODEM-SHDSL/ETH 2313643 structures. Data rates of up to 30 Mbps on the in-house copper cables, inte- grated diagnostic function, two configurable alarm outputs Accessories Type Order No.
Page 10
Supply voltage // Ethernet // DSL port A // DSL port B // FE Test voltage 1.5 kV AC, 50 Hz Vibration resistance According to IEC 60068-2-6: 5g, 150 Hz Noise immunity EN 61000-6-2 Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC PHOENIX CONTACT 104273_en_01...
Page 11
For these devices, there are further requirements according to EN 50121-4 Table 1, Note 1. Section 1, Paragraph 3 of EN 50121-4 applies. Phoenix Contact QUINT power supply units are to be used directly on the device. UL, USA/Canada X II 3 G Ex nA nC IIC T4 Gc X Conformity assessment in acc.
PSI-MODEM-SHDSL/ETH, TC ETH EXTENDER TC ETH EXTENDER S19 The TC ETH EXTENDER S19 contains the following components: – 6 x PSI-MODEM-SHDSL/ETH Ethernet extender, Order No. 2313643 – 6 x DT-TELE-SHDSL surge protection, Order No. 2801593 – 1 x MINI-SYS-PS-100-240AC/24DC/1.5 power supply, Order No. 2866983 The device is a central communication unit for networking automated systems and external stations from any location.
Page 13
Pcs. / Pkt. Industrial Ethernet extender, for point-to-point connections, line and ring PSI-MODEM-SHDSL/ETH 2313643 structures. Data rates of up to 30 Mbps on the in-house copper cables, inte- grated diagnostic function, two configurable alarm outputs USB cable, assembled at both ends with USB plug connector VS-04-C-SDA/SDB/1.8...
Page 14
STAT STAT STAT STAT STAT LINK LINK LINK LINK LINK LINK STAT STAT STAT STAT STAT STAT Extender 1 Extender 2 Extender 3 Extender 4 Extender 5 Extender 6 Figure 1-2 Dimensions of TC ETH EXTENDER S19 PHOENIX CONTACT 104273_en_01...
Page 15
1.2.3 Connection sockets Ethernet RJ45 n.c. n.c. n.c. n.c. Figure 1-3 RJ45 socket for twisted pair cable (CAT5) Figure 1-4 Type B socket for type A configuration cable SHDSL Figure 1-5 M8 socket for star-quad twisted cable 104273_en_01 PHOENIX CONTACT...
Page 16
PSI-MODEM-SHDSL/ETH, TC ETH EXTENDER PHOENIX CONTACT 104273_en_01...
The device is not designed for use in atmospheres with danger of dust explosions. • The device is only intended for operation with safety extra low voltage (SELV) accord- ing to IEC 60950/EN 60950/VDE 0805. The device may only be connected to devices that meet the requirements of EN 60950. 104273_en_01 PHOENIX CONTACT...
The device must be stopped and immediately removed from the hazardous area if it is damaged, was subjected to an impermissible load, stored incorrectly, or if it malfunc- tions. • You can download the latest documents from phoenixcontact.net/products. PHOENIX CONTACT 104273_en_01...
The IP20 degree of protection (IEC 60529/EN 60529) of the device is intended for a clean and dry environment. Do not subject the devices to mechanical and/or thermal loads that exceed the specified limits. • The device is not designed for use in atmospheres with danger of dust explosions. 104273_en_01 PHOENIX CONTACT...
Page 20
PSI-MODEM-SHDSL/ETH, TC ETH EXTENDER PHOENIX CONTACT 104273_en_01...
In this mode, the devices establish the connection again automatically so that they can continue to access the remote devices. Firmware update With the configuration software, all accessible Ethernet extenders can be updated at once with a firmware update. 104273_en_01 PHOENIX CONTACT...
Page 22
When forwarding Ethernet telegrams, it is ensured for as long as possible that high-priority data (e.g. process data) will not be affected by a bandwidth bottleneck. This means that telegrams are forwarded according to the strict priority method in a PROFINET-compliant manner. PHOENIX CONTACT 104273_en_01...
Page 23
Both the local diagnostic data as well as the diagnostic data of the remote device are avail- able to you. Figure 3-4 PSI-CONF: path status In the case of an event message, possible reasons and solutions are displayed when you double-click the corresponding symbol in diagnostics. Figure 3-5 PSI-CONF: diagnostic function 104273_en_01 PHOENIX CONTACT...
SHDSL calculator software. The software can be downloaded free of charge at phoenixcontact.net/products. The actual data rate can be determined with a practical test. Phoenix Contact provides test kits with two Ethernet extenders, which can be used to test the path under realistic condi- tions.
