This manual is applicable for the products with software version 23 and later version. version 23 and later version. Copyright a April 2003, Eaton Corporation, all rights reserved. No part of this publication may be reproduced, transmitted, transcribed or stored in a retrieval system, or translated into any language in any form by any means without the written permission of Eaton Corporation.
Chapter 1 Overview Chapter 1 Overview 1-1 General 1-1 General The Fuzzy Logic plus PID microprocessor-based controller series, incorporate a bright, easy to read 4-digit LED display, indicating process value or set point value. The Fuzzy Logic technology enables a process to reach a predetermined set point in the shortest time, with the minimum of overshoot during power-up or external load disturbance.
Page 6
PID control with properly tuned PID + Fuzzy control Temperature point Figure 1.1 Figure 1.1 Fuzzy Control Fuzzy Control Advantage Advantage Load Disturbance Warm Up Time High Accuracy High Accuracy The series are manufactured with custom designed ASIC(Application Specific Integrated Circuit ) technology which contains a 18-bit A to D converter for high resolution measurement ( true 0.1 BF resolution for thermocouple and PT100 ) and a 15-bit D to A converter for linear current or voltage control output.
Page 7
Auto-tune Auto-tune The auto-tune function allows the user to simplify initial setup for a new system. A clever algorithm is provided to obtain an optimal set of control parameters for the process, and it can be applied either as the process is warming up ( cold start ) or as the process has been in steady state ( warm start ).
1-2 Ordering Code 1-2 Ordering Code TC 24- TC 24- PC 24- PC 24- Display Color Display Color Power Input Power Input 0: Red color 0: Red color 4: 90 - 250 VAC, 4: 90 - 250 VAC, 50/60 HZ...
1- 3 Keys and Displays 1- 3 Keys and Displays KEYPAD OPERATION KEYPAD OPERATION SCROLL KEY : SCROLL KEY : This key is used to select a parameter to be viewed or adjusted. UP KEY : UP KEY : This key is used to increase the value of selected parameter. DOWN KEY : DOWN KEY : This key is used to decrease the value of selected parameter.
Page 10
Output 2 Output 2 Indicator Indicator Output 1 Output 1 Indicator Indicator Figure 1.3 Figure 1.3 Front Panel Description Front Panel Description Table 1.1 Display Form of Characters Table 1.1 Display Form of Characters Display program code of the product for 2.5 seconds.
1- 5 Menu Overview 1- 5 Menu Overview User menu *1 User menu *1 Setup menu*1 Setup menu*1 Calibration Mode Calibration Mode (DISP=PV) (DISP=PV) (DISP=SP1) (DISP=SP1) 7.4 sec. 6.2 sec. 2 sec. Value Value LOCK Value Value INPT ADLO UNIT ADHI RTDL Manual...
1-6 Parameter Descriptions 1-6 Parameter Descriptions Parameter Default Parameter Description Range Notation Value ° 25.0 C Set point for output 1 Low: SP1L High :SP1H ° (77.0 F) Set point for output 2 ° when output 2 performs 10.0 C Low: -19999 High :45536 alarm function or dwell...
Page 13
Parameter Default Range Parameter Description Notation Value Degree C unit Input unit selection Degree F unit UNIT Process unit No decimal point 1 decimal digit Decimal point selection 2 decimal digits 3 decimal digits ° -17.8 C Input low sale value High: Low: -19999...
Page 14
Parameter Default Range Parameter Description Notation Value : Display process value normally Normal display selection DISP : Display set point 1 value normally ° ° 500.0 C 10.0 C Proportional band value High: Low: 0 ° ° (900.0 F) (18.0 F) Integral time value High: Low:...
Page 15
Parameter Default Range Parameter Description Notation Value : No Ramp Function : Use unit/minute as Ramp function RAMP Ramp Rate selection : Use unit/hour as Ramp Rate ° 500.0 C Ramp rate High: Low: 0 ° (900.0 F) : Output 2 No Function : Dwell timer action : Deviation High Alarm : Deviation Low Alarm...
