Download Print this page

Siemens GDB 1 Series Mounting Instructions page 7

Rotary-type actuator
Hide thumbs Also See for GDB 1 Series:

Advertisement

de
Kabelbezeichnungen
en
Wire designations
fr
Désignation des câbles
Building Technologies / HVAC Products
Anschluss
Code
Nr.
Antriebe
G
1
AC 24 V
G0
2
Y1
6
Y2
7
Y
8
U
9
Antriebe
N
4
AC 230 V
Y1
6
Y2
7
Hilfsschalter
Q11
S1
Q12
S2
Q14
S3
Q21
S4
Q22
S5
Q24
S6
Rückführ-
a
P1
potentimeter
b
P2
c
P3
Connection
Code
No.
AC 24 V
G
1
Actuators
G0
2
Y1
6
Y2
7
Y
8
U
9
AC 230V
N
4
Actuators
Y1
6
Y2
7
Auxiliary switch Q11
S1
Q12
S2
Q14
S3
Q21
S4
Q22
S5
Q24
S6
Feedback
a
P1
potentiometer
b
P2
c
P3
Câbles de
raccordement Code
No.
servo-moteurs
G
1
AC 24 V
G0
2
Y1
6
Y2
7
Y
8
U
9
servo-
N
4
moteurs
Y1
6
AC 230V
Y2
7
commutat
Q11
S1
eurs
Q12
S2
auxiliaires
Q14
S3
Q21
S4
Q22
S5
Q24
S6
potentiom
a
P1
ètre
b
P2
de retour
c
P3
Kabel
Bedeutung
Farbe
Abkür-
zung
rot
RD
System Potential AC 24 V
schwarz
BK
Systemnull
violett
VT
Stellsignal AC 0 V "Uhrzeigersinn"
orange
OG
Stellsignal AC 0 V "Gegenuhrzeigersinn"
grau
GY
Stellsignal DC 0...10 V, 0...35 V
rosa
PK
Stellungsanzeige DC 0...10 V
blau
BU
Nullleiter
schwarz
BK
Stellsignal AC230 V, Uhrzeigersinn
weiss
WH
Stellsignal AC 230 V,Gegenuhrzeigersinn
grau/rot
GYRD
Schalter A Eingang
grau/blau
GYBU
Schalter A Ruhekontakt
grau/rosa
GYPK
Schalter A Schliesskontakt
schwarz/rot
BKRD
Schalter B Eingang
schwarz/blau
BKBU
Schalter B Ruhekontakt
schwarz/rosa
BKPK
Schalter B Schliesskontakt
weiss/rot
WHRD
Potentiometer 0...100 % (P1-P2)
weiss/blau
WHBU
Potentiometer Abgriff
weiss/rosa
WHPK
Potentiometer 100...0 % (P3-P2)
Cable
Meaning
Color
Abbreviation
red
RD
System potential AC 24 V
black
BK
System neutral
purple
VT
Actuating signal AC 0 V "clockwise"
orange
OG
Actuating signal AC 0 V "anticlockwise"
gray
GY
Actuating signal DC 0...10 V, 0...35 V
pink
PK
Position indication DC 0...10 V
blue
BU
Neutral
black
BK
Actuating signal AC 230 V, "clockwise"
white
WH
Actuating signal AC 230 V, "anticlockwise"
gray/red
GYRD
Switch A input
gray/blue
GYBU
Switch A normally closed contact
gray/pink
GYPK
Switch A normally open contact
black/red
BKRD
Switch B input
black/blue
BKBU
Switch B normally closed contact
black/pink
BKPK
Switch B normally open contact
white/red
WHRD
Potentiometer 0...100 % (P1-P2)
white/blue
WHBU
Potentiometer pick-off
white/pink
WHPK
Potentiometer 100...0 % (P3-P2)
Câble
Signification
Couleurs
Abbreviation
rouge
RD
potentiel du système AC 24 V
noir
BK
zéro du système
violet
VT
signal de commande AC 0 V "sens horaire"
orange
OG
signal de comm. AC 0 V "sens anti-horaire"
gris
GY
signal de commande DC 0...10 V, 0...35 V
rose
PK
signal de position DC 0...10 V
bleu
BU
neutre
noir
BK
Signal de commande AC 230 V "sens horaire"
blanc
WH
Signal de commande AC 230 V "sens anti-horaire"
gris/rouge
GYRD
commutateur A entrée
gris/bleu
GYBU
commutateur A contact de repos
gris/rose
GYPK
commutateur A contact de travail
noir/rouge
BKRD
commutateur B entrée
noir/bleu
BKBU
commutateur B contact de repos
noir/rose
BKPK
commutateur B contact de travail
blanc/rouge
WHRD
potentiomètre 0...100 % (P1-P2)
blanc/bleu
WHBU
potentiomètre curseur
blanc/rose
WHPK
potentiomètre 100...0 % (P3-P2)
4 319 2883 0 g
M4634
02.11.2005
7/8

Advertisement

loading

This manual is also suitable for:

Glb 1 seriesGsf 1 series