Page 25
Longer distances can be achieved using high-quality cables with larger diam- eters. The industrial Ethernet extenders from Phoenix Contact support data rates of 32 kbps to 15.3 Mbps in 2-wire operation and data rates of up to 30 Mbps in 4-wire operation. The Ethernet extenders are suitable for in-house cables, not for public telephone networks.
Page 26
The spectrum of the SHDSL signals reaches about 2 MHz at maximum. The lower the data transmission rate, the narrower the spectrum. Figure 3-8 Frequency spectrum at 15320 kbps (200 kHz/div) Figure 3-9 Frequency spectrum at 64 kpbs (200 kHz/div) PHOENIX CONTACT 104273_en_01...
The 4-wire operation is recommended for applications with high bandwidth requirements and applications that require high reliability. You can also route the SHDSL lines A and B separately from each other. The lines can be of different lengths and be operated at different data rates. 104273_en_01 PHOENIX CONTACT...
Page 28
4-wire line structure For high bandwidths, a special application is possible. Several point-to-point connections with 4-wire connection need to be configured for this purpose. These 4-wire point-to-point connections are then linearly linked to each other via the Ethernet interfaces. PHOENIX CONTACT 104273_en_01...
Page 29
= 600 ms + Number of devices x 100 ms Recovery The paths of the SHDSL ring should show a very high connection quality during normal op- eration. Otherwise the t may deviate from the value calculated above. Recovery 104273_en_01 PHOENIX CONTACT...
SHDSL connection and redundancy management is ensured via managed switches (e.g. via the switches FL SWITCH LM 8TX, 2832632 or FL SWITCH SMCS 8TX, 2989226; Phoenix Contact has additional RSTP capable switches on offer). PHOENIX CONTACT...
Page 31
Figure 3-17 Link aggregation Several switches, such as the 7000 series switches from Phoenix Contact, support the Link Aggregation Control Protocol (LACP). Several physical links can be combined as one single logical link in this protocol. Link aggregation is possible with Ethernet extenders as of firm- ware version 3.0.
Page 32
The ring structure is completed by an external switch that controls the ring via STP/RSTP. The Ethernet extenders are operated in series; further settings are not necessary. This to- pology is possible as of firmware version 3.0. PHOENIX CONTACT 104273_en_01...
Page 33
Externally connected switches regulate the ring via STP/RSTP. In this case, the Ethernet extenders must be configured with a line structure and operated in hub mode. Hub mode is possible as of firmware version 3.1. 104273_en_01 PHOENIX CONTACT...
Page 34
This solution is possible with line and ring structures. Note that during manual setting of the data rate, the data rate also has to be sufficient for the longest possible connection. As an alternative, you can select the automatic setting of the the data rate. PHOENIX CONTACT 104273_en_01...
Connect DSL port A of device 1 to DSL port B of device 2. All LEDs light up during the boot process. If the device still has the default configuration, the "DIAG" LED lights up after the boot process for about 20 seconds. 104273_en_01 PHOENIX CONTACT...
Use a suitable screwdriver to release the locking mechanism on the snap-on foot of the device (see Figure 4-1 B). • Hold onto the device by the housing cover and carefully tilt it upwards. • Carefully lift the device off the DIN rail. PHOENIX CONTACT 104273_en_01...
Page 37
Holding the device by the housing cover, carefully push the device towards the mount- ing surface so that the device bus connector is securely fixed onto the DIN rail connec- tor. • Once the snap-on foot has been audibly snapped onto the DIN rail, check that it is fixed securely. 104273_en_01 PHOENIX CONTACT...
4-wire point-to-point connec- tion implemented Connection established 15 STAT (yellow) DSL ports No connection established Off (pulsating) (Lights up every 3 s) Connection quality adequate On (pulsating) (Goes out every 3 s) Connection quality good Link quality very good PHOENIX CONTACT 104273_en_01...
WARNING: Electrical voltage The device is only intended for operation in the control cabinet and with SELV according to IEC 60950/EN 60950/VDE 0805. The device may only be connected to devices that meet the requirements of EN 60950. 104273_en_01 PHOENIX CONTACT...
Page 40
The devices are preset for 2-wire operation. As of firmware version 2.1, the device detects the 4-wire installation automatically. If you set the correct operating mode using the config- uration software PSI-CONF however, the connection is established twice as fast as with automatic detection. PHOENIX CONTACT 104273_en_01...