Page 16
Parameter Default Range Parameter Description Notation Value Output 2 hysteresis value when output 2 ° 0.1 C ° High: 50.0 C O2HY Low: 0.1 performs alarm ° (90.0 F) ° (0.2 F) function Output 2 cycle time High: 90.0 sec. CYC2 Low: 0.1 18.0...
Page 17
Parameter Default Range Parameter Description Notation Value : 7 data bits Data bit count of digital DATA communication : 8 data bits : Even parity Parity bit of digital : Odd parity PARI communication : No parity bit : One stop bit Stop bit count of digital STOP communication...
Page 18
Parameter Default Range Parameter Description Notation Value Select 2nd parameter SEL2 Same as SEL1 for user menu Select 3rd parameter SEL3 Same as SEL1 for user menu Select 4th parameter SEL4 Same as SEL1 for user menu Select 5th parameter SEL5 Same as SEL1 for user menu...
Chapter 2 Installation Chapter 2 Installation Dangerous voltages capable of causing death are Dangerous voltages capable of causing death are sometimes present in this instrument. Before installation or sometimes present in this instrument. Before installation or beginning any cleaning or troubleshooting procedures the power beginning any cleaning or troubleshooting procedures the power to all equipment must be switched off and isolated.
2 - 3 Wiring Precautions 2 - 3 Wiring Precautions Before wiring, verify the label for correct model number and Before wiring, verify the label for correct model number and options. Switch off the power while checking. options. Switch off the power while checking. Care must be taken to ensure that maximum voltage rating Care must be taken to ensure that maximum voltage rating specified on the label are not exceeded.
Page 22
2.0mm 0.08" max. Figure 2.2 Figure 2.2 Lead Termination Lead Termination 4.5 ~7.0 mm 0.18" ~0.27" 90-250 VAC 2A/240 VAC 2A/240 VAC 47-63 Hz,10VA V+,mA+ V ,mA ° 50 C max. Air ambient Use copper conductors CAT. I I (except on T/C input ) Figure 2.3 Figure 2.3 Rear Terminal Connection...
2 - 4 Power Wiring 2 - 4 Power Wiring The controller is supplied to operate at 11-26 VAC / VDC or 90-250 The controller is supplied to operate at 11-26 VAC / VDC or 90-250 VAC. Check that the installation voltage corresponds with the power VAC.
Proper sensor type is also a very important factor to obtain precise Proper sensor type is also a very important factor to obtain precise measurements. The sensor must have the correct temperature range measurements. The sensor must have the correct temperature range to meet the process requirements.
Page 25
Figure 2.7 Figure 2.7 Output 1 Relay to Drive Contactor Output 1 Relay to Drive Contactor Figure 2.8 Output 1 Figure 2.8 Output 1 Pulsed Voltage to Drive SSR Pulsed Voltage to Drive SSR www.comoso.com...
Page 26
Load Load Figure 2.9 Output 1 Linear Current Figure 2.9 Output 1 Linear Current LOAD LOAD 120V/240VAC 120V/240VAC Mains Supply Mains Supply Figure 2.10 Figure 2.10 Output 2 Relay to Drive Load Output 2 Relay to Drive Load Figure 2.11 Figure 2.11 Output 2 Relay to Drive Contactor Output 2 Relay to Drive Contactor...
Chapter 3 Programming Chapter 3 Programming Press for 5 seconds and release to enter setup menu. Press to select the desired parameter. The display indicates the parameter symbol. Press to view or adjust the value of the selected parameter. 3-1 Lockout 3-1 Lockout There are four security levels can be selected by using LOCK parameter.
process value INHI INLO input signal 3-3 Control Outputs 3-3 Control Outputs There are 4 kinds of control modes can be configured as shown in Table 3.1 Table 3.1 Table 3.1 Heat-Cool Control Setup Value Table 3.1 Heat-Cool Control Setup Value Control OUT1 OUT2...
Page 30
Dead band = O1HY SP1 O1HY Time OUT1 Action Time www.comoso.com...
