Guidebook for installation, handling and maintenance – ENG Electric heater HPe2/4CM Electric heater for outdoor and indoor installation FU-HPe2/4CM-10/2020...
Dimensions of HPe2/4CM Components Technical data of HPe2/4CM 4. Device installing Warnings before mounting Distances Front door opening procedure for HPe2/4CM Montage HPe2/4CM on wall Execution of hydraulic connections 4.6.1 Installation filling with water and waterproof testing 4.6.2 Heating pump air emission and de-blocking 4.6.3...
Description of symbols and instructions for safe work Objašnjenje simbola i uputstva za siguran rad Make sure that device is available only to professionals. Description of symbols Installation and commissioning, and maintenance and Warnings repair, must be done only by service authorised for electrical works.
2.2.2 Regular application 2.5 Inhibitors and anti-frost products HPe2/4CM may only be used in conjunction with a heat It is not allowed to use protective products against frost neither inhibitors. Id it is not possible to avoid anti-frost pump, as a supplementary heat source controlled via a protection then should use anti-frost products allowed for heat pump.
Device data Norms, regulations and standards This product is in compliance with the following regulations: EN 50110-1:2003 – Handling and work with electrical installations EN 55014:2001 – Electrical-magnetic compatibility – conditions for consumers’ devices for households, electric devices and similar devices ...
(preferably switching on the electric HPe2/4CM). • In case of failure (servicing) of the heat pump, the HPe2/4CM Beech, oak, veneered wood, felt, takes over the heating of the building - until the pump is...
The product should be in horizontal position during transportation Avoid shocks or collisions Packed HPe2/4CM put on carts for bags if needed secure it with strip and drive it to its mounting place. Remove packaging. ...
Dimensions and technical data Components Signal clamps for switching on relays and connecting Casing of HPe2/4CM Exchanger in HPe2/4CM temperature sensors Electric heater in HPe2/4CM Relay for switching heating group Thrust line Temperature sensor Return line Safety thermostat (STB) Thermal insulation HPe2/4CM...
Page 10
Min. cable cross-section mm² 3×2,5 3×4 5×2,5 Max. allowed working pressure Min. allowed working pressure Max. temperature °C Water volume Discharge line connection DN25 (1”) SN Return line connection DN25 (1”) SN Device weight (without water) 10,5 Table 4: technical data HPe2/4CM...
Comply with regulations on electric installations and freezing. minimum distances in force in subject countries. Place HPe2/4CM on the wall in such manner to leave free space as illustrated in the Image 3 Be careful prior to assembly NOTE: Material damage occurred due to incompliance with further instructions! ...
Plot the drill hole positions for the mounting kit respecting the minimum free space dimensions next to the HPe2/4CM (Image 3) and the dimensions in Table 5. Drill the holes according to the dimensions for the given type of HPe2/4CM.
Check that all safety elements are working properly. If the HPe2/4CM is tested for leaks and no leakage is observed, set the required operating pressure, according to the pre-pressure of the expansion vessel.
Min. cable cross section 5 × 2,5 mm² If both the HPe2/4CM and the Heat Pump are supplied from the same place or there are no FID switches on the installation, Table 6: Nominal current, el. fuses and cross-section of power cables a neutral line from the RSN clamps can be fed to the RSP3 for HPe2/4CM 6kW for three-phase power supply.
Electric connecting Connection of HPe2/4CM to mono-phase mains Connection to a mono-phase network is possible with a power limit of 2kW or 4kW, where the connection must be fixed (no connection is allowed with a socket) and the cross-section of the connection cable must be according to Table 7a, or 7b for 4kW power.
The line clamps for grounding the device is yellow-green. When inserting the power cord into the HPe2/4CM, carefully route the cable to the clamps blocks, taking care not to damage the cables inside the device.
Check all electrical connections Switch on circuit breakers (protective circuit) Turn on the HPe2/4CM and use it only if there is sufficient quantity of water HPe2/4CM must work with minimum pressure of 0.5 bars Before turn on, test if the following elements and joints are connecter correctly and work correctly: ...
User must comply with instructions for operating the HPe2/4CM User may only turn on the HPe2/4CM (except the first start-up), adjust temperature on the regulating device and turn off the HPe2/4CM. All other operations must be performed by authorised service ...
The volume of newly filled water is reduced in the first days Insufficient or unprofessional maintenance of HPe2/4CM can lead to damage or destruction and after charging due to heating. This creates airbags that create to loss of Warranty rights interference in the heating system.
Page 21
Cleaning and maintenance Re-fill the water and air-vent the installation WARNING: Material damage due to heat tension. Filling heating installations in warm condition can produce cracks due to tension Fill heating installation only in cold condition (temperature of starting duct lines of max 40 °C) WARNING: Material damage due to frequent re- filling!
Cleaning and maintenance The commissioning, inspection and maintenance record serves Inspection and maintenance as an attachment for copying Executed works should be authorised by signature and At least once a year perform maintenance or date. when a check shows the status of installations that require maintenance.
Environment protection/Waste disposal Environment protection /Waste disposal One of the basic concepts of business is environment protection. Quality of products, thriftiness and environment protection are equally valuable goals for us. It is critical to strictly comply with law and regulations on environment protection.
For repairs use only original spare parts. TROUBLE DESCRIPTION CAUSE MEASURE Provide power supply HPe2/4CM is out of power supply Turn on fuses HPe2/4CM does not Display does not react, Fuses on bottom plate are off ...
Page 25
EU regulation no. 811/2013 11. Product data sheet (in accordance with EU regulation no. 811/2013) Manufacturer MIKOTERM DOO Centrometal – HPe2/4CM Brand name Models HPe2/4CM Room heating: Seasonal energy-efficiency class Room heating: Nominal heat output(*8) (*11) rated η Room heating: Seasonal energy efficiency(*8)
Page 26
Centrometal d.o.o. Glavna 12 40306 MACINEC HRVATSKA Croatia tel: +385 (0)40 372 600 email: komercijala@centrometal.hr...