HPAC 90
Cooling and Heat pump models
Operating Instructions
& Safety Guide
0800 211 611
andrews-sykes.com
General Safety
This equipment should only be used by a competent
person who has read and understood these instructions.
Check condition of equipment before use. If unit is
showing any signs of damage contact your supplier
immediately.
Never operate this equipment if you are ill, feeling tired or
under the in uence of alcohol or drugs.
Keep all vents and grills clear of obstructions.
Keep children and animals away from electric powered
equipment. Never leave them alone when the unit is in
use.
Make sure equipment is switched o and unplugged after
use.
Electrical Safety
This unit operates on a 415 volt 5pin 125amp power supply
The power cable must be a minimum of 32mm2 up to a
maximum length of 40 meters. All cables over 40 meters will
require a larger C.S.A of cable.
A lways inspect plugs and power cables for damage before
plugging into power supply.
DO NOT USE IF ANY DAMAGE IS FOUND.
If an extension lead is used, ensure it is of the correct
standard and fully uncoiled before use.
Cables must not be laid in wet or damp areas.
Do not move equipment while operating.
Getting started and operation
Position equipment on level ground.
Position away from any possible
flammable materials.
Do not use within any zoned or hazardous
areas.
Do not position HPAC 90 inside of any
building or temporary structure
Keep at least 1 meter of clearance around
the unit and don't restrict the air flow
around the chiller
The HPAC 90 unit can only be controlled
on outlet Air and not inlet Air
Fig 1
5 pin 125amp 415 volt Appliance inlet
plug found on the HPAC 90
Fig 1
Need help?
Do you have a question about the HPAC 90 and is the answer not in the manual?
Questions and answers