Page 31
Cool only control: Cool only control: www.comoso.com...
Page 32
You can use the program for the new process or directly set the appropriate values for PB, TI & TD according to experience. If the control behavior is still inadequate, then use to improve the control. See for manual tuning. Adjustment of CPB is related to the cooling media used.
Page 33
OUT2=DE.HI OUT2=DE.HI SV+SP2 SV+SP2-O2HY Time OUT2 Action Time SP2+O2HY Time OUT2 Action Time www.comoso.com...
Output 2 can be selected as alarm output. There are 6 types of alarm functions and one dwell timer can be selected, and four kinds of alarm modes ( ALMD ) are available for each alarm function. A process alarm sets two absolute trigger levels. When the process is process alarm sets two absolute trigger levels.
Holding Alarm : ALMD = HOLD Holding Alarm : ALMD = HOLD A holding alarm prevents an alarm from power up. The alarm is enabled only when the process reaches the set point value. Afterwards, the alarm performs same function as normal alarm. Latching / Holding Alarm : ALMD = L T.HO Latching / Holding Alarm : ALMD = L T.HO A latching / holding alarm performs both holding and latching function.
Output 2 can be configured as dwell timer by selecting TIMR for OUT2. As the dwell timer is configured, the parameter SP2 is used for dwell time adjustment. The dwell time is measured in minutes ranging from 0.1 to 4553.6 minutes. Once the process reaches the setpoint the dwell timer starts to time down to zero ( time out ).
Object Object Object Heater Heater Heater Heat Heat Heat Transfer Transfer Transfer 165 C 165 C 200 C 200 C 200 C 235 C Sensor Sensor Sensor 35 C temperature Adjust SHIF Display is stable difference is observed SHIF= -35 C SHIF= -35 C SHIF= 0 Supply more heat...
In certain application the process value is too unstable to be read. To improve this a programmable low pass filter incorporated in the controller can be used. This is a first order filter with time constant specified by parameter . The default value of FILT is 0.5 sec. before shipping.
The controller will enter as one of the following conditions occurs: occurs due to the input sensor break or input current below 1mA if 4-20 mA is selected or input voltage below 0.25V if 1-5 V is selected . occurs due to the A-D converter of the controller fails. The output 1 and output 2 will perform the function as the controller enters failure mode.
1. The system has been installed normally. 2. Set the correct values for the setup menu of the unit. But don't use a zero value for PB and TI, otherwise, the auto-tuning program will be disabled. The LOCK parameter should be set at NONE. 3.
The auto-tuning can be applied either as the process is warming up ( Cold Start ) or as the process has been in steady state ( Warm Start ). After the auto-tuning procedures are completed, the display will stop flashing and the unit will revert to PID control, using he new PID values.
CALIBRATION SHOULD BE DONE ONLY BY EXPERIENCED PERSONNEL WITH APPROPRIATE CALIBRATION EQUIPMENT . THE USE OF A CERTIFIED CALIBRATION LABORATORY IS HIGHLY RECOMMENDED. FOR DETAILED CALIBRATION INSTRUCTIONS, OR FOR ADDITIONAL INFORMATION, PLEASE CONTACT YOUR LOCAL EATON REPRESENTATIVE OR CALL EATON CARE AT 877-ETN-CARE. www.comoso.com...
Display Error Error Description Corrective Action Symbol Code Illegal setup values been used: Check and correct setup values of Before COOL is used for OUT2, OUT2, PB, TI and OUT1. IF OUT2 DIRT ( cooling action ) has already is required for cooling control, the been used for OUT1, or PID mode control should use PID mode ( PB is not used for OUT1 ( that is PB...
Eaton distributor or Eaton Care at 877-ETN-CARE. A charge is made for repairing after the expiration of the warranty. IN NO EVENT SHALL EATON BE LIABLE FOR CLAIMS BASED UPON BREACH OF EXPRESS OR IMPLIED WARRANTY OR NEGLIGENCE OR ANY...