EasyBuilder Pro Software Settings
Launch EasyBuilder Pro software, select your project file, press F7 shortcut key to open the download
dialog box: Select Ethernet > IP tab > Enter your cMT-FHDX IP > Click Download to download this project
file to cMT-FHDX.
(Please refer to EasyBuilder Pro User Manual for software operation details.)
Communication Connection
7
NOTE: COM2 and COM3 [RS485] support MPI 187.5K, please use one at a
PIN#
9 Pin, Male, D-sub
COM1 [RS232]
1
COM2 [RS485]
2
COM3 [RS485]
3
4
5
6
7
8
9
8
DIP SW Settings
9
Battery Replacement
Battery Specification: UL Certification Battery, Type CR1220, Rated 3V, Max. Abnormal Charging Current
10mA, Working Temperature: max. 70°C
Battery replacement shall be performed by qualified personnel (engineer) only and care must be taken
when handling lithium batteries.
The terms HDMI, HDMI High-Definition Multimedia Interface, and the HDMI Logo are trademarks or
registered trademarks of HDMI Licensing Administrator, Inc.
time.
COM2 [RS-485]
COM1
COM3
[RS-232]
[RS-485] 2W
2W
4W
Data+
RxD
TxD
Data-
GND
Data+
Rx+
Data-
Rx-
Tx+
Tx-
SW1
SW2
Mode
OFF
OFF
Normal Mode
OFF
Hide Start Button
ON
OFF
Update OS
ON
Restore Factory Default
ON
ON
NOTE: Make sure that all local and national electrical standards are met when
CAUTION
installing the unit. Contact your local authorities to determine which codes apply.
Use power output that meets SELV (Safety Extra-Low Voltage) requirements. The unit can be
powered by DC power only, voltage range: 24±20%, compatible with most controller DC
Power
systems. The power conditioning circuitry inside the unit is accomplished by a switching power
supply. The peak starting current can be as high as 2A.
If the Power LED does not light up immediately after power up, remove power. A resettable
Fusing Require-
fuse will protect against overcurrent faults in DC circuit and the resetting will take place after a
ments
period of time. Check wiring for proper connections and try to power up again.
A resettable fuse will prevent damage for overcurrent condition however it isn't guaranteed.
High Voltage
DC voltage sources should provide proper isolation from main AC power and similar hazards.
A Hard-wired EMERGENCY STOP should be fitted in any system using an HMI to comply with
Emergency Stop
ICS Safety Recommendations.
Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same
Supply Voltage
power supply. Note: The 24 VDC output from some controllers may not have enough current to
Condition
power the unit.
a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).
b. Please use twisted pair cables for power wire and signal wire and conform to the
impedance matching.
c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression
Wire Routing
devices.
d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.
e.
Add a resistor and capacitor in the parallel connection between the ungrounded DC power
supply and the frame ground. This provides a path for static and high frequency
dissipation. Typical values to use are 1M Ohm and 4700pF.
DANGER
The system designer should be aware that devices in Controller systems could fail and
thereby create an unsafe condition. Furthermore, electrical interference in an operator
interface can lead to equipment start-up, which could result in property damage and/or
physical injury to the operator.
Hardware
If you use any programmable control systems that require an operator, be aware that this
Considerations
potential safety hazard exists and take appropriate precautions. Although the specific design
steps depend on your particular application, the following precautions generally apply to
installation of solid-state programmable control devices, and conform to the guidelines for
installation of Controllers recommended in NEMA ICS 3-304 Control Standards.
To conform with ICS Safety Recommendations, checks should be placed in the controller to
ensure that all writable registers that control critical parts of plant or machinery have limit
Programming
checks built into the program, with an out-of-limit safe shut down procedure to ensure safety of
Considerations
personnel.
Limited Warranty
A copy of the Warranty and Limitation of Liability is contained in the product box. It can
also be found on the Maple Systems website.