STEPS TO DEFAULT SiX, SIXA and PROSIX
Defaulting a device may be necessary if the device is enrolled in a panel (paired with a panel) in a
location that is different than the intended panel, and the installer does not have access to the
unintended panel to delete the sensor.
Each device provides visual indication showing whether or not it is paired with a controller. This is
described in the table below for each device.
The procedure to default each device is primarily the same (except for the keypad and key fob): Open
the device cover, remove the battery, activate the tamper switch, and then reinstall the battery while
the tamper switch is still held down.
For devices other than the SiXFOB, this process is available for 24 hours after enrollment with the panel
and while the device remains powered (battery installed in sensors; AC power applied at keypad). For
the SixFOB, this process expires after the first 100 transmissions.
PROCEDURES
MODEL
DEFAULT PROCEDURE
SiXCT
1. Open the cover.
SiXMINICT
2. Remove the battery.
SiXGB
3. Hold the tamper switch down.
4. Reinstall the battery while still holding
the tamper switch down.
SiXSIREN
1. Open the cover.
SiXSIRENOD
2. Remove the batteries.
3. Hold the tamper switch down.
4. Reinstall the batteries while still holding
the tamper switch down.
SiXSMOKE
1. Open the cover.
2. Remove the batteries.
3. Activate the tamper with a magnet.
4. Reinstall the batteries while still
activating the tamper switch.
SiXCOMBO
1. Open the cover.
2. Remove the battery.
3. Activate the tamper with a magnet.
4. Reinstall the battery while still holding
the tamper switch down.
SiXPIR
1. Open the cover.
SiXHEAT
2. Remove the battery.
3. Hold the tamper switch down.
4. Reinstall the battery while still holding
the tamper switch down.
LKP500-EN
1. Press the 3 key until the advanced menu
is displayed
(SiX KEYPAD)
2. Scroll until "Default" is displayed.
3. Press select.
SiXFOB
1. Press and hold the three white buttons
simultaneously for more than five (5)
Company Internal
SERIES DEVICES
PAIRED/NOT PAIRED INDICATION
Indicator
Paired
Green LED
slow blink
when tamper
faulted
Indicator
Paired
Green LED
slow blink
when tamper
faulted
Indicator
Paired
Green LED
slow blink
when tamper
faulted
Indicator
Paired
Green LED
slow blink
.
when tamper
faulted
Indicator
Paired
Green LED
slow blink
when tamper
faulted
Indicator
Paired
Status icon slow blink
Indicator
Paired
both LEDs
LEDs not
Not Paired
fast
blinking
Not Paired
fast
blinking
Not Paired
fast
blinking
Not Paired
fast
blinking
Not Paired
fast
blinking
Not Paired
fast
blinking
Not Paired
alternating,