Caution: electrical interference can cause erratic system operation.
Do not route temperature sensor wiring with building power wiring,
next to control contactors, near light dimming circuits, or electric
motors.
Use shielded cable to reduce interference when rerouting is not
possible.
Be sure wires have a cable separate from the humidistat cable.
See Figure 5 for wiring diagram.
exterior Wall installation
To mount the Outdoor Temperature Sensor outdoors the signal wire will
need to penetrate an exterior wall. Use the following guidelines for proper
operation of the sensor:
Mount the sensor where:
there is good air circulation
wire distance between sensor and humidistat is less than 200 feet
it can measure true outdoor ambient air temperature
it is above the expected snow line
do not mount the sensor:
in direct sun
where it may be covered by debris, snow, or ice