Page 41
For a 2-wire connection, connect DSL port A (a and b) to DSL port B (a and b) of the next Ethernet extender. Connect a and b as desired. For point-to-point connections, DSL port B of the first device and DSL port A of the last device are not used. 104273_en_01 PHOENIX CONTACT...
Page 42
Connect DSL port A (a and b) of the second device to DSL port B of the first device (a and b). Select wire pairs In the case of star quad twisted cables, use the single wires on the opposite side (1a/1b or 2a/2b) to avoid crosstalk. Figure 4-7 Star quad PHOENIX CONTACT 104273_en_01...
Page 43
Color codes with varying cable types Figure 4-8 Phone cables with bundle stranding Figure 4-9 Layer stranding (two double wires, e.g. J-Y(ST)Y 2 x 2 x 0.6) Figure 4-10 Layer stranding (five double wires, e.g. J-Y(ST)Y 5 x 2 x 0.6) 104273_en_01 PHOENIX CONTACT...
Page 44
For short routes in which no great differences in potential can be expected or in which an equipotential bonding line is installed: Connect the shield at both ends. – For long routes: Connect the shield only at one end to avoid compensating currents. PHOENIX CONTACT 104273_en_01...
Page 45
No or only moderately good connection DSL B DIO = 24 V Good to very good connection DIO = open No or only moderately good connection Connecting • Connect the cable to the corresponding screw terminal block. 104273_en_01 PHOENIX CONTACT...
Page 46
The LEDs indicate (see also page 38): – LINK: whether the connection has been established – ERR: whether an error occurred – ACT: whether data traffic is taking place Please note that the "ERR" LED can also refer to an SHDSL connection. PHOENIX CONTACT 104273_en_01...
Page 47
USB. • Connect the device to the computer with the PSI-CA-USB A/MINI B/1METER cable (Order No. 2313575). Connect the mini-USB plug (type B) to the Ethernet extender and connect the USB plug to your computer. 104273_en_01 PHOENIX CONTACT...
Page 48
If the LED is off, no operating voltage is present. If it flashes at 1 Hz, the device is being supplied via USB and if flashing at 2 Hz this indicates that an error occurred when boot- ing. PHOENIX CONTACT 104273_en_01...
Page 49
-20 °C ... +55 °C ed in series) – Connected in series (without restrictions) -20 °C ... +50 °C Operation (other modules supplied via the device, 1.5 A, maximum) -20 °C ... +45 °C Storage/Transport -40 °C ... +85 °C 104273_en_01 PHOENIX CONTACT...
Connect DSL port A of device 1 to DSL port B of device 2. All LEDs light up during the boot process. If the device still has the default configuration, the "DIAG" LED lights up after the boot process for about 20 seconds. 104273_en_01 PHOENIX CONTACT...
Removal • Disconnect all cables from the device. • One person needs to hold the device as a second person loosens the screws (3) from the device. • Carefully lift the device out of the 19-inch rack. PHOENIX CONTACT 104273_en_01...
4-wire point-to-point connec- tion implemented Connection established STAT (yellow) DSL ports No connection established Off (pulsating) (Lights up every 3 s) Connection quality adequate On (pulsating) (Goes out every 3 s) Connection quality good Link quality very good 104273_en_01 PHOENIX CONTACT...
Page 54
Socket M8, 4-pos., DSL port A/B On the back of the device Connector C13/C14 acc. to IEC 60320-1, power supply Glass fuse , 20 x 5 mm, 1.6 A, medium-blow, 250 V Switch 1/0, switching the power supply on and off PHOENIX CONTACT 104273_en_01...
All output cables must be the correct size for the maximum device output current or have separate fuse protection. – Sufficient convection must be guaranteed. – The device may only be connected to devices that satisfy the requirements of EN 60950 (Safety of information technology equipment). 104273_en_01 PHOENIX CONTACT...
Page 56
4-wire installation automatically. If you set the correct operating mode using the config- uration software PSI-CONF however, the connection is established twice as fast as with automatic detection. 2-wire operation PSI-MODEM-SHDSL/ETH Ord.-No. 23 13 643 PSI-MODEM-SHDSL/ETH Ord.-No. 23 13 643 Figure 5-3 2-wire operation, point-to-point connection PHOENIX CONTACT 104273_en_01...
Page 57
For 4-wire connection, connect DSL port A (a and b) from the first device to DSL port B (a and b) of the second device. Connect a and b as desired. • Connect DSL port A (a and b) of the second device to DSL port B of the first device (a and b). 104273_en_01 PHOENIX CONTACT...
