'' WEATHER LIGHT '' SERIES FOR NON-MAINTAINED EMERGENCY LUMINAIRES
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
ILLUMINATION SOURCE
EMERGENCY ILLUMINATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
Thank you for purchasing this product of
O l y m p i a E l e c t r o n i c s . A E u r o p e a n
manufacturer.
GENERAL
These luminaires are used in places where
emergency luminaires are needed.
Each luminaire must be permanently
connected to mains power supply. In normal
operation the battery is charging and the 2
yellow LED's light in the screen (see step 4
on page 2). In case of a mains power
supply failure the luminaire will light the
led strip automatically in emergency mode.
When the mains power supply is restored
the device turns to normal operation.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance
or testing must be done by authorized
personel only.
2. The device must be connected to the
mains power supply thru a fuse dependent
by the total amount of the line's power load.
3. It is sugested to check every month the
indication LED for battery charging, and by
pushing the TEST button (see the paragraph
9 on page 2), to check the emergency cirquit.
The lamp should light as long as the TEST
button is
pressed. In the opposite condition
contact the installer.
Page 1 from 2
High Quality European based Manufacturers
GR-935/4P
GR-935/6P GR-936/4P GR-936/6P
4VA
4.8V/1.5Ah
From overcharge and full discharge
Charge indication LED, TEST button
90min
4 power LED's
6 power LED's
300lm
450lm
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
Bayblent FR3010, transparent polycarbonate
950gr.
3 years (1 year for the battery)
4. It is sugested to check every 6 months the
minimum autononous duration by
disconnecting the mains power supply. Count
the time that the led strip lights and in case of
less time than the minimum autonomous
duration the battery must be replaced. If the
measured time is considerably less than the
minimum autonomous duration
installer.
the light source must be done using parts of
the same type, by the manufacturer or by a
competent person.
5. In case of inactive use for a period greater
than 2 months, disconnect the battery by
pulling out the battery's connector.
6. I s not allowed to discard batteries in
t i
to common trash bins, they must be
discarded only
points. Do not incinerate.
INSTALLATION
To install the luminaire follow the installation
instructions οn page 2.
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
0: Non Maintained
A: Including test device
*90: 90min duration
180: 180min duration
220-240V AC/50-60Hz
4,8VA
4.8V/3Ah
24h
4 power LED's
300lm
IP 65
o
0 to 40 C
Up to 95%
363 x 145 x 73 mm
980gr.
The replacement of the battery and
in battery recycling
5,5VA
4.8V/4Ah(Ni-MH)
180min
6 power LED's
415lm
1020gr.
contact the
923936006_23_011