11. Maintenance

11.1 Trouble Shooting
Small problems sometimes can be solved locally with the help of the below tab of trouble shooting.
If you don't succeed, contact us or your nearest distributor.
Symptom
Indication on
front unit
Green LED is
always light
off.
Green LED
(PW) light on
and green LED
Thyristor unit
(ON) in light
doesn't go in
off condition.
conduction with
Green LED
input signal.
(PW) in light
on condition
and green LED
(ON) in light on
condition.
Load current
Green LED
flows also with
(ON) always in
no input signal.
light off
condition.
Current flows at
Yellow HB in
nominal value
light on
but yellow LED
condition.
(HB) in light on
condition.
Red LED (SC) is
Red LED in
lighted also if
light on
current is at
condition.
nominal value.
Thyristor unit
doesn't work
properly.
CD3000M-1PH up to 110A
Possible reasons of the symptom
No voltage auxiliary power
-
supply to terminals 1-3 (see
wiring diagram).
No input signal.
-
Reversed polarities of input
-
signal.
Reset contact in open condition
-
(see wiring diagram).
Fuse failure.
-
Load failure.
-
Load connection interruption.
-
Thyristor faulty and always in
-
open circuit.
With HB option the yellow led
-
(HB) in light on condition.
Short circuit on thyristor. If there
-
is HB circuit the red LED (SC) is
light on.
HB circuit not tuned.
-
Current transformers not
-
properly wired (if are external to
CD3000).
HB circuit not properly tuned.
-
Wrong input signal selection.
-
Wrong input signal calibration
-
(out of range).
Auxiliary voltage supply out of
-
limits.
53
Honeywell
Actions
Give auxiliary voltage supply
-
to terminals 1-3.
Provide to give input signal.
-
Reverse the input signal
-
polarity.
Make link on reset terminals.
-
Substitute the fuse.
-
Repair the load.
-
Provide to repair the wiring.
-
Substitute the faulty thyristor.
-
Check the load.
-
Substitute the thyristor.
-
Check that load is not in short
circuit.
Push CAL button in front unit
-
to start HB calibration
procedure.
Control current transformers
-
wiring and Push CAL button in
front unit to start HB
calibration procedure.
Push CAL button in front unit
-
to start HB calibration
procedure.
Control input signal setting.
-
Repeat input calibration
-
procedure.
Verify the auxiliary voltage
-
supply.
www.honeywell.com/imc