Page 58
Short flashing of the green "LINK" LEDs indicates that the DSL port is not disabled. The two "STAT" LEDs indicate the link quality. The longer the LED lights up, the better the quality of connection (see page 53). PHOENIX CONTACT 104273_en_01...
Page 59
The LEDs indicate (see also page 53): – LINK: whether the connection has been established – ERR: whether an error occurred – ACT: whether data traffic is taking place Please note that the "ERR" LED can also refer to an SHDSL connection. 104273_en_01 PHOENIX CONTACT...
Page 60
1 Hz in this case. DSL operation is not possible. Ambient temperature range The device may be operated in the temperature range 5 °C ... 35 °C. Provide sufficient ven- tilation and air-conditioning in the 19-inch installation system. PHOENIX CONTACT 104273_en_01...
DO = 24 V Good to very good connection DO = open No or only moderately good connection DSL B DIO = 24 V Good to very good connection DIO = open No or only moderately good connection 104273_en_01 PHOENIX CONTACT...
To start the software, Microsoft NET Framework 2.0 must be installed on your computer. If not already installed, it will be installed automatically. A USB driver is also required, which is installed automatically during software installation. For further instructions, please refer to the Help file for the installation program. PHOENIX CONTACT 104273_en_01...
PSI-CONF: Selecting the language and device Select Device • Select the PSI-MODEM-SHDSL/ETH by double-clicking. • A new dialog box appears that provides support during configuration. PSI-CONF al- ways starts in offline mode (the active mode is highlighted in green). 104273_en_01 PHOENIX CONTACT...
Page 64
A new window appears when you click on "Configuration file". Here you can choose between "New project" or "Open proj- ect". The configuration is created and saved on the computer in offline mode. It will be transferred to the Ethernet extender later. PHOENIX CONTACT 104273_en_01...
Line structure in 2-wire connection A network can be configured via several steps for up to 50 devices. Ring structure wizard Ring structure in 2-wire connection A network can be configured via several steps for up to 50 devices. 104273_en_01 PHOENIX CONTACT...
Page 66
Each device already has a name (Device 1, Device 2, etc.). You can select a device by names clicking on it or using the "Last device"/"Next device" buttons and assign a new name, e.g. "Device A" or "Pumping station". The name can contain 255 characters including special characters. PHOENIX CONTACT 104273_en_01...
Page 67
Manual setting of the data rate: Enter a fixed data rate. The lower the data rate, the more robust is the connection. However, it does not normally make sense to use a rate of less than 144 kbps. The slider control has no influence. 104273_en_01 PHOENIX CONTACT...
Page 68
If necessary, you can set the data rate (10 or 100 Mbps) and the type of communication (half or full duplex). You can set the configuration individually for each Ethernet extender. If the configuration is the same for each Ethernet extender, click on "Accept for all". PHOENIX CONTACT 104273_en_01...
Page 69
You can set the configuration individually for each Ethernet extender. If the configuration is the same for each Ethernet extender, click on "Accept for all". Step 6: Summary A summary of the settings is provided here. Click on "Print" to print out the settings. 104273_en_01 PHOENIX CONTACT...
Page 70
DSL A, DO = 24 V, good to very good connection DSL A, DO = open, no or only moderately good connection DSL B, DIO = 24 V, good to very good connection DSL B, DIO = open, no or only moderately good connection PHOENIX CONTACT 104273_en_01...
The order number can be used to clearly identify the device type. You can use this number to search for additional informa- tion and downloads for this device on the Phoenix Contact website. The order number is printed on the device.
Page 72
The line attenuation mainly depends on the cable length, the cable cross section, and the data rate. Network load (RX/TX) Network load for outgoing (TX) and incoming (RX) data traffic Error diagnostics Indicates how strongly SHDSL data traffic is disturbed. PHOENIX CONTACT 104273_en_01...
Page 73
The IDs of diagnostic messages are described under “Diag- nostic IDs” on page 79. Event description Description of the event Port Port to which the event is assigned Seconds since boot Time in seconds between the event and the time of the last boot procedure 104273_en_01 PHOENIX CONTACT...
Page 74
The line attenuation mainly depends on the cable length, the cable cross section, and the data rate. Port A/B/Ethernet port Network load for incoming data traffic RX network load PHOENIX CONTACT 104273_en_01...
There are two options: You can open an existing file and save it to the Ethernet extender that is connected via USB. You can read the existing configuration and save it to a file. The file extension is ".dat". 104273_en_01 PHOENIX CONTACT...
Order No. The order number can be used to clearly identify the device type. Serial No. The serial number is unique for each device. It can be used to assign a device and is printed on the device. PHOENIX CONTACT 104273_en_01...
