WATER COOLED SELF-CONTAINED AIR-CONDITIONER INSTALLATION, OPERATION, MAINTENANCE IOM NO: O-WCP16-SEP21-2 Scan QR code to download the latest version of IOM Issue: O-WCP16-SEP21-2...
Page 2
Daikin makes no commitment to update or provide current information automatically to the manual owner. Updated manuals, if applicable, can be obtained by contacting the nearest Daikin Service office. Operating/service personnel maintain responsibility for the applicability of these documents to the equipment. If there...
The water-cooled self-contained air conditioner is the ultimate solution addressing the energy efficiency, reliability, indoor air quality, and sound concerns for commercial, industrial and institutional buildings. Daikin offers a simple system design, increases system redundancy by providing individual air conditioning systems per floor, lowers maintenance costs, eases operation and maintenance, and provides the lowest life cycle cost available.
Even though there is no vertical clearance specification listed, clearance above the unit may be an advantage during change out of any of the above components. Table 2: Minimum Installation Clearance Side Distance FRONT 1000 LEFT RIGHT REAR Issue: O-WCP16-SEP21-2 Page 2...
All openings around doors should be sealed. The return air opening must be acoustically treated. Noise will also be carried through the fan and supply ductwork to the occupied space. When the sound attenuation package is required, you should consider installing sound attenuation in the supply ductwork. Issue: O-WCP16-SEP21-2 Page 4...
4/14 3/14 4/14 3/14 Material & Thickness G3 & 25mm (nominal) 595 X 595 Nominal 961 X 518 (1) 1301 X 518 (1) 1377 X 677 (1) 1377 X 894 (1) Size (Qty) 290 X 595 Issue: O-WCP16-SEP21-2 Page 5...
Page 10
420 X 420 X 595 480 X 350 (15) 595 (4) Note: Cooling capacity based on nominal air inlet temperature of 26.7 C DB/19.4 C WB and condenser water temperature 30 C In/ 35 C Out. Issue: O-WCP16-SEP21-2 Page 6...
Page 12
2. EER = Total Cooling Capacity (MBH)/ Total Power Input (kW) Note: 1. Cooling capacity based on nominal air flow rate under given conditions and water temperature difference 5 2. Direct interpolation is allowed but extrapolation is not recommended. Issue: O-WCP16-SEP21-2 Page 8...
8. Size piping to minimize system pressure drop. 9. All piping must be supported independent of the unit. 10. To aid in service the unit should have a union in the water inlet and outlet water lines. Issue: O-WCP16-SEP21-2 Page 22...
Dirty filters will reduce the capacity of the unit and may result in frosted coils and safety shutdowns. The unit should never be operated for any length of time without the proper filters installed in the unit Issue: O-WCP16-SEP21-2 Page 23...
The figures shown in the Table 7 are for information purpose only. They should be checked and selected to comply with the local/national codes of regulations. This is also subject to the type of installation and conductors used. Issue: O-WCP16-SEP21-2 Page 31...
Correct Fan Motor Rotation Verify correct rotation of fan motor by ensuring cold air discharged from unit. Swap any two live wires on the incoming supply to the fan contactors if fan motor reverse direction. Issue: O-WCP16-SEP21-2 Page 32...
The heater is interlocked with the compressor contactor and is not controlled directly by the controller. When the compressor is OFF, a normally closed auxiliary contact on the compressor contactor closes the circuit and energize the crankcase heater. Issue: O-WCP16-SEP21-2 Page 47...
Page 52
If a condition of low or high air flow exists, a pulley change may be required. Once it is ascertained that the air quantity leaving the unit is according to the design CFM, the thermostats should be set to the desired space temperature. The system should now function as designed. Issue: O-WCP16-SEP21-2 Page 48...
It is the responsibility of the owner to provide the necessary maintenance for the unit. If a system failure occurs due to improper maintenance during the warranty period, Daikin will not be liable for costs incurred to return the unit to satisfactory operation.
Page 54
Table 9: Force for Different Pulleys & Belts Sizes (Fix Type) Setting Force to Deflect Belt 15mm per Meter of Span Pulley Type 1.3 x Basic Setting Force (kgf) Small Pulley Datum Diameter (mm) Minimum Maximum Issue: O-WCP16-SEP21-2 Page 50...
Page 55
* If the refrigerant gas leakage occurs during installation/servicing, be sure to ventilate fully. If the refrigerant gas comes into contact with fire, a poisonous gas may occur. Issue: O-WCP16-SEP21-2 Page 51...
Page 56
6. Defective overload protector. 6. Replace protector. 1. Slipping belts. 1a. Apply belt dressing/belt EXCESSIVE BELT tensioning. "SCREAM" WHEN FAN(S) START UP 1b. Adjust belt tension correctly. Issue: O-WCP16-SEP21-2 Page 52...
Page 57
Indoor coil 2 anti freeze[auto reset] Indoor coil 3 anti freeze[auto reset] Indoor coil 4 anti freeze[auto reset] Manual reset: When there is failure occurred, press MENU and key for 3 seconds to clear the errors. Issue: O-WCP16-SEP21-2 Page 53...