The table below gives details of all menu items, in the order that they will appear: Menu Item Function Default Value Internal Safe Pressure Within The Vacuum Cylinder For The 1 Start Pressure 14 PSI Pumps To Start Circulating Water 0 PSI (LTHW Internal Stop Pressure For The Pumps, Required Vacuum Systems) 2 Stop Pressure Pressure -7 PSI (CHW Systems) Internal High Pressure Alarm Setting, To Activate The Slam-shut 3 Alarm Pressure 58 PSI Solenoid Valve 4 Normal Minutes Normal Interval Between Pump Runs (De-aeration) 60 MINS 5 Turbo Hours Running Time For Turbo Mode Before Returning To Normal 168 HRS Time Limit For Vacuum Generation Or Restoration Of Internal 6 Timeout Minutes 10 MINS Pressure (Error Checking) Time Setting For Water To Be Re-circulated Into The Main 7 Purge Seconds 20 SEC System, Taking A Fresh Sample 8 Pump Count Pump Activation Counter (Logging) 9 Pump Hours...
Operation Once commissioned, the Deaerating unit should operate without any user intervention. For practical guidance on diagnosing and rectifying faults, please refer to the Troubleshooting section of this manual. Deaerating Fault Codes Auto/Manual Fault Code Description Reset Auto Reset Error Incorrect password (Code) entered. High Pressure High system pressure, audible alarm sounds. The Safety Solenoid closes. This alarm will self-reset when the system Auto Reset pressure returns to normal, audible alarm can be silenced by pressing “mute”.
Troubleshooting If for any reason the Deaerating unit does not seem to be functioning correctly, please refer to the table below for a list of solutions to known problems. Symptom Problem Solution The safety solenoid valve will automatically close and the The internal pressure within the vacuum system will attempt to self- cylinder has reached the high pressure reset during the next alarm limit, probably due to the pressure Deaerating cycle. Repeated High Pressure reducing valve being contaminated with High pressure alarms will debris. require the pressure reducing valve to be inspected and cleaned. Clean the air intake preventer, The Vacuum cylinder is full of air and the and test the unit. If this fails low level switch is stopping further pump then check the bypass solenoid activation to prevent the pump(s) running and pipework for dry. There is an air leak on the cylinder, Insufficient Vacuum contamination. Finally replacing the bypass solenoid is contaminated with the automatic air vent debris or the air intake preventer is assembly is the best course of contaminated with debris action. Check the controller settings The pump is drawing either too much first to ensure that the correct current or not enough, signifying a...
Any modifications to the supplied equipment must be approved in writing by Nexus Valve, failure to do so will invalidate the warranty. All goods are carefully tested and inspected before dispatch. Should any goods appear defective owing to faulty materials or manufacture, they must be returned to us for examination.
If the unit is identified with a manufacturing defect then no charge is made for correcting the defect. The Nexus Valve equipment is manufactured to order and is clearly marked, where applicable, with a unique serial number, allowing traceability to both individual model configuration and the engineer or site responsible for the build and test.
Need help?
Do you have a question about the PSD and is the answer not in the manual?
Questions and answers