Page 77
Name of the open firmware file Firmware version Firmware version of the update Release date Date the firmware to be installed was released Start update The selected firmware file is transferred to the device that is connected via USB. 104273_en_01 PHOENIX CONTACT...
Page 78
PSI-MODEM-SHDSL/ETH, TC ETH EXTENDER PHOENIX CONTACT 104273_en_01...
Both devices must have By a data rate that was set too the default settings high Reduce data rate. Error when boot- VCC and Switch defective – Replace device ing the switch ERR are flashing (2 Hz) 104273_en_01 PHOENIX CONTACT...
Page 80
– – – – Incompatible DIAG on An incompatible device from DSL_A, Connect correct device device connected ERR on Phoenix Contact DSL_B (only Ethernet extender 2.0 or LINK of the (PSI-MODEM-SHDSL/SERIAL or PSI-MODEM-SHDSL/ETH) later) corresp. PSI-MODEM-SHDSL/PB FW 2.0 or port...
Page 81
– Update firmware with later) installed with firm- gle transfer. PSI-CONF configuration ware 3.0 or earlier software Firmware and configuration soft- ware can be downloaded free of charge at phoenixcontact.net/products. 104273_en_01 PHOENIX CONTACT...
Page 82
Check the condition of the cable – Check the cable length (less than 100 m) DSL port A or B errors – Check whether the wire pair is connected correctly (twist- ed pair, star quad stranding). – Reduce DSL data rate. PHOENIX CONTACT 104273_en_01...
Page 83
The warning is relevant if the link good flickers "good". DSL_B quality was previously "very (goes out good". If necessary, reduce the every 3 s) data rate if more interference oc- curs. 92 ... Reserved – – – – 104273_en_01 PHOENIX CONTACT...
Page 84
FW 3.0 ports the functions of the firmware ver- software discovered in the sion 3.0, such as ring, remote diag- Firmware and configuration soft- system nostics and remote configuration. ware can be downloaded free of charge at phoenixcontact.net/products. PHOENIX CONTACT 104273_en_01...
Page 85
Set condition not – The set condition is no longer met for – – met anymore for the DO. Set condition not – The set condition is no longer met for – – met anymore for the DIO. 104273_en_01 PHOENIX CONTACT...
Page 86
This can happen when you later) is switching back replug a 4-wire installation to a 2-wire to 2-wire mode installation and then remove just one (line) of the two plugs. The removed device switches automatically to the correct operating mode. PHOENIX CONTACT 104273_en_01...
Page 87
– First, the last established SHDSL line – – changed (only in is reserved. Afterwards, the line qual- 3.0 or the ring) ity is evaluated automatically and the later) line with the lowest performance is re- served. 104273_en_01 PHOENIX CONTACT...
– Make sure side perforated grid of the housing is unob- structed. – Remove neighboring devices that have a high ther- mal output or power dissipation. – Provide air-conditioning for the 19"-rack installation system. PHOENIX CONTACT 104273_en_01...
Page 89
2-wire operation, line structure or point-to-point connection ....41 Figure 4-5: 2-wire operation, ring structure ............41 Figure 4-6: 4-wire operation, point-to-point connection ......... 42 Figure 4-7: Star quad .................... 42 Figure 4-8: Phone cables with bundle stranding ........... 43 104273_en_01 PHOENIX CONTACT...
Page 91
See Line structure Four-wire operation............. 42 Data rate PSI-MODEM-SHDSL/ETH ........42 Automatic setting........... 67 TC ETH EXTENDER S19........57 Manual setting ............67 Frequency spectrum PSI-MODEM-SHDSL/ETH ........9 See SHDSL frequency spectrum TC ETH EXTENDER S19........13 104273_en_01 PHOENIX CONTACT...
Page 92
Shielding ..............44 Single transfer............. 70 Slip ring communication..........30 Pluggable screw terminal block Star coupler See COMBICON See Connection station Point-to-point connection ........27, 42 Star quad ..............42 Potentially explosive area........18, 36 Star structure .............. 29 PHOENIX CONTACT 104273_en_01...
Page 93
Troubleshooting ............79 Twisted pair cables ............. 46 Two-wire operation PSI-MODEM-SHDSL/ETH ........41 TC ETH EXTENDER S19........56 UL approval..............11 Update See Firmware update USB interface PSI-MODEM-SHDSL/ETH ........47 TC ETH EXTENDER S19........60 Zone 2................. 18 104273_en_01 PHOENIX CONTACT...