Summary of Contents for LogiCO2 MK10

  • Page 1 User’s Manual MK10 Safety System Connected to Central Unit...
  • Page 2: Table Of Contents

    Please note that whenever installing or disconnecting a system, refer to this manual first! Table of contents Safety..........................3 The purpose of CO2 detection General Description ...................... 4-8 Product description, performance and intended use Temperature surveillance The function of the Central Unit The function of the CO2 Sensor Installation ........................9-11 Connection Diagrams .....................12...
  • Page 3: Safety

    The function of the equipment will be impaired if it is not properly installed. LogiCO2 bears no legal responsibility for the functionality of the CO2 Safety System if installed by a company that has not been certified by LogiCO2.
  • Page 4: General Description

    II General Description Product description, performance red LED will light continuously and the digital display will show ALARM. The room in which the sensor and intended use is located must not be entered when the CO2 concentration is over 3%! The Carbon Dioxide (CO2) Safety System is Emergency services must be contacted! designed to measure CO2 concentration in a...
  • Page 5 General Description II Internal buzzer Internal layout The built-in buzzer has two different sounds: 1. Beeping sound indicates Low Alarm (warning) and Error. 2. Continuous sound indicates High Alarm (danger) Reset button A short push on the reset button mutes the internal buzzer during an alarm situation.
  • Page 6 TWA ALARM Display information during TWA Alarm: Display information during start-up: CO2 TWA Alarm CO2 TWA concentration Software version Cycle/Start-up shows in highlighted text LogiCO2 Central unit ID CO2 TEMP ID CO2 ID CO2 FW:1420* 1 Heating… 1 0,14% ALARM...
  • Page 7: The Function Of The Co2 Sensor

    Central Unit. CO2 TWA alarm is classified as Low Alarm. The CO2 Alert MK10 has 2 red diodes on the side marked with L1 and L2. When starting the sensor, both diodes L1 and L2 go ON. This is a self CO2 “Awareness Alert”...
  • Page 8 II General Description DIP-switch settings CO2 Awareness CO2 Awareness Indication Activated Indication NOT Activated All DIP-switches are set to OFF as default. CO2 Awareness Indication configuration Sensor ID is configured using switch 4 of the DIP on the sensor board Switch 4 OFF : CO2 Awareness Indication activated (default) Switch 4 on : CO2 Awareness Indication NOT activated...
  • Page 9: Installation Iii

    Installation III OBSERVE! NOTE: If a room only has mechanical ventilation, it should have a sensor, since the ventilation can be turned of. “All persons responsible for the operation and maintenance of this equipment must read and The sensor should be mounted 12” / 30 cm understand the safety and operating information from the floor to the bottom of the sensor.
  • Page 10 III Installation • Mount the Plug-lock so that the power supply Horn/Strobe cannot be disconnected without the use of mechanical tools. The CO2 Safety System is equipped with a pre-wired Horn/Strobe. Its power cord has a blue connector • Make sure the Central Unit is not placed in the at the end terminal that is connected to the splitter, risk area that is being monitored! marked with a blue dot.
  • Page 11 All signs must be mounted in a secure, permanent way to eliminate any risk that they fall down. Sign 1: ”CO2 Safety System - What to do” should be placed next to the Central Unit. CO2 Safety System – MK10 What to do in case of an ALARM? 1.
  • Page 12: Connection Diagrams

    IV Connection Diagrams Connection diagram Option US Option CO2 Safety System – MK10 WARNING FLASH-24-R What to do in case of an ALARM? 1. Keep Calm! 2. Turn off the sounding alarm on the Central Unit by pressing the RESET button on the front.
  • Page 13: Function/Installation Check V

    Function/Installation check V Function and installation check for the MK10 CO2 Safety System Store Name (Store Number) Address City State / Region Zip Code Country Date of inspection Service Provider’s Company Name Repair Company Name (if different) Power supply control...
  • Page 14 V Function/Installation check CO2 Values displayed on the Central Unit When the System is running properly, the CO2 level measured by each sensor is displayed in % (actual value) and in ppm (Time Weighted Average over 8 hours). The values are displayed sequentially on the second line of the display.
  • Page 15 Function/Installation check V Horn/Strobe with sign Warning Lamp with sign Sensor 2 Sensor serial number (normally written on a sticker on the side of the Sensor housing ). CO2 Value on Sensor CO2 TWA on Sensor Is the green diode ON Is the yellow diode ON Is the red diode ON Is the Horn/Strobe or Warning Lamp mounted at a height of 2.1-2.5 m/6.9-8.2 ft so that the staff can see it...
  • Page 16: Ordering Service And Parts

    5. The Sensor and Central Unit housing must NEVER be opened by unauthorized personnel. 6. Cleaning is done by use of water on a moistened cloth. Ordering parts or service Description Item code CO2 MK10 Detector SET 4 A 2049 CO2 MK10 Detector SET 4 A consists of: CO2 Central Unit MK10...
  • Page 17: Specifications Vii

    Specifications VII Environmental conditions for system a) For indoor use. b) Calibrated for altitude up to 2 000 m. c) Ambient temperature 0 °C to +40 °C. d) Maximum relative humidity 95 % (non condensing). e) MAINS supply voltage fluctuations up to ±10 % of the nominal voltage. TRANSIENT OVERVOLTAGES up to the levels of OVERVOLTAGE CATEGORY II.
  • Page 18 VII Specifications CO2 SENSOR Power supply: 24V DC Power consumption: No alarm status: 56 mA Alarm status: 68 mA (external optional warning lamp not included) Wiring connections: RJ 45 Digital interface: RS485 serial port – MODBUS Display: Acoustic signal-strength: 76 dBa (1m) max. Approval: Manufactured in accordance with DIN 6653-2.
  • Page 19 Specifications VII CO2 CENTRAL UNIT Supply: 24V DC Current consumption: No alarm status: 21 mA Alarm status: 32 mA Communication: RS485, Modbus Display: Graphical 128x64, backlit Acoustic signal-strength: 80 dBa (1m) max. Ambient temperature: 0 to +40°C (+32°F to +102°F) Humidity: 0-90% non-condensing Approval:...
  • Page 20 Sales and service contact: For parts or service contact your local authorized supplier or equipment service agent. Company: ........................Phone: ..........................Place company stamp or sticker here ©2014-11-25 Rev. 2.2, LogiCO2 International Manufactured by: LogiCO2 International AB E-mail: info@logico2.com Box 4113 Web: www.logico2.com...